3RT1064-6AP36
- 3RT: SIRIUS Electromagnetic Contactor Serie
- 1: Classic imported SIRIUS 3RT1 Series (Equivalente nacional: 3RT5/3RT6)
- 0: 3-pole contactor for motor loads (3SIN contactos principales)
- 64: Frame Size S10, AC-3 rated current 225 A
- 6: Conventional electromagnetic operating mechanism (non-electronic coil)
- A: Coil voltage code → AC/DC 220~240 V (Bobina universal CA/CC)
- PAG: Main circuit busbar connection
- 36: Permanently built-in auxiliary contacts 2NO + 2CAROLINA DEL NORTE
Descripción completa: 3-pole power contactor, Frame S10, busbar terminals, 220~240 V AC/DC coil, fijado 2 Normalmente abierto + 2 Normally Closed auxiliary contacts.
- Main Electrical Specifications
| Artículo | Parámetro |
| Configuración del contacto principal | 3P Normally Open (3NO) |
| Rated operational current AC-3 / AC-3e @400 V | 225 A |
| Rated motor power (3-fase, 400 V) | 110 kilovatios |
| Rated operational current AC-4 @400 V | 195 A |
| Tensión de la bobina de control | UC = 220~240 V AC/DC (Universal AC & corriente continua) |
| Coil operating range | 0.7~1.25 × rated voltage |
| Contactos auxiliares estándar | 2NO + 2CAROLINA DEL NORTE (Incorporado, no removible) |
| Tamaño del marco | S10 |
| Conexión del circuito principal | Busbar connection (fijación con pernos) |
| Auxiliar & coil connection | Terminales de tornillo |
| Tensión nominal de aislamiento | 1000 V |
| Grado de contaminación | 3 |
Cable Connection Capacity
Circuito principal: Stranded cable 70~240 mm²
circuito auxiliar: 0.5~4 mm²
- Outline & Installation Information
Método de montaje: Base plate screw mounting (DIN rail mounting NOT supported; large S10 frame can only be fixed to cabinet base plate)
Front protection class: IP00
Temperatura ambiente de funcionamiento: -25℃ ~ +60℃ (full-load operation at 60℃)
- Escenarios de aplicación típicos
Direct-on-line starting of 3-phase induction motors, main contactor for star-delta starters, VFD bypass
Compresores de aire, bombas de agua, fans, máquinas de moldeo por inyección, high-power production line drives
climatización, central eléctrica, metalurgia, port crane power circuits
⚠️ Not recommended for long-term inching operation under AC-4 duty; select higher frame size for frequent start-stop applications.
- Alternative Selection Reference
1) Direct OEM replacement (Siemens original)
3RT1064-6AP36 (modelo de sujeto, 220~240 V AC/DC coil)
Coil voltage variants:
3RT1064-6AP36 = 220~240 V AC/DC
3RT1064-6BP36 = 110~127 V AC/DC
2) Alternativa mejorada
3RT1065-6AP36: Frame S10, AC-3 265 A (Higher capacity, dimensiones de montaje idénticas)
⚠️ Important distinction: 3RT12xx series are vacuum contactors with different construction; not directly interchangeable.
Domestic economical model: 3RT5064 (AC-only coil, different terminal structure; cannot directly replace imported busbar-type 3RT1064).
- Selection Pitfall Reminders
- Main circuit adopts busbar connection, not cable terminals; terminal adapter accessories are required if cable wiring is needed.
- S10 frame without DIN rail base, only base plate mounting available.
- Bobina universal CA/CC; compatible with both AC230 V control and DC220 V control circuits.
- Auxiliary contacts 2NO+2NC are permanently built-in, cannot be removed or reconfigured freely.
- Standard ordering designation with hyphen: 3RT1064-6AP36, do not omit the hyphen.
- Optional Compatible Accessories
3RU thermal overload relays (S10 frame rating)
Surge suppressors (RC network, varistor for coil protection)
Mechanical interlock kits (for forward/reversing contactor pairs)
Main circuit terminal adapters (cable-to-busbar transition)
Mounting Dimensions – Siemens 3RT1064-6AP36 (Frame S10)
Important Precondition: DIN rail mounting is not supported; only base plate bolt mounting
- Overall Outer Dimensions (Ancho × Alto × Fondo, milímetros)
Ancho W: 145 milímetros
Height H: 210 milímetros
Depth D: 202 milímetros (cabinet internal depth occupation)
- Base Plate Mounting Hole Dimensions (Critical for cabinet sheet metal processing)
4 fixing through holes, bolt specification: M8
- Distancia entre centros horizontales (left-right): 124 milímetros
- Distancia al centro vertical (up-down): 186 milímetros
- Diámetro del orificio de montaje: Φ9 mm (for M8 bolts)
Bounding outline of mounting hole centers: 124 milímetros (W.) × 186 milímetros (h)
- Wiring Clearance for Main Circuit Busbar
Main terminals exposed on top and bottom for busbar installation:
Phase spacing: 50 milímetros
Terminal bolt: M12
Recommended maximum busbar thickness ≤12 mm
- Minimum Cabinet Installation Clearance (Siemens official heat dissipation specification)
Top clearance above contactor: ≥10 mm
Bottom clearance below contactor: ≥10 mm
Left & right side clearance: ≥10 mm
Front clearance (towards arc shield): ≥20 mm
Insufficient clearance causes temperature rise and derated operation.
- Peso
Net weight of unit: aprox. 7.8 kilos
- Supplementary Installation Notes
- 3RT1064-6AP36 = busbar connection version. Cable-terminated models of the same frame share identical overall dimensions, only terminal structure differs.
- 3RT1065 (265 A) of the same series uses S10 frame; mounting dimensions are fully interchangeable, base plate hole layout can be reused.
- Minimum center-to-center distance between two side-by-side contactors with mechanical interlock for forward/reversing circuit: 150 milímetros.
- For continuous full-load operation above 40℃ ambient temperature, expand surrounding heat dissipation clearance to minimum 15 milímetros.
Service Life Parameters – Siemens 3RT1064-6AP36 (Frame S10)
- Vida útil mecánica (Typical value from official datasheet)
Resistencia mecánica: 10,000,000 ciclos de operación (10 millones de veces)
Definición: No-load open/close cycles without main circuit load. Built-in standard mechanical auxiliary contacts (2NO+2NC) do not reduce mechanical life.
⚠️ Distinction:
If electronic auxiliary modules are fitted → mechanical endurance reduced to 5,000,000 ciclos.
Standard built-in 2NO+2NC mechanical auxiliary contacts of this model are not subject to this limitation.
- Vida útil eléctrica (Contactos principales, key reference for selection)
Duty condition: AC-3, 400 V, normal motor start-stop (breaking 6×Ie starting current)
Electrical endurance ≈ 200,000 ciclos (200,000 veces)
AC-4 inching duty (rotor bloqueado, frequent reversing): Electrical life drops significantly, typically limited to tens of thousands of cycles. Select higher-rated contactor or dedicated AC-4 contactor for frequent jogging applications.
- Key Supplementary Notes
- Mechanical life ≠ Electrical life
Mechanical endurance reflects durability of magnetic core, springs and transmission mechanism; electrical endurance is limited by contact arc erosion. In most operating conditions, electrical service life expires first.
- Environmental Influences
Temperatura alta, polvo, humedad, coil voltage deviation and vibration will shorten both mechanical and electrical service life.
- Maximum Permissible Operating Frequency
Servicio estándar: ≤1200 cycles/hour. Exceeding this frequency requires current derating, resulting in aggravated temperature rise and accelerated service life reduction.
- Interchangeability within Frame
All S10 frame contactors including 3RT1064 / 3RT1065 share uniform mechanical endurance of 10 millones de ciclos, applicable for reference.