Allen-Bradley 440R-N23114 Safety Relay - Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-mail: kent@bestcontactor.com

À propos Contact |

 Allen-Bradley 440R-N23114 Safety Relay - Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires

électrique/

Allen-Bradley 440R-N23114 Safety Relay

Basic Model Definition Catalog Number: 440R-N23114 Internal Model Code: MSR126.1T Brand: Allen-Bradley (Rockwell Automatisation), Guardmaster Minotaur Series Lifecycle: Active production model, manufactured in Czech Republic, standard 1-year warranty Core Electrical Specifications 2.1 Power Supply Rated Voltage: 24V CA/CC, operating range: 0.85~1.1× rated voltage (20.4~26.4V) Consommation d'énergie: 4W, compatible with 50/60Hz Terminals A1/A2: Power input 2.2 ...

  • Détails du produit

Basic Model Definition

Catalog Number: 440R-N23114

Internal Model Code: MSR126.1T

Marque: Allen-Bradley (Rockwell Automatisation), Guardmaster Minotaur Series

Cycle de vie: Active production model, manufactured in Czech Republic, standard 1-year warranty

  1. Core Electrical Specifications

2.1 Alimentation

Tension nominale: 24V CA/CC, operating range: 0.85~1.1× rated voltage (20.4~26.4V)

Consommation d'énergie: 4W, compatible with 50/60Hz

Terminals A1/A2: Power input

2.2 Safety Inputs (Dual-channel 4-wire with cross short-circuit detection)

2 normalement fermé (Caroline du Nord) safety input paths (S11-S12 / S21-S22)

Supports dual-channel emergency stop, safety door switches and safety light curtains; built-in cross-channel short-circuit fault diagnosis

Maximum input loop resistance: ≤90Ω

2.3 Reset Circuit (S33-S34)

MSR126.1T supports automatic reset and manual reset dual modes

  1. Réinitialisation automatique: Short S33 and S34; outputs close automatically after faults are cleared
  2. Réinitialisation manuelle: Connect an external normally open reset pushbutton to S33-S34; manual push is required to restore outputs

Difference from MSR126.1R: MSR126.1R only provides monitored manual reset without automatic reset function

2.4 Safety Output Contacts (Force-guided safety contacts complying with IEC 61810-3)

2 safety normally open (NON) contacts: 13-14, 23-24

Load Ratings:

DC-13: 6A/24V DC; 3A/24V DC (for frequent switching)

AC-15: 5A/250 V CA

Temps de réponse: Environ. 15MS; Recovery Time: 100MS

No auxiliary alarm contacts

  1. Safety Certification Ratings (Top Industry Standards)

OIN 13849-1: Catégorie 4 / PL e

CEI 61508 / CEI 61511: SIL 3

DANS 954-1: Safety Category 4, Catégorie 0 Arrêt

Certifications: CE, cULus, CCC, BG, C-Tick

  1. Mechanical Dimensions & Montage

Largeur: 22.5mm (compact DIN rail mounting)

Dimension globale: 110mm (H) × 75mm (D) × 22.5mm (W)

Poids: 160g

Terminaux: Fixed screw terminals (non-pluggable), Indice de protection IP20

Température de fonctionnement: -25℃ ~ +70℃

  1. Front Panel LED Indicator Meanings
  2. PWR (Vert): Steady on when power supply is normal
  3. CH1 (Vert): Illuminated when Channel 1 input circuit is closed
  4. CH2 (Vert): Illuminated when Channel 2 input circuit is closed

All three LEDs on → Safety output contacts closed; Any single channel open → Outputs cut off

  1. Scénarios d'application typiques
  2. Dual-channel emergency stop button circuit monitoring
  3. 4-wire safety door switches (with short-circuit detection)
  4. Safety light curtain / light screen safety circuits
  5. Safety cut-off for machine tools, automated production lines and packaging equipment

Suitable for equipment requiring high safety ratings of PL e / SIL3

  1. Series Model Comparison for Selection
Catalog No.Internal CodeMode de réinitialisationAlimentationChannel Configuration
440R‑N23114MSR126.1TSelectable Auto/Manual Reset24V CA/CCDual-channel 4-wire
440R‑N23113MSR126.1RMonitored Manual Reset Only24V CA/CCDual-channel 4-wire
440R‑N23112MSR126TAuto/Manual Reset230V etDual-channel 4-wire
  1. Brief Wiring Logic
  2. Connect 24V AC/DC power to terminals A1/A2
  3. Wire two NC safety switches (arrêt d'urgence / door switches) in series to S11-S12 and S21-S22 respectively
  4. Short-circuit S33-S34 for automatic reset; connect an NO pushbutton in series for manual reset
  5. Wire the safety coil of main contactors in series across terminals 13-14 et 23-24
  6. Disconnection of any safety input or cross-channel short-circuit will simultaneously open both NO outputs to cut power supply
  7. Troubleshooting Guidelines
  8. LED PWR éteinte: Power phase loss, insufficient voltage or loose wiring
  9. Single CH1/CH2 LED off: Corresponding channel switch open or circuit wire breakage
  10. Both CH1 and CH2 LEDs lit but outputs fail to close: Cross-channel short-circuit fault; power cycle to reset, or reset circuit not shorted / reset button not pressed
  11. Soudage par contact: Charge de sortie excessive; replace contactors with higher capacity

Full Specifications of Safety Output Contacts for Allen-Bradley 440R-N23114

  1. Basic Contact Structure
  2. Quantité & Taper: 2 independent redundant safety normally open (NON) contacts at terminals 13-14 et 23-24; no auxiliary alarm contacts or delayed outputs
  3. Contact Construction: Force-guided safety contacts (CEI 61810-3), dual-channel redundant mechanical interlock. Single contact welding cannot maintain circuit conduction, fulfilling Category 4 / PL e / SIL3 safety architecture
  4. Matériel de contact: AgSnO₂ silver tin oxide, résistant à l'arc et anti-soudure
  5. Minimum Conducting Current: 10mA (ensures reliable circuit detection by contacts)
  6. Rated Load Currents (Official Standard Load Categories)

2.1 Charge CA (AC-15, standard load for electromagnetic contactors)

250V et: 6UN (inductive-resistive load, cosφ=0.35)

UL B300 certified rating: 5UN / 250V et

2.2 Charge CC (DC-13, électrovannes / DC coils)

Frequent switching at 24V DC: 3UN (standard switching rating)

Low-frequency light load (0.1Hz) at 24V DC: Max.. 6A for short-term use (long-term high-frequency operation not recommended)

2.3 Continuous Thermal Current Ith (static carrying current without switching)

Maximum static continuous current per single contact: 6UN (only for permanent conduction with rare break operations)

  1. Endurance électrique & Operating Timing
  2. Endurance électrique (220V et / 4UN / cosφ=0.35)

6A breaking capacity: 100,000 opérations

4A light load: 500,000 opérations

  1. Safety Operation Timing

Response time from safety input open to contact break: ≤15ms

Contact pull-in recovery time after fault clearance: Environ. 100MS

  1. Dielectric Withstand Voltage

Withstand voltage across open contacts: AC750V for 1 minute

Résistance d'isolation (DC500V test): ≥1000MΩ

  1. External Protection & Wiring Limitations
  2. Recommended Fuse for Output Circuit

Slow-blow fuse: 6UN; Fast-acting fuse: 10UN. Over-rated fuses are prohibited to prevent contact ablation and welding

  1. Applicable Wire Gauge: 0.2~2.5mm² solid / stranded copper wires; fixed non-pluggable screw terminals
  2. Maximum Operating Voltage: 250V et / 30À DC; overvoltage is strictly forbidden
  3. Contact Performance Matching Safety Ratings

OIN 13849-1: Catégorie 4, PL e (independent cut-off via dual redundant contacts)

CEI 61508: SIL3; single contact failure will not disable safety cut-off function

Stop Category: DANS 60204-1 Catégorie 0 hard cut-off stop

  1. Quick Load Selection Table
Type de chargeTensionCourant nominalScénarios d'application
AC‑15250V et6UNAC contactor coils
DC‑1324À DC3UNDC solenoid valves, DC contactors
Static Continuous≤250VAC / 30VCC6UNCircuits with permanent conduction and minimal breaking operations

tic Continuous | ≤250VAC / 30VCC | 6UN | Circuits with permanent conduction and minimal breaking operations |