ABB ACS580-01-087A-4 Variable Frequency Drive

The ACS580-01-087A-4 is a standard wall-mounted single drive unit from ABB’s ACS580 series, rated for three-phase 380–480V AC input. This drive series features user-friendly operation, high reliability and superior energy efficiency as core advantages. Multiple standard built-in functions eliminate the need for extra optional components, enabling rapid commissioning and deployment. Widely compatible with general industrial ...

  • Détails du produit

The ACS580-01-087A-4 is a standard wall-mounted single drive unit depuis ABB’s ACS580 series, rated for three-phase 380–480V AC input. This drive series features user-friendly operation, high reliability and superior energy efficiency as core advantages. Multiple standard built-in functions eliminate the need for extra optional components, enabling rapid commissioning and deployment. Widely compatible with general industrial loads such as pumps, les fans, conveyors and mixers, it is the preferred solution for light industry, building HVAC, water treatment and other applications.

Breakdown of Model Code

Per ABB official naming convention, each segment of the model designation is defined as follows:

ACS580: Identifiant de la série de produits, representing ABB’s general-purpose standard drive series covering power ratings from 0.75kW to 500kW

-01: Construction type, standing for wall-mounted standard single drive. Standard equipment includes IP21 enclosure rating, Assistant Control Panel, built-in Class C2 EMC filter, Coupure sûre du couple (STO), braking chopper and triple-protection coated circuit boards

-087UN: Rated output current marking, indicating the nominal rated output current of the drive is 87A

-4: Classe de tension, denoting three-phase 380V–480V AC input, compatible with 50/60Hz mains power grids

Spécifications techniques de base

Caractéristiques électriques

ParamètreSpécificationRemarques
Plage de tension d'entrée3-phase AC 380V ~ 480VTolerance: +10% / -15%
Fréquence d'entrée50/60HzTolerance: ±5%
Courant de sortie nominal87UNNominal value for light-duty applications
Puissance moteur adaptée (Travaux légers)45kWFor variable-torque loads (les fans, pompes à eau)
Puissance moteur adaptée (Robuste)37kWFor constant-torque loads (transmettre, mixing)
Plage de fréquence de sortie0 ~ 500HzSupports high-speed motor operation
Input Power Factor≥0.98High power factor across full power range
Overall Efficiency≥98%At rated operating conditions
Capacité de surcharge150% courant nominal pendant 60 sOne overload cycle permitted every 10 minutes
110% rated current continuously

Contrôle & Spécifications des interfaces

Motor Control Modes: Scalar V/F control, contrôle vectoriel sans capteur; compatible with induction motors, permanent magnet synchronous motors and synchronous reluctance motors

Dimensions physiques & Spécifications environnementales

Taille du cadre: R5

Dimensions hors tout (H × W × D): 896mm × 345mm × 293mm

Poids net: Environ. 23kilos

Enclosure Rating: IP21 (standard); IP55 high-protection version available as option

Type de montage: Montage mural, side-by-side compact installation supported

Température ambiante de fonctionnement: -15℃ ~ +50℃ (déclassement requis au-dessus de 40 ℃)

Stockage & Transport Temperature: -40℃ ~ +70℃

Humidité relative: 5% ~ 95%, sans condensation

Altitude Rating: Full power output up to 1000m; 1% power derating per additional 100m above 1000m

Code SH: 85044088

Configuration standard & Accessoires en option

Factory Standard Equipment

  1. ACS-AP-S Assistant Control Panel (Chinese language supported)
  2. Built-in Class C2 EMC Filter
  3. Integrated Braking Chopper
  4. Coupure sûre du couple (STO) Fonction
  5. Triple-protection Coated Printed Circuit Boards
  6. Bottom Cable Entry Compartment
  7. Multilingual Quick Installation & Commissioning Manual

Common Optional Accessories

Enclosure Upgrade: IP55 protective enclosure, flange mounting kit

Communication Extensions: Fieldbus adapters including Profibus DP, Profinet IO, EtherNet/IP, Modbus-TCP

Electrical Options: Input reactors, output reactors, du/dt filters, sine-wave filters, braking resistors

Functional Extensions: I/O expansion modules, temperature sensor interface cards, NETA-21 remote monitoring module

Software Tools: Drive Composer professional commissioning software

Scénarios d'application typiques

Water Treatment Industry: Clean water pumps, pompes à eaux usées, aeration fans, sludge mixers

Building HVAC: Chilled water pumps, cooling water pumps, supply & exhaust fans for central air conditioning

Fabrication légère: Convoyeurs à bande, packaging production lines, mixing & équipement de mélange, compresseurs d'air

Métallurgie & Exploitation minière: Dust extraction fans, material transport belts, pompes de drainage minier

Ingénierie municipale: Water supply pumping stations, ventilation systems for wastewater treatment plants

Common Troubleshooting Matrix

Phénomène de défautRoot CausesStep-by-Step Remedial Actions
Overcurrent Trip (Code d'erreur 0001)Short circuit in motor/cables, sudden load surge, overly short acceleration time1. Cut power and test insulation & wiring of motor and power cables
2. Appropriately extend acceleration time parameter
3. Verify consistency between motor rated parameters and drive settings
DC Overvoltage Trip (Code d'erreur 0002)Excessively high mains voltage, overly short deceleration time, faulty braking circuit1. Measure input mains voltage to confirm it falls within allowable range
2. Extend deceleration time or enable DC braking function
3. Check wiring and resistance value of braking resistor for matching
Déclenchement sous-tension (Code d'erreur 0003)Single-phase power loss, blown input fuses, excessively low mains voltage1. Inspect three-phase input power to eliminate phase loss issues
2. Check status of input fuses / disjoncteurs
3. Confirm on-site mains voltage meets equipment requirements
Motor Overload Alarm (Code d'erreur 0005)Jammed mechanical load, incorrect motor parameters, sustained overload operation1. Cut power and rotate motor shaft manually to check mechanical smoothness
2. Re-run motor identification auto-tune
3. Evaluate actual load conditions and upsize drive model if necessary
Défaut de surchauffe (Code d'erreur 0009)Température ambiante trop élevée, blocked cooling air ducts, faulty cooling fan1. Clear dust buildup on drive air intake cooling grille
2. Verify normal operation of cooling fan
3. Improve cabinet ventilation and lower ambient temperature

Detailed List of Standard Accessories for ABB ACS580-01-087A-4 (Frame R5 / IP21 Version)

This model is a standard wall-mounted unit of ACS580 Frame R5. Factory supply contents are split into built-in onboard functions and physical accessories supplied in carton. Below is a detailed breakdown of the official standard supply scope:

  1. Standard Built-in Onboard Functions (Intégré, No Extra Fitting Required)

All functions below are factory pre-configured and ready for direct use without purchasing extra options:

  1. EMC Components: Built-in Class C2 EMC filter to meet industrial site electromagnetic compatibility requirements
  2. Braking Circuit: Integrated braking chopper allowing direct connection of braking resistors for fast deceleration
  3. Safety Function: Coupure sûre du couple (STO) compliant with PL e / SIL 3 safety level
  4. Protection de l'environnement: Full triple-protection coating on control and power boards, resistant to humid, dusty and corrosive gas environments
  5. Standard Control Interfaces: 6 entrées numériques, 2 sorties numériques, 2 entrées analogiques, 1 sortie analogique
  6. Basic Communications: Embedded RS-485 hardware port with native Modbus RTU protocol support
  7. Conception structurelle: Bottom cable entry compartment supporting standardized wiring and cable ingress protection
  8. Physical Standard Carton Accessories (Separately Packed Inside Shipment Box)

Independent accessories available upon unpacking for installation and basic commissioning:

  1. ACS-AP-S Assistant Control Panel (Chinese version): Equipped with LCD screen and full-function keys for parameter setup, status monitoring and fault diagnosis; pluggable onto drive front panel and supplied in separate packaging
  2. Wall Mounting Template: 1:1 paper drilling positioning template for marking mounting hole positions on-site to reduce drilling errors
  3. Cable Junction Box Assembly: Standard for Frame R5 IP21 units, including power cable grounding brackets, control cable shielding clamps and assembly fasteners
  4. Mounting Fastener Kit: M6 bolts, nuts and other metal hardware for wall mounting fixation
  5. Ground Terminals & Cable Crimp Accessories: Dedicated main circuit grounding terminals and auxiliary crimp fittings for control terminals

III. Supplied Documentation & Identification Labels

  1. Quick Installation and Startup Guide: Multilingual edition (including Chinese) covering full procedures of wiring, power-up and basic commissioning
  2. Safety Warning Stickers: Multilingual residual voltage warning labels to be affixed near equipment to alert maintenance personnel
  3. Product Certificate of Conformity and Warranty Document

Note: Full hardware manuals and firmware parameter manuals are not supplied as standard; downloadable via ABB official website or available as separate printed copies upon order.

  1. Packaging Auxiliary Protection Materials

Standard industrial shipping packaging for logistics protection, not classified as drive accessories:

VCI vapor corrosion inhibitor anti-rust bag

Paper buffer liners and corner protectors

Strapping bands

Shipping pallet (for full carton industrial packaging specifications)

  1. Non-Standard Optional Components Requiring Separate Ordering

Items below are excluded from standard supply scope and must be purchased separately per project demands:

Enclosure Upgrade: IP55 protective enclosure, flange mounting kit

Communication Extensions: Fieldbus adapters including Profibus DP, Profinet IO, EtherNet/IP, Modbus-TCP

Electrical Matching Components: Input reactors, output reactors, du/dt filters, sine-wave filters, braking resistors

Functional Extensions: I/O expansion modules, cartes d'interface d'encodeur, temperature sensor interface cards, remote monitoring modules