The ACS580-01-087A-4 is a standard wall-mounted single drive unit depuis ABB’s ACS580 series, rated for three-phase 380–480V AC input. This drive series features user-friendly operation, high reliability and superior energy efficiency as core advantages. Multiple standard built-in functions eliminate the need for extra optional components, enabling rapid commissioning and deployment. Widely compatible with general industrial loads such as pumps, les fans, conveyors and mixers, it is the preferred solution for light industry, building HVAC, water treatment and other applications.
Breakdown of Model Code
Per ABB official naming convention, each segment of the model designation is defined as follows:
ACS580: Identifiant de la série de produits, representing ABB’s general-purpose standard drive series covering power ratings from 0.75kW to 500kW
-01: Construction type, standing for wall-mounted standard single drive. Standard equipment includes IP21 enclosure rating, Assistant Control Panel, built-in Class C2 EMC filter, Coupure sûre du couple (STO), braking chopper and triple-protection coated circuit boards
-087UN: Rated output current marking, indicating the nominal rated output current of the drive is 87A
-4: Classe de tension, denoting three-phase 380V–480V AC input, compatible with 50/60Hz mains power grids
Spécifications techniques de base
Caractéristiques électriques
| Paramètre | Spécification | Remarques |
| Plage de tension d'entrée | 3-phase AC 380V ~ 480V | Tolerance: +10% / -15% |
| Fréquence d'entrée | 50/60Hz | Tolerance: ±5% |
| Courant de sortie nominal | 87UN | Nominal value for light-duty applications |
| Puissance moteur adaptée (Travaux légers) | 45kW | For variable-torque loads (les fans, pompes à eau) |
| Puissance moteur adaptée (Robuste) | 37kW | For constant-torque loads (transmettre, mixing) |
| Plage de fréquence de sortie | 0 ~ 500Hz | Supports high-speed motor operation |
| Input Power Factor | ≥0.98 | High power factor across full power range |
| Overall Efficiency | ≥98% | At rated operating conditions |
| Capacité de surcharge | 150% courant nominal pendant 60 s | One overload cycle permitted every 10 minutes |
| 110% rated current continuously |
Contrôle & Spécifications des interfaces
Motor Control Modes: Scalar V/F control, contrôle vectoriel sans capteur; compatible with induction motors, permanent magnet synchronous motors and synchronous reluctance motors
Dimensions physiques & Spécifications environnementales
Taille du cadre: R5
Dimensions hors tout (H × W × D): 896mm × 345mm × 293mm
Poids net: Environ. 23kilos
Enclosure Rating: IP21 (standard); IP55 high-protection version available as option
Type de montage: Montage mural, side-by-side compact installation supported
Température ambiante de fonctionnement: -15℃ ~ +50℃ (déclassement requis au-dessus de 40 ℃)
Stockage & Transport Temperature: -40℃ ~ +70℃
Humidité relative: 5% ~ 95%, sans condensation
Altitude Rating: Full power output up to 1000m; 1% power derating per additional 100m above 1000m
Code SH: 85044088
Configuration standard & Accessoires en option
Factory Standard Equipment
- ACS-AP-S Assistant Control Panel (Chinese language supported)
- Built-in Class C2 EMC Filter
- Integrated Braking Chopper
- Coupure sûre du couple (STO) Fonction
- Triple-protection Coated Printed Circuit Boards
- Bottom Cable Entry Compartment
- Multilingual Quick Installation & Commissioning Manual
Common Optional Accessories
Enclosure Upgrade: IP55 protective enclosure, flange mounting kit
Communication Extensions: Fieldbus adapters including Profibus DP, Profinet IO, EtherNet/IP, Modbus-TCP
Electrical Options: Input reactors, output reactors, du/dt filters, sine-wave filters, braking resistors
Functional Extensions: I/O expansion modules, temperature sensor interface cards, NETA-21 remote monitoring module
Software Tools: Drive Composer professional commissioning software
Scénarios d'application typiques
Water Treatment Industry: Clean water pumps, pompes à eaux usées, aeration fans, sludge mixers
Building HVAC: Chilled water pumps, cooling water pumps, supply & exhaust fans for central air conditioning
Fabrication légère: Convoyeurs à bande, packaging production lines, mixing & équipement de mélange, compresseurs d'air
Métallurgie & Exploitation minière: Dust extraction fans, material transport belts, pompes de drainage minier
Ingénierie municipale: Water supply pumping stations, ventilation systems for wastewater treatment plants
Common Troubleshooting Matrix
| Phénomène de défaut | Root Causes | Step-by-Step Remedial Actions |
| Overcurrent Trip (Code d'erreur 0001) | Short circuit in motor/cables, sudden load surge, overly short acceleration time | 1. Cut power and test insulation & wiring of motor and power cables |
| 2. Appropriately extend acceleration time parameter | ||
| 3. Verify consistency between motor rated parameters and drive settings | ||
| DC Overvoltage Trip (Code d'erreur 0002) | Excessively high mains voltage, overly short deceleration time, faulty braking circuit | 1. Measure input mains voltage to confirm it falls within allowable range |
| 2. Extend deceleration time or enable DC braking function | ||
| 3. Check wiring and resistance value of braking resistor for matching | ||
| Déclenchement sous-tension (Code d'erreur 0003) | Single-phase power loss, blown input fuses, excessively low mains voltage | 1. Inspect three-phase input power to eliminate phase loss issues |
| 2. Check status of input fuses / disjoncteurs | ||
| 3. Confirm on-site mains voltage meets equipment requirements | ||
| Motor Overload Alarm (Code d'erreur 0005) | Jammed mechanical load, incorrect motor parameters, sustained overload operation | 1. Cut power and rotate motor shaft manually to check mechanical smoothness |
| 2. Re-run motor identification auto-tune | ||
| 3. Evaluate actual load conditions and upsize drive model if necessary | ||
| Défaut de surchauffe (Code d'erreur 0009) | Température ambiante trop élevée, blocked cooling air ducts, faulty cooling fan | 1. Clear dust buildup on drive air intake cooling grille |
| 2. Verify normal operation of cooling fan | ||
| 3. Improve cabinet ventilation and lower ambient temperature |
Detailed List of Standard Accessories for ABB ACS580-01-087A-4 (Frame R5 / IP21 Version)
This model is a standard wall-mounted unit of ACS580 Frame R5. Factory supply contents are split into built-in onboard functions and physical accessories supplied in carton. Below is a detailed breakdown of the official standard supply scope:
- Standard Built-in Onboard Functions (Intégré, No Extra Fitting Required)
All functions below are factory pre-configured and ready for direct use without purchasing extra options:
- EMC Components: Built-in Class C2 EMC filter to meet industrial site electromagnetic compatibility requirements
- Braking Circuit: Integrated braking chopper allowing direct connection of braking resistors for fast deceleration
- Safety Function: Coupure sûre du couple (STO) compliant with PL e / SIL 3 safety level
- Protection de l'environnement: Full triple-protection coating on control and power boards, resistant to humid, dusty and corrosive gas environments
- Standard Control Interfaces: 6 entrées numériques, 2 sorties numériques, 2 entrées analogiques, 1 sortie analogique
- Basic Communications: Embedded RS-485 hardware port with native Modbus RTU protocol support
- Conception structurelle: Bottom cable entry compartment supporting standardized wiring and cable ingress protection
- Physical Standard Carton Accessories (Separately Packed Inside Shipment Box)
Independent accessories available upon unpacking for installation and basic commissioning:
- ACS-AP-S Assistant Control Panel (Chinese version): Equipped with LCD screen and full-function keys for parameter setup, status monitoring and fault diagnosis; pluggable onto drive front panel and supplied in separate packaging
- Wall Mounting Template: 1:1 paper drilling positioning template for marking mounting hole positions on-site to reduce drilling errors
- Cable Junction Box Assembly: Standard for Frame R5 IP21 units, including power cable grounding brackets, control cable shielding clamps and assembly fasteners
- Mounting Fastener Kit: M6 bolts, nuts and other metal hardware for wall mounting fixation
- Ground Terminals & Cable Crimp Accessories: Dedicated main circuit grounding terminals and auxiliary crimp fittings for control terminals
III. Supplied Documentation & Identification Labels
- Quick Installation and Startup Guide: Multilingual edition (including Chinese) covering full procedures of wiring, power-up and basic commissioning
- Safety Warning Stickers: Multilingual residual voltage warning labels to be affixed near equipment to alert maintenance personnel
- Product Certificate of Conformity and Warranty Document
Note: Full hardware manuals and firmware parameter manuals are not supplied as standard; downloadable via ABB official website or available as separate printed copies upon order.
- Packaging Auxiliary Protection Materials
Standard industrial shipping packaging for logistics protection, not classified as drive accessories:
VCI vapor corrosion inhibitor anti-rust bag
Paper buffer liners and corner protectors
Strapping bands
Shipping pallet (for full carton industrial packaging specifications)
- Non-Standard Optional Components Requiring Separate Ordering
Items below are excluded from standard supply scope and must be purchased separately per project demands:
Enclosure Upgrade: IP55 protective enclosure, flange mounting kit
Communication Extensions: Fieldbus adapters including Profibus DP, Profinet IO, EtherNet/IP, Modbus-TCP
Electrical Matching Components: Input reactors, output reactors, du/dt filters, sine-wave filters, braking resistors
Functional Extensions: I/O expansion modules, cartes d'interface d'encodeur, temperature sensor interface cards, remote monitoring modules
Software Tools: Drive Composer professional commissioning software, USB commissioning cable
Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires





















NH42-63-318x560.png)