Schneider TSXSAY1000 Master Module - contactor,cortacircuitos,sensor,Codificador,SOCIEDAD ANÓNIMA,Convertidor

chatear: +86-13184948252 Whatsapp: 0086-13811255435 Correo electrónico: kent@bestcontactor.com

Acerca de Contacto |

Schneider TSXSAY1000 Master Module - contactor,cortacircuitos,sensor,Codificador,SOCIEDAD ANÓNIMA,Convertidor

eléctrico/

Schneider TSXSAY1000 Master Module

Nombre completo del producto: Modicon Premium AS‑Interface V2 Master Module (AS-i Master) It is a rack-mounted module for Premium (TSX57) SOCIEDAD ANÓNIMA. End-of-life (EOL: 2021‑01‑23), end of service: 2026‑12‑31. No recomendado para nuevos proyectos.; only available for spare parts and retrofit of legacy equipment. Model Code Definition TSX: Prefix for Modicon Premium series SAY: AS-i bus master ...

  • Detalles del producto

Nombre completo del producto: Modicon Premium AS‑Interface V2 Master Module (AS-i Master)

It is a rack-mounted module for Premium (TSX57) SOCIEDAD ANÓNIMA. End-of-life (EOL: 2021‑01‑23), end of service: 2026‑12‑31. No recomendado para nuevos proyectos.; only available for spare parts and retrofit of legacy equipment.

  1. Definición del código del modelo

TSX: Prefix for Modicon Premium series

SAY: AS-i bus master module

1000: Version V2, supports standard and extended addressing

  1. Especificaciones principales
ArtículoParámetro
Bus ProtocolAS‑Interface V2, M2E profile
Addressing ModeStandard addressing + extended addressing
Slave CapacityArriba a 31 slaves in standard mode; analog slaves available with extended addressing
Supported Slave TypesDiscrete I/O (4I/3O, 4I/4O), AS-i analog slaves, AS-i safety interface slaves
Fuente de alimentaciónPowered by Premium rack backplane
Backplane Current Draw450mA @5VDC
Interfaz3-pin male SUB-D, AS-i bus terminal
Peso0.34kilos
Max Modules per RackTSX570/TSX57C: 1 ordenador personal; TSX571: 2 piezas; TSX572: 4 piezas; TSX573~TSX576: arriba a 8 piezas
Panel frontalLED de estado (PWR/OK/FAULT, A/B group), 32-point slave diagnostic LEDs, 2 botones de operación
Software de programaciónunidad profesional
Código HS85389099
  1. Descripción de la función
  2. Acts as the AS-i bus master for Premium PLC to connect field AS-i sensors and actuators (interruptores de proximidad, válvulas solenoides, modular I/O, etc.), greatly simplifying field wiring.
  3. Front panel integrated diagnostic LEDs for quick troubleshooting of AS-i bus faults, slave disconnection and address conflicts.
  4. Supports acquisition from AS-i analog slaves, not limited to discrete signals only.
  5. Compatible with AS-i safety slaves (safety input / safety output).
  6. Modelo de reemplazo

Reemplazo oficial recomendado: BMXEIA0100 (M340 PLC AS-i Master Module)

Nota: Platform migration from Premium TSX57 to M340 requires rack, CPU and software replacement. It is not a direct plug-and-play replacement. For legacy systems, only used / surplus TSXSAY1000 can be sourced as spare parts.

  1. Instalación & Pautas de mantenimiento
  2. Instalación: DIN rail mounting in Premium rack, X-Bus backplane communication; Grado de protección IP20, solo para instalación en gabinete.
  3. AS-i Bus: Use dedicated AS-i yellow flat cable; AS-i power supply must be installed at both ends of the bus. SUB-D connector spare: Contacto Fénix 1841909, Schneider internal part number W815891970101A.
  4. Solución de problemas de fallas

FAULT red LED: Bus short circuit, corte de energía, duplicate slave address

A/B LED: Indicate AS-i A/B dual group slaves

32 LEDs: Corresponding slave online status; OFF = slave lost

  1. Second-hand Inspection Checklist

Power on and verify PWR/OK LED without faults

All front panel LEDs light normally, no damage

SUB-D connector free of oxidation and intact pins

Rack gold-plated contacts without burn marks

Perform bus scan test with AS-i power supply and AS-i slave

  1. Aclaración de conceptos erróneos comunes

❌ Not an analog output module. Some vendors incorrectly label it as AO module. It is an AS-i fieldbus communication master module.

TSXSAY1000 (Premium AS-i V2 Master Module) Casos de aplicación

Característica principal: TSXSAY1000 is the AS-i bus master mounted on Premium PLC rack. Suitable for scattered field I/O, large quantity of sensors, solenoid valves and safety signal acquisition. One AS-i yellow flat cable transmits data and power simultaneously, drastically reducing hardwiring work. All cases are legacy projects (Premium platform, Unity Pro programming), mainly for retrofit and maintenance of existing equipment. Premium platform is not recommended for new projects.

Caso 1: Automotive Component Assembly Line (Aplicación típica)

Descripción general del proyecto

Controlador principal: TSXP573623M Premium CPU + TSXSAY1000 AS-i master module for one assembly station bus

AS-i slaves: Proximity sensors, sensores fotoeléctricos, station pushbutton boxes, solenoid valve islands, AS-i safety slaves (puertas de seguridad, parada de emergencia)

I/O count: A/B dual group, around 42 AS-i slaves; includes discrete I/O and a small number of analog slaves (pressure sensor AS-i modules)

Arquitectura del sistema

Premium Rack (TSXP57+TSXSAY1000) → SUB-D Connector → AS-i Yellow Flat Cable → Field AS-i Slaves

Reason for TSXSAY1000 Selection

  1. Assembly stations are distributed. Traditional hardwiring requires separate cables from each sensor back to control cabinet, with high cost of cables, trunking and wiring labor. AS-i single cable connects all points in series.
  2. AS-i Safety support: Safety gate and E-stop signals transmitted via AS-i safety channel, natively supported by TSXSAY1000.
  3. Front panel 32-channel diagnostic LEDs allow maintenance personnel to identify offline slaves at a glance for fast fault location.

Lógica de control

Material presence detection at station, cylinder solenoid valve actuation, safety gate interlock, protección de parada de emergencia

Analog pressure acquisition (press-fit pressure) uploaded to PLC for press-fit judgment

Pain Points & Mantenimiento

Fallos: AS-i flat cable insulation damage, poor contact from piercing terminals. TSXSAY1000 FAULT LED alarm, read bus diagnostic word in Unity Pro.

Limitación: Max bus length ≤100m; AS-i repeater required for longer distance.

Retrofit Alternative

Full Premium platform replacement: M340 + BMXEIA0100 AS-i master

Caso 2: Food Packaging Line (Envolvedora de flujo horizontal / Case Packer)

Descripción general del proyecto

Premium TSXP57254M + TSXSAY1000; case conveying line with multi-section belt conveyors, material stop cylinders and detection photoelectric sensors

AS-i slaves: Sensores fotoeléctricos, material presence switches, válvulas solenoides, AS-i modular I/O

Process Requirement

Multi-section conveyor sorting, material detection, material stop and reject. Field I/O points scattered along long conveying line.

Ventajas

  1. Humid environment in packaging workshop. AS-i flat cable with piercing connection, fast wiring, M12 waterproof slaves.
  2. Simple configuration in Unity Pro for TSXSAY1000, automatic slave scan and I/O mapping.
  3. Add new slaves directly on AS-i bus when expanding stations, no massive recabling.

Typical Fault

Insufficient AS-i power capacity. Voltage drop occurs when multiple solenoid valves energize simultaneously, causing temporary slave dropout reported by TSXSAY1000.

Caso 3: Automated Warehouse Conveyance & Pallet Detection

Descripción general del proyecto

Pallet inbound conveyor section in automated warehouse, Premium PLC + TSXSAY1000 to manage scattered detection points on conveyor line

AS-i slaves: Pallet presence photoelectric sensors, position proximity switches, stop cylinder solenoid valves, pallet oversize detection

Proceso

Pallet inbound, position identification, stop and release. I/O points spread along long conveyor, control cabinet installed at one end of warehouse.

Justificación de la selección

Traditional point-to-point wiring incurs extremely high cable cost. AS-i cable routed along conveyor cable tray with single drop branches. TSXSAY1000 supports up to 62 discrete AS-i slaves, sufficient for one inbound conveyor line.

Nota: For multi-bus warehouse projects, multiple TSXSAY1000 modules can be installed on Premium rack (arriba a 8 modules for TSX573 and above) to expand multiple independent AS-i buses.

Caso 4: Valve Island & Level Switch Acquisition in Wastewater Treatment Plant (Industria de procesos)

Descripción general del proyecto

Wastewater pre-treatment, mechanical bar screens and sludge discharge valve banks; Premium PLC, TSXSAY1000, field AS-i valve islands + level switches

AS-i slaves: Pneumatic valve AS-i valve islands, level switches, flow switches, 4-20mA AS-i analog modules

Proceso

Bar screen start/stop, on/off control of sludge discharge valves, liquid level monitoring. Valve groups distributed around tanks under humid and corrosive environment.

Características

TSXSAY1000 supports AS-i analog slaves for direct acquisition of liquid level and pressure analog signals, eliminating large quantity of additional analog input modules.

Consideration

AS-i bus is not suitable for ultra-long distance wiring across tanks; AS-i repeater required if length exceeds 100m.

Summary of TSXSAY1000 Application Profile

✅ Escenarios adecuados

  1. Scattered field sensors and actuators, large volume of discrete I/O (fotoeléctrico, proximity, válvulas solenoides)
  2. Systems requiring AS-i safety bus (puertas de seguridad, parada de emergencia)
  3. Small volume analog acquisition (presión, liquid level via AS-i slaves)
  4. Retrofit and spare part replacement of legacy Premium systems

❌ Escenarios inadecuados

  1. High-speed process and heavy analog volume applications (Profibus / Modbus TCP preferred)
  2. Long bus distance (>100m without repeater)
  3. Nuevos proyectos (Premium platform EOL, M340+BMXEIA0100 recommended)

Configuration Guidelines (unidad profesional)

  1. Insert TSXSAY1000 into hardware tree of Premium rack
  2. Configure AS-i V2, estándar / extended addressing
  3. Bus scan to identify group A / B slaves
  4. Automatically map AS-i input and output to PLC internal variables
  5. Read module diagnostic word for SCADA alarm (bus fault, slave dropout)

Schneider Modicon Premium AS-i V2 Master Module TSXSAY1000 Full Technical Specifications

Posicionamiento del producto: AS‑Interface V2 fieldbus master module for Premium PLC rack. EOL, configured by Unity Pro software.

  1. Información básica
ArtículoParámetro
ModeloTSXSAY1000
Familia de productosModicon Premium (TSX57)
Tipo de móduloAS‑Interface V2 Bus Master
AS-i ProfileM2E
Softwareunidad profesional
Código HS85389099
Peso neto0.34 kilos
  1. Bus Communication Parameters
ArtículoParámetro
AS-i VersionAS‑Interface V2
Addressing ModeStandard addressing + extended addressing (A/B dual group)
Max Slave QuantityStandard addressing: 31 unidades; extended addressing: 31 unidades; maximum total 62 discrete slaves
Supported Slave TypesDiscrete I/O slaves (standard 4I/4O, extended 4I/3O), AS-i analog slaves, AS-i safety interface slaves (safety gate, parada de emergencia)
Bus MediumAS-i dedicated yellow flat cable
Max Bus Length100metro (without repeater)
Bus PowerExternal independent AS-i power supply (backplane only supplies module itself, not AS-i bus power)
  1. Parámetros eléctricos
ArtículoParámetro
Fuente de alimentación del móduloPremium rack X-Bus backplane 5VDC
Backplane Current Consumption450mA @5VDC
Interfaz de autobús3-pin male SUB-D (AS-i+, AS-i-)
  1. Rack Configuration (Max TSXSAY1000 Quantity per Premium CPU)
CPU ModelMax TSXSAY1000 Quantity
TSX570 / TSX57C1 ordenador personal
TSX5712 piezas
TSX5724 piezas
TSX573 / TSX574 / TSX575 / TSX5768 piezas
  1. Front Panel LEDs & Operation Buttons

Indicadores LED de estado

  1. PWR OK (Verde): Backplane power supply of module normal
  2. FALLA (Rojo): AS-i bus fault, cortocircuito, slave loss, address conflict
  3. A/B (Verde): A-group / B-group slave group indicator
  4. 32 Diagnostic LEDs: No.0~31, slave online status; OFF = slave offline

Botones

  1. A/B: Toggle display between A-group and B-group slave status
  2. MODO: Offline / online switch, slave initialization, infrared address setting support
  3. Ambiental & Especificaciones mecánicas
ArtículoParámetro
Clase de protecciónIP20 (cabinet use only)
Temperatura ambiente de funcionamiento0 ℃ ~ +60 ℃
Temperatura de almacenamiento-25 ℃ ~ +70 ℃
Vibration TestIEC 60068‑2‑6 Fc
Shock TestIEC 60068‑2‑27 Ea
Método de montajeSlot installation on Premium rack backplane
  1. Aspectos destacados funcionales
  2. Supports AS-i Safety safety bus, safety slave connection for safety gate and emergency stop signal acquisition.
  3. Supports AS-i analog slaves for pressure, liquid level analog signal acquisition.
  4. Built-in bus diagnostics; diagnostic word readable in PLC program for SCADA alarm.
  5. Supports automatic bus scan, slave address detection and conflict detection.
  6. Limitation Notes
  7. ❗ Not an I/O module. It is a fieldbus communication master module without local I/O points.
  8. EOL spare part only, not recommended for new projects. Official hardware migration: M340 + BMXEIA0100.
  9. AS-i bus is not suitable for high-speed mass analog transmission; AS-i repeater required when bus length exceeds 100m.

Anterior:

Próximo:

Deja una respuesta