Siemens 3RT2025-1AC20 Motor Contactor

Serie de productos: SIRIUS 3RT2 3-pole Power Contactor (Motor Contactor) Full Order No.: 3RT2025-1AC20 ✅ Model Code Explanation 3RT: SIRIUS contactor series 2: New generation SIRIUS Innovations 0: 3-pole motor contactor 25: S0 frame size, AC-3 17A, rated for 7.5kW motor at 400V 1: Built-in 1NO + 1NC auxiliary contacts A: AC coil C: 24V y, ...

  • Detalles del producto

Serie de productos: SIRIUS 3RT2 3-pole Power Contactor (Motor Contactor)

Full Order No.: 3RT2025-1AC20

✅ Explicación del código del modelo

3RT: SIRIUS contactor series

2: New generation SIRIUS Innovations

0: 3-pole motor contactor

25: S0 frame size, AC-3 17A, rated for 7.5kW motor at 400V

1: Built-in 1NO + 1CAROLINA DEL NORTE contactos auxiliares

A: bobina de CA

do: 24V y, 50/60Hz coil

20: Screw-type terminal

✅ Core Technical Specifications

ArtículoParámetro
Main Contacts Poles3PAG (3 normally-open main contacts)
Rated Current AC-317A @ 400V
Rated Current AC-1 (carga resistiva)40A
máx.. Voltaje de funcionamiento690V
Bobina24V y, 50/60Hz
Contactos auxiliares1NO + 1CAROLINA DEL NORTE
Tamaño del marcoS0
Tipo de cableadoTerminales de tornillo
MontajeMontaje en carril DIN
Clase de protecciónIP20 (frente / terminales)
Temperatura ambiente de funcionamiento-25℃ ~ +60℃
Vida mecánica10 millones de operaciones

✅ Typical Applications

Start/stop control of 3-phase asynchronous motors (fans, zapatillas, transportadores)

climatización, embalaje, machine tool automation control cabinets

Can be matched with 3RU2 thermal relays for motor overload protection; contactos auxiliares, surge suppressors and mechanical interlock modules can be added.

✅ Coil Variant Reference for Selection & Reemplazo

3RT2025-1AC20: 24V y

3RT2025-1AG20: 110V y

3RT2025-1AN20: 220V y

3RT2025-1AP00: 230V y

3RT2025-1BB40: 24En DC

✅ Replacement Information

  1. siemens internal replacement: Old model 3RT1025-1AC20 (interrumpido). Direct replacement with 3RT2025-1AC20, mounting dimensions are compatible.
  2. Domestic alternative reference: Chint NC1-18, Delixi CJX2-1810 (match coil voltage and confirm 1NO+1NC auxiliary contacts).

✅ Troubleshooting Guidelines

  1. Coil energized but no pull-in: Measure A1/A2 for 24V AC; check burnt coil and loose terminals.
  2. No output on main circuit after pull-in: Main contacts erosion, inspect L1/L2/L3 and T1/T2/T3.
  3. Quemado repetido de la bobina: Overvoltage or surge on coil circuit. RC snubber module is recommended for parallel connection.
  4. Abnormal auxiliary contacts: Auxiliary contacts worn out. External auxiliary contact modules can be fitted.

The built-in 1NO+1NC auxiliary contacts integrated inside 3RT2025-1AC20 cannot be replaced separately.

They are integrated into the contactor housing with no spare parts available. Once the built-in auxiliary contacts are damaged, the whole contactor must be replaced.

Distinguish two concepts:

  1. Contactos auxiliares incorporados (1NO+1NC): Integrated inside S0 frame body, non-detachable and non-replaceable individually.
  2. External add-on auxiliary contact modules (montado en el frente / side-mounted): Detachable and replaceable separately, classified as accessories.

📌 External Auxiliary Contact Module Selection (Desmontable & Reemplazable)

1) Montado en el frente (fit only 1 piece on front face)

3RH2911-1HA11: 1NO+1NC

3RH2911-1HA22: 2NO+2NC

2) Side-mounted (can be fitted on left or right side, máximo 2 piezas, one on each side)

3RH2921-1DA11: 1NO+1NC

3RH2921-1DA20: 2NO

3RH2921-1DA02: 2CAROLINA DEL NORTE

🛠️ Fault Handling Solutions

  1. Burnt built-in auxiliary contacts: No spare parts available; replace the entire 3RT2025-1AC20 contactor.
  2. Damaged external auxiliary contact module: Remove the faulty auxiliary contact module and replace it with the same model accessory; reuse the contactor body.
  3. Insufficient contact quantity: Add front/side mounted auxiliary contact modules listed above.

⚠️ Additional Remarks

For S0 frame (3RT2025), no separate spare main contact kits are available. The whole contactor needs replacement when main contacts are burned. Only S2 and larger frame contactors have independent spare main contacts.

Siemens 3RT2025-1AC20 Main Contacts vs Auxiliary Contacts

  1. Definición & Función

Contactos principales (L1/L2/L3 ↔ T1/T2/T3)

Función: Switch high-power main circuit, directly turn on/off motors and loads

Cantidad: 3 normally-open sets (3PAG)

Clasificación: AC-3 17A@400V for 7.5kW motor; AC-1 40A for resistive load

Circuito: High-power main circuit

Estructura: Oversized thick silver-alloy contacts with arc extinguishing chamber to withstand breaking arc under high current

Observación: marco S0, main contacts cannot be replaced individually. Full contactor replacement required after damage.

Contactos auxiliares (Built-in 1NO+1NC, expandable with 3RH accessories)

Función: Retroalimentación de señal, entrelazar, latching (control circuit logic, not for high-power load driving)

Cantidad: Built-in 1NO +1NC. Expandable by external modules

Clasificación: Low current, typically ≤6A for PLC input, relay coils and indicator lamps

Circuito: Low-power control circuit

Estructura: Small silver contacts without heavy-duty arc extinguishing, only for small current breaking

Observación: Built-in auxiliary contacts are integrated and non-replaceable; external 3RH auxiliary modules can be assembled and replaced individually.

  1. Tabla comparativa
Artículo de comparaciónContactos principalesBuilt-in Auxiliary Contacts
Marcado de terminalesL1/L2/L3, T1/T2/T313/14 (NO normalmente abierto), 21/22 (NC normalmente cerrado)
Capacidad de cargaHigh current for motors and heatersLow current only for signal, interlock and latching
Corriente nominalAC-3:17A @ 400VTypically 6A (AC-15)
Extinción de arcoWith arc chute for heavy arcNo heavy-duty arc suppression, only for minor arc
Individually Replaceable❌ No disponible (marco S0)❌ Built-in non-replaceable; ✅ External auxiliary modules replaceable
Uso típicoMain power supply switching for motorsContactor latching, running feedback, entrelazar, indicator lamp, PLC acquisition
  1. Ejemplo típico de cableado
  2. Contactos principales: 3-phase power supply feeds L1/L2/L3 on contactor top terminals; bottom terminals T1/T2/T3 connect to motor.
  3. Contactos auxiliares

13-14 (NO normalmente abierto): Latching circuit or send “contactor energized” feedback signal to PLC.

21-22 (NC normalmente cerrado): enclavamiento eléctrico (forward/reverse circuit, prevent simultaneous pull-in of two contactors causing 3-phase short circuit).

  1. Fault Differentiation

Main Contacts Failure: Motor weak rotation, pérdida de fase, overheating or arcing at terminals, load cannot power up normally.

Auxiliary Contacts Failure: Motor can start/stop normally, but latching fails, loss of feedback signal, interlock invalid. Main power circuit remains unaffected.

  1. Advertencia importante

Never use auxiliary contacts to switch motors, heaters or other high-power loads. Contact erosion will occur rapidly. High-power loads must be wired via main contacts.

Siemens 3RT2025-1AC20|Application Scenarios of Main Contacts and Auxiliary Contacts

  1. Contactos principales (L1/L2/L3 ↔ T1/T2/T3, 3 sets of high-power normally-open contacts)

Core purpose: Switch high-power main circuit and carry load operating current

✅ Applicable scenarios:

  1. Direct start-stop of 3-phase motors (más común): Zapatillas, fans, transportadores, compresores de aire, machine tool spindle motors. This model is rated for 7.5kW 400V 3-phase motors.
  2. 3-phase resistive load control: 3-phase heating elements, large 3-phase dehumidification heaters, max 40A under AC-1 rating.
  3. High-power switching in power distribution circuits: Power switching for heavy loads inside control cabinets.

❌ Not suitable for:

PLC signals, lámparas indicadoras, small relay coils and other low-current control circuits;

Logical interlock or status feedback.

Características: Equipped with arc extinguishing chamber and thick silver contacts, withstand motor inrush current and breaking arc.

  1. Contactos auxiliares (Built-in 1NO+1NC, terminales:13-14 NO,21-22 CAROLINA DEL NORTE; expandable with 3RH external modules)

Core purpose: Low-current signal in control circuit, only transmit logic status, no high-power load driving

✅ Normally Open NO (13-14) Escenarios típicos

  1. Contactor latching (self-holding): Maintain coil energized after releasing start pushbutton to keep motor running continuously.
  2. Running status feedback: Send signal to PLC, DIO module or indicator lamp for HMI to display “contactor pulled in, equipment running”.
  3. Sequential startup: Use NO contact to trigger coil of next relay/contactor after this contactor pulls in, to realize sequential start-up.

✅ Normally Closed NC (21-22) Escenarios típicos

  1. enclavamiento eléctrico (classic application): Connected in series to coil circuit of reverse contactor in forward/reverse control circuit, to avoid 3-phase short circuit caused by simultaneous pull-in of forward and reverse contactors.
  2. Falla / stop feedback: NC closed when contactor is open, used for stop status acquisition.
  3. Safety circuit interlock: NC contact conducts when contactor is de-energized, serving as ready signal.

Auxiliary contacts are low rated (AC-15 approx.6A), only for low-current control circuits. Do NOT use auxiliary contacts to directly control motors or high-power heating loads.

Quick Selection Rule

motores, high-power heaters, 3-phase power → Main Contacts

Enganche, entrelazar, PLC signal, running indicator lamp, logic linkage → Auxiliary Contacts

On-site Quick Fault Diagnosis

El motor no funciona, pérdida de fase, hot or arcing terminals → Most likely main contact fault

Motor can start and stop, but stops immediately once start button released, no running feedback, risk of short circuit due to failed interlock → Most likely auxiliary contact fault