Chint NM8N-1600SEM 3P 1250A 50kA Moulded Case Circuit Breaker - Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-mail: kent@bestcontactor.com

À propos Contact |

 Chint NM8N-1600SEM 3P 1250A 50kA Moulded Case Circuit Breaker - Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires

disjoncteur/

Chint NM8N-1600SEM 3P 1250A 50kA Moulded Case Circuit Breaker

  Model Code Definition Segment Code Detailed Description NM8N Series Code New-generation moulded case circuit breaker (MCCB) of Chint; N stands for upgraded version with higher breaking capacity 1600 Frame Size Maximum frame current: 1600A S Breaking Capacity Grade Standard breaking type, 50le (ultimate short-circuit breaking capacity at 400V) E Trip Unit Type Electronic intelligent trip unit with ...

  • Détails du produit

 

  1. Model Code Definition
SegmentCodeDescription détaillée
NM8NSeries CodeNew-generation moulded case circuit breaker (MCCB) of Chint; N stands for upgraded version with higher breaking capacity
1600Taille du cadreMaximum frame current: 1600UN
SBreaking Capacity GradeStandard breaking type, 50le (ultimate short-circuit breaking capacity at 400V)
EType de déclencheurElectronic intelligent trip unit with four-stage protection functions
M.Type de montageType fixe; Facultatif: P=Plug-in, D=Draw-out
3P.Numéro de pôle3-pôle, for main protection of three-phase circuits
1250UNCourant nominalSetting rated current In​=1250A, long-term stable operating current
50leCapacité de rupture ultimeIcu​=50kA@400V, maximum short-circuit current that can be safely disconnected
  1. Paramètres techniques de base
ArticleValeurRemarques
Courant nominal (In​)1250UNElectronic trip unit adjustable range: 800–1250A
Taille du cadre1600UNCompatible with trip units ≤1600A
Numéro de pôle3P.Main protection for three-phase three-wire systems
Type de montageFixéVertical / horizontal mounting available; haut & bottom incoming line supported
Tension d'isolation nominale (Ui​)1000VConforme à la CEI 60947-2
Tension de fonctionnement nominale (Ue​)AC400V / AC690VApplicable to power distribution systems of different voltage levels
Ultimate Short-circuit Breaking Capacity (Icu​)50kA@400VStandard S type; Ics​=100%Icu​
Service Short-circuit Breaking Capacity (Ics​)50kA@400VResists multiple short-circuit current impacts
Type de déclencheurElectronic Intelligent Type (E)Four-stage protection: long delay, short delay, instantaneous & earth fault
Tension de contrôleStandard AC230V, optional DC220VPower supply for shunt trip, under-voltage trip and control circuit
Mechanical Endurance≥10,000 timesIndustrial long-life design
Electrical Endurance≥5,000 timesMaking & breaking capacity under rated current
Température ambiante-40℃ ~ +70℃Adaptable to harsh industrial environments
  1. Core Functions of Electronic Intelligent Trip Unit (E-Type)
  2. Full-range Protection: Accurate four-stage protection including long delay (inverse time), short delay (fixed/inverse time), instantaneous trip (fixed time) and earth fault (fixed/inverse time).
  3. Monitoring Function: Real-time monitoring of three-phase current, fault current and operating status, with fault memory.
  4. Adjustable Parameters: Flexible adjustment of protection current and delay time for customized protection in various distribution systems.
  5. Expansion des communications: Optional Modbus-RTU communication module for remote monitoring and data transmission.
  6. Comprehensive Protection Features: Surcharge, court-circuit, under-voltage, phase loss and three-phase unbalance protection to prevent equipment damage and electrical fire hazards.
  7. Scénarios d'application
  8. Distribution d'énergie industrielle: Incoming/outgoing circuit protection for main distribution cabinets in workshops and production lines; control circuits for large-capacity motors.
  9. Bâtiments commerciaux: Distribution trunk protection for shopping malls, hôtels, office buildings and large commercial complexes.
  10. Infrastructure: Secondary power distribution protection for hospitals, schools, data centers and other key facilities.
  11. Energy Systems: Low-voltage distribution protection for photovoltaic power stations, wind power systems and substations.
  12. Protection du moteur: Overload and short-circuit protection for infrequently started large-capacity motors (pompes à eau, les fans, compresseurs, etc.).
  13. Complete Accessory List (Classified by Function)

5.1 Opération & Control Accessories

Nom de l'accessoireModèleFonctionPortée applicable
Déclenchement de dérivationNM8N-FRemote opening control, AC230V/DC220V optionalFull series; for emergency shutdown and remote control
Under-voltage TripNM8N-UVTDelayable under-voltage protection to avoid equipment damage from undervoltageFull series; essential for critical loads
Closing SolenoidNM8N-CERemote closing control for automatic control systemsFull series; for frequent operation
Mécanisme de fonctionnement électriqueMOD22-M8Electric energy storage, clôture & opening to improve operation efficiency1600Un cadre; suitable for unattended power distribution rooms
External Operating HandleRH11Extended cabinet external operation for safety and convenienceFull series

5.2 Auxiliaire & Alarm Accessories

Nom de l'accessoireModèleConfiguration des contactsFonction
Contact auxiliaireNM8N-A1/A2/A41/2/4 changeover contactsCircuit breaker status indication and control circuit expansion
Contact d'alarmeNM8N-B1/B21/2 changeover contactsFault alarm signal output and equipment linkage
Auxiliaire & Alarm CombinationNM8N-AB2 contacts auxiliaires + 1 contact d'alarmeIntegrated status monitoring and space saving
Prepaid Trip UnitNM8N-PPRemote power cut-offLinked with prepaid system for automatic power outage on arrears

5.3 Connexion & Mounting Accessories

Nom de l'accessoireModèleApplicable FrameFonction
Phase BarrierNM8N-IS16001600Un cadreStandard inter-phase insulation barrier to prevent arc spreading
Front Connection PlateFM221600Un cadreDedicated for front wiring; enlarged terminal area for cable connection
Rear Wiring KitNM8N-RB1600Un cadreDedicated for rear wiring, suitable for draw-out cabinets
Plug-in BaseNM8N-IB1600Un cadrePlug-in installation for easy maintenance and replacement
Terminal Protective CoverNM8N-COVER1600Un cadreDustproof and anti-touch protection for wiring terminals

5.4 Sécurité & Expansion Accessories

Nom de l'accessoireModèleFonctionApplication
Key LockNM8N-KLLock on/off status to prevent misoperationPublic areas and key equipment protection
Padlock DeviceNM8N-LOCKLock circuit breaker at open position for safety isolationEquipment maintenance and overhaul
Module de communicationNM8N-MODModbus-RTU protocol for remote monitoring and data uploadSmart power distribution and IoT systems
Residual Current Protection ModuleNM8N-LLeakage protection against electric shock and equipment leakage failureHumid environments and densely populated areas
  1. Cross-Brand Equivalent Comparison (Mainstream MCCB)
Chint NM8N ModelSchneider NSXABB Tmax XTSiemens 3VTChangshu CM3Remarques
NM8N-1600SEM-3P-1250A-50kANSX1600N 1250A Micrologic 5.0XT4S1600 TMD 1250A 50kA3VT8416-1AA03-0AA0CM3-1600H/3340 1250A1600Un cadre, electronic trip, 50kA breaking
NM8N-1600SPM-3P-1250A-50kANSX1600N 1250A Micrologic 2.0XT4S1600 TMD 1250A 50kA3VT8416-1AA03-0AA0CM3-1600H/3300 1250APlug-in type, standard protection
NM8N-1600EDM-3P-1250A-50kANSX1600N 1250A Micrologic 5.0XT4S1600 TMD 1250A 50kA3VT8416-1AA03-0AA0CM3-1600H/3340 1250ADraw-out type, intelligent protection
  1. Sélection & Procurement Guidelines
  2. Breaking Capacity Selection: 50kA standard S type for general industrial and commercial distribution; select H type (70le) or HH type (100le) for higher breaking requirements.
  3. Trip Unit Selection: Electronic intelligent E-type for precise protection and remote monitoring; thermal-magnetic T-type for conventional distribution scenarios.
  4. Type de montage: Low-cost fixed type (M.); replaceable plug-in type (P.); draw-out type (D) for critical load maintenance.
  5. Accessory Configuration:

Essentiel: 1~2 sets of auxiliary contacts and under-voltage trip for basic control and protection.

Facultatif: Electric operating mechanism, communication module and residual current module to enhance intelligence and safety.

  1. Conformité aux certifications: Compliant with GB14048.2 and IEC 60947-2, with CE & UL certifications to ensure product quality and operational safety.

Chint NM8N Series MCCB Complete Model List & Price Guide

  1. Complete Naming Rule

NM8N-□□□□-□□-□□-□P

SegmentDéfinitionOptional CodeDescription
NM8NSérieFixéChint upgraded MCCB series with enhanced breaking performance
Taille du cadreMax frame current125,160,250,400,630,800,1250,1600Covering 125A~1600A rated current
Breaking GradeShort-circuit capacityS(Standard),H(Haut),R.(Current-limiting),Q, CS=50kA, H=70kA, R=100kA, Q=120kA, C=150kA@400V
Type de voyageProtection modeMT(Thermal-Magnetic), EM(Électronique)MT: overload inverse time + instantaneous short-circuit; EM: four-stage intelligent protection
Courant nominalSetting current16~1600AElectronic trip adjustable: 63%~100% of rated current
MontageInstallation formM.(Fixé), P.(Plug-in), D(Draw-out)Universal installation options for cabinet design
Numéro de pôleMain poles1P/2P/3P/4B/4C4B: 4-pôle (N non-protected); 4C: 4-pôle (N protected)
Breaking Currentjecu25/36/50/70/100/120/150le400V short-circuit breaking parameter
  1. Full Model List by Frame Size

2.1 125Un cadre (NM8N-125)

BreakingTripDansMountPôleModèlePrix ​​de référence(USD)
S(50le)MT63~125AM.3P.NM8N-125S TM 125 M 3P65–80
S(50le)EM80~125AM.4CNM8N-125S EM 100 M 4C108–128
H(70le)MT100~125AP.3P.NM8N-125H TM 125 P 3P90–108
R.(100le)EM125UND3P.NM8N-125R EM 125 D 3P165–205

2.2 250Un cadre (NM8N-250)

BreakingTripDansMountPôleModèlePrix ​​de référence(USD)
S(50le)MT160~250AM.3P.NM8N-250S TM 250 M 3P136–160
Q(120le)MT125~160AM.2P.NM8N-250Q TM 125 M 2P272–305
H(70le)EM200~250AP.3P.NM8N-250H EM 250 P 3P233–270
R.(100le)EM250UND4CNM8N-250R EM 250 D 4C318–368

2.3 400Un cadre (NM8N-400)

BreakingTripDansMountPôleModèlePrix ​​de référence(USD)
S(50le)MT315~400AM.3P.NM8N-400S TM 400 M 3P180–215
C(150le)MT315~400AM.3P.NM8N-400C TM 400 M 3P248–290
H(70le)EM350~400AP.3P.NM8N-400H EM 400 P 3P330–385
R.(100le)EM400UND4CNM8N-400R EM 400 D 4C440–500

2.4 630Un cadre (NM8N-630)

BreakingTripDansMountPôleModèlePrix ​​de référence(USD)
S(50le)MT500~630AM.3P.NM8N-630S TM 630 M 3P305–355
H(70le)MT630UNM.4CNM8N-630H TM 630 M 4C388–445
R.(100le)EM500~630AP.3P.NM8N-630R EM 630 P 3P528–595
C(150le)EM630UND3P.NM8N-630C EM 630 D 3P665–750

2.5 800Un cadre (NM8N-800)

BreakingTripDansMountPôleModèlePrix ​​de référence(USD)
S(50le)MT630~800AM.3P.NM8N-800S TM 800 M 3P430–495
H(70le)EM800UNM.4CNM8N-800H EM 800 M 4C585–655
R.(100le)EM800UNP.3P.NM8N-800R EM 800 P 3P735–820
C(150le)EM800UND3P.NM8N-800C EM 800 D 3P905–1005

2.6 1250Un cadre (NM8N-1250)

BreakingTripDansMountPôleModèlePrix ​​de référence(USD)
S(50le)MT1000~1250AM.3P.NM8N-1250S TM 1250 M 3P665–750
H(70le)EM1250UNM.3P.NM8N-1250H EM 1250 M 3P860–960
R.(100le)EM1250UNP.3P.NM8N-1250R EM 1250 P 3P1040–1150
C(150le)EM1250UND4CNM8N-1250C EM 1250 D 4C1290–1415

2.7 1600Un cadre (NM8N-1600)

BreakingTripDansMountPôleModèlePrix ​​de référence(USD)
S(50le)MT1250~1600AM.3P.NM8N-1600S TM 1600 M 3P905–1005
S(50le)EM1250UNM.3P.NM8N-1600S EM 1250 M 3P1220–1350
H(70le)EM1600UNM.3P.NM8N-1600H EM 1600 M 3P1450–1610
R.(100le)EM1600UND3P.NM8N-1600R EM 1600 D 3P1795–2010
  1. Série spéciale

3.1 DC MCCB (NM8NDC)

CadreActuelBreakingPôleModèlePrix(USD)
125UN100UN25le2P.NM8NDC-125B TM 100 2P.80–95
400UN315UN36le3P.NM8NDC-400C TM 315 3P.248–290
1600UN800UN36le3P.NM8NDC-1600C TM 800 3P.720–805

3.2 Leakage Protection MCCB (NM8NL)

CadreActuelLeakage CurrentPôleModèlePrix(USD)
125UN63UN500mA4BNM8NL-125S TM 63 4B RCD2510–550
250UN160UN2000mA3P.NM8NL-250S EM 160 3P RCD4990–1050
400UN315UN500mA4CNM8NL-400H EM 315 4C RCD41360–1460
  1. Price Factors & Purchasing Advice

4.1 Price Influencing Factors

FacteurPrice FluctuationExplication
Breaking Grade+20%~+150%Price rises 20%~30% per grade from S to C type
Unité de déclenchement+40%~+80%Electronic EM type 40%~80% higher than thermal-magnetic TM type
Type de montage+15%~+40%Plug-in +15%~20%, Draw-out +30%~40% vs fixed type
Numéro de pôle+10%~+50%4-pole 10%~20% higher than 3-pole
Courant nominal+5%~+30%Higher current within the same frame leads to higher cost
Accessoires+10%~+100%Déclenchement de dérivation +10%, under-voltage trip +15%, electric mechanism +80%~100%

4.2 Conseils de sélection

  1. Capacité de coupure: S(50le) for general use; H(70le) for heavy industrial; R.(100le) for key facilities.
  2. Unité de déclenchement: TM for conventional distribution; EM for intelligent monitoring and precise protection.
  3. Mounting Solution: Fixed for cost-saving; Plug-in for easy replacement; Draw-out for critical loads.
  4. Attestation: Meet GB & IEC standards with CE/UL certification for global project delivery.
  5. Quick Selection Reference
ApplicationModèle recommandéParamètres clésPrix(USD)
Residential DistributionNM8N-125S TM 100 M 3P125Un cadre, 100UN, 50le, 3P.65–80
Bâtiment CommercialNM8N-250S TM 200 M 3P250Un cadre, 200UN, 50le, 3P.136–160
Industrial WorkshopNM8N-400H EM 350 M 3P400Un cadre, 350UN, 70le, electronic trip330–385
Large FactoryNM8N-800R EM 800 P 3P800Un cadre, 800UN, 100le, plug-in735–820
Data CenterNM8N-1600C EM 1600 D 3P1600Un cadre, 1600UN, 150le, draw-out1795–2010

Note: All prices are 2026 April market reference prices. Actual prices vary by purchase quantity, region and distributor. Confirm official quotation from authorized Chint dealers before ordering.

 