Chint NA1-3200X-3200M/3P Air Circuit Breaker

  Code Segment Description NA1 Series code for Chint air circuit breakers (PBR) 3200 Frame rated current: 3200UN (maximum current specification of the breaker) X Breaking capacity grade: Class X (100le); distinguished from standard type (80le) and Class H (120le) 3200 Courant de fonctionnement nominal: 3200UN (actual set working current) M Trip unit type: Intelligent trip ...

  • Détails du produit

 

Segment de codeDescription
NA1Series code for Chint air circuit breakers (PBR)
3200Frame rated current: 3200UN (maximum current specification of the breaker)
XBreaking capacity grade: Class X (100le); distinguished from standard type (80le) and Class H (120le)
3200Courant de fonctionnement nominal: 3200UN (actual set working current)
M.Trip unit type: Intelligent trip unit (Micrologic); distinguished from standard Type L and high-breaking Type H
3P.Numéro de pôle: 3-pôle (3-protection des circuits de phases, without neutral pole)
  1. Spécifications techniques de base
Catégorie de paramètreTechnical Data
Type de produitIntelligent low-voltage air circuit breaker (PBR)
Tension de fonctionnement nominaleC.A. 400 V/690 V, 50Hz
Courant de trame (ui)3200UN
Courant de fonctionnement nominal (Dans)3200UN
Rated Ultimate Short-circuit Breaking Capacity (ICU)100le (Class X @ 400V)
Rated Service Short-circuit Breaking Capacity (IC)100le (equal to Icu)
Courant de tenue nominal de courte durée (Icw)80le (1s)
Unité de déclenchementType M intelligent trip unit, featuring long-time delay overload, short-time delay short-circuit and instantaneous short-circuit protection
Type de montageDraw-out or fixed type (X series is generally draw-out)
Mode de fonctionnementManual or motorized (motor operating mechanism optional)
Tension du circuit de commandeAC 220V/380V or DC 220V (facultatif)
Contacts auxiliairesStandard: 5NON + 5Caroline du Nord (expandable)
Protection contre la pénétrationIP30 (conforme à GB/T 4942.2)
Normes applicablesGB/T 14048.2, CEI/EN 60947-2
Dimensions (H×L×P)Draw-out type: environ. 600mm×400mm×1000mm (refer to official manual for exact data)
PoidsEnviron. 80~100kg (varies by mounting type and accessory configuration)
  1. Fonctionnalités principales

3.1 Intelligent Protection System

Three-stage protection: Long-time delay for overload (caractéristique à temps inverse), short-time delay for short circuit (selectable fixed/inverse time), and instantaneous short-circuit protection, precisely matching power distribution system requirements.

Protection contre les défauts de terre: Residual current protection optional, sensitivity adjustable from 0.03A to 1A.

Adjustable protection parameters: Flexible parameter configuration via intelligent controller to adapt to diverse load characteristics.

Fault recording: Automatically stores the latest 10 fault records including fault type, current value and time for rapid troubleshooting.

3.2 High Reliability Design

High Class X breaking capacity: 100kA short-circuit breaking capacity to ensure reliable disconnection under severe short-circuit faults and guarantee equipment safety.

Optimized arc extinguishing system: Adopts multi-break and longitudinal seam arc extinguishing technology for rapid arc extinction and fast recovery after breaking.

Long service life: Mechanical durability up to 10,000 opérations; electrical durability up to 5,000 opérations.

Vibration and shock resistance: Compliant with GB/T 14048.2 to adapt to harsh industrial environments.

3.3 Flexible Expandability

De riches accessoires optionnels: Déclenchement de dérivation, undervoltage trip, closing solenoid, motor charging mechanism, contacts auxiliaires, contacts d'alarme, key lock, etc..

Extended communication: Optional Modbus-RTU, Profinet, EtherNet/IP modules for remote monitoring and intelligent power distribution management.

Interlock functions: Cable interlock and connecting rod interlock available to meet electrical and mechanical interlock requirements.

  1. Compatible Equipment & Scénarios d'application

Compatible Equipment

Distribution transformer: Main protection switch for low-voltage side of transformers

Generator set: Protection switch for generator outgoing circuits

Busbar system: Bus section protection and tie control

Gros moteur: Incoming switch for Motor Control Center (Centre multicompte)

UPS system: Protection switch for UPS input and output circuits

Scénarios d'application

  1. Industrial power distribution: Main power distribution systems for factories, workshops and production lines.
  2. Commercial building power distribution: Main and floor power distribution for shopping malls, hotels and high-rise buildings.
  3. Data centers: Mission-critical areas requiring high power supply reliability such as server rooms and cloud computing centers.
  4. New energy industry: Low-voltage power distribution systems for photovoltaic power stations and wind farms.
  5. Infrastructure: Power distribution systems for transportation hubs including airports, subways and railways.
  6. Comparaison des modèles
ModèleCapacité de coupureCourant nominalUnité de déclenchementApplication
NA1-3200-3200M/3P80le (Standard)3200UNType M IntelligentGeneral industrial distribution with low short-circuit current
NA1-3200X-3200M/3P100le (Class X)3200UNType M IntelligentIndustrial sites with high short-circuit current and high breaking capacity requirements
NA1-3200H-3200M/3P120le (Classe H)3200UNType M IntelligentLarge industrial enterprises and grid connection points with extreme short-circuit current
NA1-3200X-2500M/3P100le (Class X)2500UNType M Intelligent3200A frame with actual load current of 2500A
NA1-3200X-3200L/3P100le (Class X)3200UNType L StandardGeneral scenarios with basic protection demands
  1. Cross-Brand Equivalent Model Comparison
ChintSiemensSchneiderABBMitsubishi
NA1-3200X-3200M/3P3WL2N32 ETU25B 3PMT32H1 3P 3200A Micrologic 5.0EMAX2 E3S3200 R100 3PAE3200-SW 3P F 3200A
Capacité de coupure100le100le100le85le
Unité de déclenchementType M IntelligentETU25B IntelligentMicrologic 5.0 IntelligentStandard Intelligent Trip
Type de montageDraw-out / FixéDraw-out / FixéDraw-out / FixéDraw-out / Fixé
CommunicationOptional Modbus / ProfinetOptional Profinet / EtherNet/IPOptional Modbus / ProfinetOptional CC-Link / Profinet
  1. Sélection & Application Guidelines
  2. Breaking capacity matching: Select proper grade according to system short-circuit current calculation (Standard 80kA, Class X 100kA, Class H 120kA).
  3. Rated current selection: Determine operating current based on total load current and future expansion; optional ratings under 3200A frame: 2000UN, 2500UN, 3200UN.
  4. Trip unit selection: Type M intelligent trip for most industrial and commercial applications; Type L standard trip for simple protection requirements.
  5. Mounting type: Draw-out type for easy maintenance and replacement (critical circuits); fixed type for cost-effective general circuits.
  6. Operation mode: Manual for small-capacity and infrequent operation; motorized for large-capacity, frequent operation and remote control.
  7. Accessory configuration: Select shunt trip, undervoltage trip, auxiliary contacts and communication modules as required by control and protection logic.
  8. Entretien: Regularly inspect mechanical mechanisms, arc extinguishing chambers and contact wear to ensure long-term stable operation.

Chint NA1-3200X-3200M/3P Complete Accessory List & Selection Codes

  1. Core Control Accessories (Essential for Control Circuit)

1.1 Déclenchement de dérivation (F)

Used for remote breaker tripping, applicable to emergency shutdown and automatic control systems.

TaperModèleTension nominaleConsommation d'énergieApplicationSelection Code
Continuous (Défaut)NA1-F-3200XAC220V/230V460Virginie(AC220V)Contrôle industriel général, infrequent operationF-AC220
AC380V/400V400Virginie(AC380V)F-AC380
DC110V70W(DC110V)F-DC110
DC220V140W(DC220V)F-DC220
Pulse Type (Recommandé)NA1-FP-3200XAC220V/230V880Virginie(AC220V)Wind & solar power, ATS system, opération fréquenteFP-AC220
AC380V/400V1800Virginie(AC380V)FP-AC380
DC110V850W(DC110V)FP-DC110
DC220V880W(DC220V)FP-DC220

Selection Note: Pulse type: single power-on duration ≤ 2s, maximum 5 times/min; Continuous type: single power-on duration ≤ 2s to avoid component burnout.

1.2 Déclenchement sous-tension (Q)

Automatically trips the breaker under low grid voltage to prevent equipment overload damage.

TaperModèleTension nominaleOperating CharacteristicDelay TimeSelection Code
Instant Suction (Défaut)NA1-Q-3200XAC230VTrip at 70% Us, reliable trip at 35% UsInstantQ-AC230
AC400VQ-AC400
Delayed SuctionNA1-QD-3200XAC230VSame as above1s/3s/5s (Fixé)QD-AC230-1s
AC400VQD-AC400-3s
Self-suction DelayNA1-QZ-3200XAC230VSame as above0.3s~7.5s (Réglable)QZ-AC230
AC400VQZ-AC400
Under-voltage Delay (UVTZ-1)NA1-UVTZ-1AC230VAutomatic reclosure after voltage recovery1s/3s/5sUVTZ-1-AC230
AC400V

Selection Note: 3200A frame adopts instant suction type as standard; self-suction type features wider delay range for voltage-fluctuation-sensitive equipment.

1.3 Closing Solenoid (X) / Closing Coil

For remote closing, matched with motor charging mechanism.

TaperModèleTension nominaleConsommation d'énergieApplicationSelection Code
Pulse Type (Mandatory for ATS)NA1-X-3200XAC220V/230VSame as shunt tripAutomatic control system, frequent closingX-AC220
AC380V/400VX-AC380
DC110VX-DC110
DC220VX-DC220

1.4 Motor Charging Mechanism (M.)

Stores energy for breaker closing and provides closing power.

ModèleTension nominalePouvoirCharging TimeSelection Code
NA1-M-3200XAC220V/230V0.37kW≤15sM-AC220
AC380V/400VM-AC380
DC110VM-DC110
DC220VM-DC220
  1. Intelligent Control & Communication Accessories

2.1 Intelligent Controller Upgrade

Type M is standard; upgraded versions with enhanced functions are optional.

ModèleCaractéristiquesApplicationSelection Code
Type 3MAdded voltage measurement and harmonic analysisPower quality monitoring required3M.
Tapez HAdvanced protection with extended parameter settingsComplex power distribution systems & protection préciseH
Type 3HHighest configuration, full 3M+H functions + event loggingCritical circuits & fault analysis3H

2.2 Modules de communication (Surveillance à distance)

Module TypeModèleProtocolFonctionMatching ComponentSelection Code
Modbus-RTUNA1-COM-MODModbus-RTUData acquisition & télécommandeNot requiredCOM-MOD
Profibus-DPNA1-COM-DPProfibus-DPIndustrial fieldbus communicationST-DP protocol moduleCOM-DP+ST-DP
ProfinetNA1-COM-PNProfinetEthernet communicationPSU-1 power moduleCOM-PN+PSU-1
EtherNet/IPNA1-COM-ENIPEtherNet/IPEtherNet/IP communicationPSU-1 power moduleCOM-ENIP+PSU-1

2.3 Auxiliary Functional Modules

NomModèleFonctionApplicationSelection Code
Power Supply UnitPSU-1Stable power supply for communication modulesMandatory for all Ethernet modulesPSU-1
Relay ModuleRU-1Signal amplification & contact expansion (AC250V/10A, DC28V/10A)High-power load controlRU-1
Under-voltage Delay ControllerUVTZ-1Delayed trip during temporary low voltageVoltage-sensitive equipmentUVTZ-1
  1. Auxiliary Contact System (Indication d'état & Control)

NA1-3200X standard configuration: 4 sets of transfer contacts (4NO+4NC), expandable.

TaperModèleConfiguration des contactsNotationApplicationSelection Code
3 sets TransferNA1-AX-3Z3NON+3NCAC230V/5ABasic controlAX-3Z
4 sets Transfer (Défaut)NA1-AX-4Z4NO+4NCAC230V/5AConfiguration standardAX-4Z
5 sets TransferNA1-AX-5Z5NO+5NCAC230V/5AExtended controlAX-5Z
3NON+3NCNA1-AX-333NON+3NCAC230V/5ACustom control logicAX-33
4NO+4NCNA1-AX-444NO+4NCAC230V/5AConfiguration standardAX-44
5NO+5NCNA1-AX-555NO+5NCAC230V/5AContrôle complexeAX-55
6NO+6NCNA1-AX-666NO+6NCAC230V/5AOnly for Type M controller, cannot match suction undervoltage delayAX-66
  1. Verrouillage mécanique & Safety Accessories

4.1 Verrouillage mécanique (Misoperation Prevention)

TaperModèleFonctionApplicationSelection Code
Connecting Rod InterlockNA1-LK-LGMutual interlock for two breakers to prevent simultaneous closingBus tie & ATS systemLK-LG
Cable InterlockNA1-LK-GLRemote mechanical interlock, standard cable length: 2mATS system with large cabinet spacingLK-GL
Key LockNA1-KEYMultiple configurations: 1-lock-1-key, 2-lock-1-keyUnauthorized operation preventionKEY-1-1
KEY-2-1
Button LockNA1-BLLock closing/tripping buttonsAccidental touch preventionBL

4.2 Door Interlock

TaperModèleFonctionApplicationSelection Code
Position Door InterlockNA1-DL-WZCabinet door locked at test/connected positionDraw-out breaker, electric shock preventionDL-WZ
Status Door InterlockNA1-DL-ZTCabinet door locked when breaker closedLive operation prevention for all typesDL-ZT

4.3 Other Safety Accessories

NomModèleFonctionApplicationSelection Code
Transparent Protective CoverNA1-TPIP54 protection for operating mechanismDust environments & safety enhancementTP
CounterNA1-CTMechanical operation countingFrequent circuits & maintenance prédictiveCT
Position IndicatorNA1-PSDraw-out position indication (Disconnect/Test/Connected)Draw-out breaker status monitoringPS
Phase BarrierNA1-PSBIsolate three-phase busbars to prevent phase short circuitInsulation improvementPSB
  1. Montage & Connection Accessories

5.1 Main Circuit Accessories

NomModèleNotationApplicationSelection Code
Horizontal BusbarNA1-BUS-H3200UNStandard horizontal wiringBUS-H
Vertical L-type BusbarNA1-BUS-V3200UNVertical installation & space savingBUS-V
Rotatable BusbarNA1-BUS-R3200UNFlexible wiring for draw-out breakersBUS-R

5.2 Secondary Circuit Accessories

NomModèleFonctionApplicationSelection Code
Secondary ConnectorNA1-SPSecondary circuit connection for draw-out breakersQuick plug & unplugSP
Control FuseNA1-FU6UN, control circuit protectionMandatory for all control loopsFU-6A
  1. Complete Configuration Example

Exemple:

NA1-3200X-3200M/3P, motorized draw-out type, AC220V, with shunt trip / undervoltage trip / closing solenoid + 5 sets transfer contacts + Profinet communication + connecting rod interlock

Complete Order Model:

NA1-3200X-3200M/3P Motorized Draw-out AC220 F-AC220 Q-AC230 X-AC220 AX-5Z COM-PN+PSU-1 LK-LG

  1. Accessory Application Notes
  2. Unified control voltage: Use identical voltage for shunt trip, undervoltage trip, closing solenoid and motor charging mechanism to simplify wiring.
  3. Communication matching: PSU-1 power module required for Profinet/EtherNet/IP; ST-DP module required for Profibus-DP.
  4. Auxiliary contact capacity: 5A@AC230V; use RU-1 relay module for high-power load control.
  5. Undervoltage trip requirement: Undervoltage trip coil must be powered on before breaker closing.
  6. Shunt trip specification: Single energization time ≤ 2s, frequency ≤ 5 times/min to avoid overheating damage.

 