Nombre completo del producto: Modicon Premium AS‑Interface V2 Master Module (AS-i Master)
It is a rack-mounted module for Premium (TSX57) SOCIEDAD ANÓNIMA. End-of-life (EOL: 2021‑01‑23), end of service: 2026‑12‑31. No recomendado para nuevos proyectos.; only available for spare parts and retrofit of legacy equipment.
- Definición del código del modelo
TSX: Prefix for Modicon Premium series
SAY: AS-i bus master module
1000: Version V2, supports standard and extended addressing
- Especificaciones principales
| Artículo | Parámetro |
| Bus Protocol | AS‑Interface V2, M2E profile |
| Addressing Mode | Standard addressing + extended addressing |
| Slave Capacity | Arriba a 31 slaves in standard mode; analog slaves available with extended addressing |
| Supported Slave Types | Discrete I/O (4I/3O, 4I/4O), AS-i analog slaves, AS-i safety interface slaves |
| Fuente de alimentación | Powered by Premium rack backplane |
| Backplane Current Draw | 450mA @5VDC |
| Interfaz | 3-pin male SUB-D, AS-i bus terminal |
| Peso | 0.34kilos |
| Max Modules per Rack | TSX570/TSX57C: 1 ordenador personal; TSX571: 2 piezas; TSX572: 4 piezas; TSX573~TSX576: arriba a 8 piezas |
| Panel frontal | LED de estado (PWR/OK/FAULT, A/B group), 32-point slave diagnostic LEDs, 2 botones de operación |
| Software de programación | unidad profesional |
| Código HS | 85389099 |
- Descripción de la función
- Acts as the AS-i bus master for Premium PLC to connect field AS-i sensors and actuators (interruptores de proximidad, válvulas solenoides, modular I/O, etc.), greatly simplifying field wiring.
- Front panel integrated diagnostic LEDs for quick troubleshooting of AS-i bus faults, slave disconnection and address conflicts.
- Supports acquisition from AS-i analog slaves, not limited to discrete signals only.
- Compatible with AS-i safety slaves (safety input / safety output).
- Modelo de reemplazo
Reemplazo oficial recomendado: BMXEIA0100 (M340 PLC AS-i Master Module)
Nota: Platform migration from Premium TSX57 to M340 requires rack, CPU and software replacement. It is not a direct plug-and-play replacement. For legacy systems, only used / surplus TSXSAY1000 can be sourced as spare parts.
- Instalación & Pautas de mantenimiento
- Instalación: DIN rail mounting in Premium rack, X-Bus backplane communication; Grado de protección IP20, solo para instalación en gabinete.
- AS-i Bus: Use dedicated AS-i yellow flat cable; AS-i power supply must be installed at both ends of the bus. SUB-D connector spare: Contacto Fénix 1841909, Schneider internal part number W815891970101A.
- Solución de problemas de fallas
FAULT red LED: Bus short circuit, corte de energía, duplicate slave address
A/B LED: Indicate AS-i A/B dual group slaves
32 LEDs: Corresponding slave online status; OFF = slave lost
- Second-hand Inspection Checklist
Power on and verify PWR/OK LED without faults
All front panel LEDs light normally, no damage
SUB-D connector free of oxidation and intact pins
Rack gold-plated contacts without burn marks
Perform bus scan test with AS-i power supply and AS-i slave
- Aclaración de conceptos erróneos comunes
❌ Not an analog output module. Some vendors incorrectly label it as AO module. It is an AS-i fieldbus communication master module.
TSXSAY1000 (Premium AS-i V2 Master Module) Casos de aplicación
Característica principal: TSXSAY1000 is the AS-i bus master mounted on Premium PLC rack. Suitable for scattered field I/O, large quantity of sensors, solenoid valves and safety signal acquisition. One AS-i yellow flat cable transmits data and power simultaneously, drastically reducing hardwiring work. All cases are legacy projects (Premium platform, Unity Pro programming), mainly for retrofit and maintenance of existing equipment. Premium platform is not recommended for new projects.
Caso 1: Automotive Component Assembly Line (Aplicación típica)
Descripción general del proyecto
Controlador principal: TSXP573623M Premium CPU + TSXSAY1000 AS-i master module for one assembly station bus
AS-i slaves: Proximity sensors, sensores fotoeléctricos, station pushbutton boxes, solenoid valve islands, AS-i safety slaves (puertas de seguridad, parada de emergencia)
I/O count: A/B dual group, around 42 AS-i slaves; includes discrete I/O and a small number of analog slaves (pressure sensor AS-i modules)
Arquitectura del sistema
Premium Rack (TSXP57+TSXSAY1000) → SUB-D Connector → AS-i Yellow Flat Cable → Field AS-i Slaves
Reason for TSXSAY1000 Selection
- Assembly stations are distributed. Traditional hardwiring requires separate cables from each sensor back to control cabinet, with high cost of cables, trunking and wiring labor. AS-i single cable connects all points in series.
- AS-i Safety support: Safety gate and E-stop signals transmitted via AS-i safety channel, natively supported by TSXSAY1000.
- Front panel 32-channel diagnostic LEDs allow maintenance personnel to identify offline slaves at a glance for fast fault location.
Lógica de control
Material presence detection at station, cylinder solenoid valve actuation, safety gate interlock, protección de parada de emergencia
Analog pressure acquisition (press-fit pressure) uploaded to PLC for press-fit judgment
Pain Points & Mantenimiento
Fallos: AS-i flat cable insulation damage, poor contact from piercing terminals. TSXSAY1000 FAULT LED alarm, read bus diagnostic word in Unity Pro.
Limitación: Max bus length ≤100m; AS-i repeater required for longer distance.
Retrofit Alternative
Full Premium platform replacement: M340 + BMXEIA0100 AS-i master
Caso 2: Food Packaging Line (Envolvedora de flujo horizontal / Case Packer)
Descripción general del proyecto
Premium TSXP57254M + TSXSAY1000; case conveying line with multi-section belt conveyors, material stop cylinders and detection photoelectric sensors
AS-i slaves: Sensores fotoeléctricos, material presence switches, válvulas solenoides, AS-i modular I/O
Process Requirement
Multi-section conveyor sorting, material detection, material stop and reject. Field I/O points scattered along long conveying line.
Ventajas
- Humid environment in packaging workshop. AS-i flat cable with piercing connection, fast wiring, M12 waterproof slaves.
- Simple configuration in Unity Pro for TSXSAY1000, automatic slave scan and I/O mapping.
- Add new slaves directly on AS-i bus when expanding stations, no massive recabling.
Typical Fault
Insufficient AS-i power capacity. Voltage drop occurs when multiple solenoid valves energize simultaneously, causing temporary slave dropout reported by TSXSAY1000.
Caso 3: Automated Warehouse Conveyance & Pallet Detection
Descripción general del proyecto
Pallet inbound conveyor section in automated warehouse, Premium PLC + TSXSAY1000 to manage scattered detection points on conveyor line
AS-i slaves: Pallet presence photoelectric sensors, position proximity switches, stop cylinder solenoid valves, pallet oversize detection
Proceso
Pallet inbound, position identification, stop and release. I/O points spread along long conveyor, control cabinet installed at one end of warehouse.
Justificación de la selección
Traditional point-to-point wiring incurs extremely high cable cost. AS-i cable routed along conveyor cable tray with single drop branches. TSXSAY1000 supports up to 62 discrete AS-i slaves, sufficient for one inbound conveyor line.
Nota: For multi-bus warehouse projects, multiple TSXSAY1000 modules can be installed on Premium rack (arriba a 8 modules for TSX573 and above) to expand multiple independent AS-i buses.
Caso 4: Valve Island & Level Switch Acquisition in Wastewater Treatment Plant (Industria de procesos)
Descripción general del proyecto
Wastewater pre-treatment, mechanical bar screens and sludge discharge valve banks; Premium PLC, TSXSAY1000, field AS-i valve islands + level switches
AS-i slaves: Pneumatic valve AS-i valve islands, level switches, flow switches, 4-20mA AS-i analog modules
Proceso
Bar screen start/stop, on/off control of sludge discharge valves, liquid level monitoring. Valve groups distributed around tanks under humid and corrosive environment.
Características
TSXSAY1000 supports AS-i analog slaves for direct acquisition of liquid level and pressure analog signals, eliminating large quantity of additional analog input modules.
Consideration
AS-i bus is not suitable for ultra-long distance wiring across tanks; AS-i repeater required if length exceeds 100m.
Summary of TSXSAY1000 Application Profile
✅ Escenarios adecuados
- Scattered field sensors and actuators, large volume of discrete I/O (fotoeléctrico, proximity, válvulas solenoides)
- Systems requiring AS-i safety bus (puertas de seguridad, parada de emergencia)
- Small volume analog acquisition (presión, liquid level via AS-i slaves)
- Retrofit and spare part replacement of legacy Premium systems
❌ Escenarios inadecuados
- High-speed process and heavy analog volume applications (Profibus / Modbus TCP preferred)
- Long bus distance (>100m without repeater)
- Nuevos proyectos (Premium platform EOL, M340+BMXEIA0100 recommended)
Configuration Guidelines (unidad profesional)
- Insert TSXSAY1000 into hardware tree of Premium rack
- Configure AS-i V2, estándar / extended addressing
- Bus scan to identify group A / B slaves
- Automatically map AS-i input and output to PLC internal variables
- Read module diagnostic word for SCADA alarm (bus fault, slave dropout)
Schneider Modicon Premium AS-i V2 Master Module TSXSAY1000 Full Technical Specifications
Posicionamiento del producto: AS‑Interface V2 fieldbus master module for Premium PLC rack. EOL, configured by Unity Pro software.
- Información básica
| Artículo | Parámetro |
| Modelo | TSXSAY1000 |
| Familia de productos | Modicon Premium (TSX57) |
| Tipo de módulo | AS‑Interface V2 Bus Master |
| AS-i Profile | M2E |
| Software | unidad profesional |
| Código HS | 85389099 |
| Peso neto | 0.34 kilos |
- Bus Communication Parameters
| Artículo | Parámetro |
| AS-i Version | AS‑Interface V2 |
| Addressing Mode | Standard addressing + extended addressing (A/B dual group) |
| Max Slave Quantity | Standard addressing: 31 unidades; extended addressing: 31 unidades; maximum total 62 discrete slaves |
| Supported Slave Types | Discrete I/O slaves (standard 4I/4O, extended 4I/3O), AS-i analog slaves, AS-i safety interface slaves (safety gate, parada de emergencia) |
| Bus Medium | AS-i dedicated yellow flat cable |
| Max Bus Length | 100metro (without repeater) |
| Bus Power | External independent AS-i power supply (backplane only supplies module itself, not AS-i bus power) |
- Parámetros eléctricos
| Artículo | Parámetro |
| Fuente de alimentación del módulo | Premium rack X-Bus backplane 5VDC |
| Backplane Current Consumption | 450mA @5VDC |
| Interfaz de autobús | 3-pin male SUB-D (AS-i+, AS-i-) |
- Rack Configuration (Max TSXSAY1000 Quantity per Premium CPU)
| CPU Model | Max TSXSAY1000 Quantity |
| TSX570 / TSX57C | 1 ordenador personal |
| TSX571 | 2 piezas |
| TSX572 | 4 piezas |
| TSX573 / TSX574 / TSX575 / TSX576 | 8 piezas |
- Front Panel LEDs & Operation Buttons
Indicadores LED de estado
- PWR OK (Verde): Backplane power supply of module normal
- FALLA (Rojo): AS-i bus fault, cortocircuito, slave loss, address conflict
- A/B (Verde): A-group / B-group slave group indicator
- 32 Diagnostic LEDs: No.0~31, slave online status; OFF = slave offline
Botones
- A/B: Toggle display between A-group and B-group slave status
- MODO: Offline / online switch, slave initialization, infrared address setting support
- Ambiental & Especificaciones mecánicas
| Artículo | Parámetro |
| Clase de protección | IP20 (cabinet use only) |
| Temperatura ambiente de funcionamiento | 0 ℃ ~ +60 ℃ |
| Temperatura de almacenamiento | -25 ℃ ~ +70 ℃ |
| Vibration Test | IEC 60068‑2‑6 Fc |
| Shock Test | IEC 60068‑2‑27 Ea |
| Método de montaje | Slot installation on Premium rack backplane |
- Aspectos destacados funcionales
- Supports AS-i Safety safety bus, safety slave connection for safety gate and emergency stop signal acquisition.
- Supports AS-i analog slaves for pressure, liquid level analog signal acquisition.
- Built-in bus diagnostics; diagnostic word readable in PLC program for SCADA alarm.
- Supports automatic bus scan, slave address detection and conflict detection.
- Limitation Notes
- ❗ Not an I/O module. It is a fieldbus communication master module without local I/O points.
- EOL spare part only, not recommended for new projects. Official hardware migration: M340 + BMXEIA0100.
- AS-i bus is not suitable for high-speed mass analog transmission; AS-i repeater required when bus length exceeds 100m.