MBS 3000-1011-A1AB04-0
Général industrial pressure transmitter, Pression manométrique, 4–20 mA output
✅ Key Specifications
Plage de mesure: 0~1 bar (0~14.5 psi) Jauge
Signal de sortie: 4–20 mA (2-fil)
Alimentation: 9~32 VDC, protection contre l'inversion de polarité
Raccordement à pression: G1/4 external thread
Electrical connector: Angular DIN connector
Wetted material: AISI 316L stainless steel
Précision: Typical ±0.5%FS, max ±1%FS
Temps de réponse: ≤4 ms
Overpressure: 4 bar; Pression d'éclatement 6 times full scale
Température moyenne: -40~+85 ℃
Température ambiante: -40~+85 ℃
No built-in pulse snubber (MBS3050 equipped with snubber)
📌 Pin Definition (Angular DIN plug)
- Fournir +
- Commun (signal / supply return for 4–20mA)
2-câblage: DC24V+ → Pin1; Pin2 → PLC AI module+; AI module→ DC24V-
🛠️ Typical Applications
CVC, compresseurs d'air, traitement de l'eau, light-duty hydraulics, low-pressure pipeline monitoring. Suitable for air, water and neutral media. Low range only, 0~1 bar, mainly used for micro / low pressure monitoring.
⚠️ Sélection & Notes d'installation
- Medium must be compatible with 316L stainless steel; not suitable for strong corrosive media.
- Ne dépassez pas 4 bar overpressure; pressure spikes may damage the diaphragm.
- Minimize pressure spikes during installation; MBS3050 with snubber is recommended for water hammer conditions.
- Check total loop resistance of the 4–20mA circuit to meet the minimum supply voltage requirement of transmitter.
- Classe de protection: IP65 with connector properly tightened.
🧩 Alternative Reference
Alternative nationale: Diffused silicon pressure transmitter, G1/4, 0-1bar, 4-20mA, 316Diaphragme L
Danfoss same-series replacement: Verify range, thread and connector type. 060G1113 is 0~1 bar gauge, do not confuse with 0~4bar / 0~10bar models.
📎 Model Code Decoding (MBS3000-1011-A1AB04-0)
MBS3000: Série, no pulse snubber
1: Range code 0~1 bar gauge pressure
0: Output 4–20mA
1: G1/4 pressure connection
1: Angular DIN electrical connector
A1AB04-0: Construction, seal and option codes
- Troubleshooting Checklist for MBS3000 060G1113 (2-wire 4-20mA)
Tools required: Multimètre numérique (mA & V range), insulation tester; Do NOT plug/unplug DIN connector under power.
1) Aucune sortie / 0mA current
- Vérification de la puissance: Measure voltage between Pin1-Pin2 of transmitter, normal operating voltage 9~32VDC. Output fails below 9V.
- Polarity verification: Pin1=24V+, Pin2=signal return. Reverse polarity is protected internally, transmitter will not be damaged but no output.
- Open circuit check: Disconnect API côté, insert multimeter in series to measure loop current. If still 0mA, inspect DIN connector crimping and wire breakage.
- Water ingress / oxidation at connector: Failed sealing of angular DIN plug causes terminal corrosion; check for water stains or green rust.
- Severe diaphragm damage from overpressure: Long-term pressure exceeding 4bar deforms diaphragm and damages internal sensing element.
- Fixed at 4mA (minimum reading, no response to pressure change)
- Open circuit in loop (le plus courant): Broken wire, loose terminal or poor crimp in DIN plug.
- Diaphragm jammed: Medium crystallization, sludge or solid particles blocking diaphragm, pressure cannot be transferred.
- Internal hardware failure of transmitter, sensing element damaged.
Quick test: Disconnect transmitter, short the loop. If PLC reads ~20mA, PLC module and wiring are good, fault lies in transmitter.
- Fixed at 20mA (full scale reading, no response to pressure change)
- Short circuit in loop: Cable insulation damage causing short between positive and negative cores, shorted terminals inside DIN plug.
- Permanent damage caused by sustained overpressure; bulged diaphragm locks sensor output at full scale.
- Strongly corrosive medium penetrates 316L diaphragm and causes internal leakage.
Quick test: Remove transmitter, if PLC reading drops back, module is healthy, fault in transmitter or field wiring.
- Signal drift (zero offset, reading slowly fluctuates while pressure remains stable)
- Thermal drift: Medium temperature out of range -40~85℃ or drastic temperature cycling. MBS3000 has no high-grade temperature compensation chip, drift occurs under extreme temperature.
- Residual stress on diaphragm: Excessive tightening torque transfers stress to diaphragm; Recommended max torque ≤25 Nm for MBS3000.
- Medium deposit: Oil scale or limescale adheres to diaphragm and gradually shifts zero point.
- Alimentation instable: High ripple on switching power supply causes voltage fluctuation.
- Aging drift: Degradation of sensing element after long service time.
Étalonnage: Vent to atmospheric pressure to check if reading returns to 0bar (4mA). Large deviation requires zero correction, MBS3000 has no local zero adjustment knob, correction can only be done via controller software.
- Fluctuation des signaux / noisy reading
- Interférence électromagnétique (top reason)
Ground loop caused by shield grounding at both ends. Correct practice: Shield grounded only at control cabinet end, shield at transmitter end kept floating.
Signal cable routed together with power cables (contacteurs, motor cables). Separate routing with minimum distance ≥30cm; cross cables perpendicularly, avoid parallel laying.
- Pressure shock / water hammer: Instant pressure spikes vibrate diaphragm even for 0~1bar range; switch to MBS3050 with built-in snubber if water hammer exists.
- Bornes de câblage desserrées: Poor crimp of DIN terminals, contact resistance varies under vibration.
- Insufficient filtering on PLC module: Short filter time on AI channel amplifies noise. Increase channel filtering time.
- Air bubbles in medium: Bubbles hitting diaphragm cause signal jitter for liquid pipelines.
- Intermittent fault (reading unstable, works occasionally)
Vibration loosens connector or causes internal wire break at bending points.
Insulation expansion/contraction with temperature change leads to intermittent short/open circuit.
Condensation inside plug under high humidity, intermittent connection.
- Danfoss Same Series Comparison (MBS3000 / MBS3050 / MBS3100)
| Modèle | Caractéristiques | Application | Difference vs MBS3000 060G1113 |
| MBS3000 | General economy type, no snubber, fast response ≤4ms, 316Diaphragme L, 4-20mA/0-10V optional | CVC, air compressor, clean water, stable pressure without spikes | Modèle de référence, no pulse snubber, low range 0~1bar |
| MBS3050 | MBS3000 base with built-in pulse snubber, suppress water hammer and pressure spikes | Pump outlet, pipeline with pressure shock / water hammer | Identical mechanical dimension, built-in snubber slows response; direct mechanical replacement available |
| MBS3100 | Taille compacte, stainless housing, IP67, better vibration resistance | Espace d'installation limité, équipement mobile, high vibration environment | Smaller body; fil & connector vary for some versions; not mechanically interchangeable without verification |
Other Danfoss Pressure Transmitter Series (Alternatives)
- MBS4500: High accuracy version, ±0.25%FS, high EMC immunity; precision process and lab use; higher price than MBS3000.
- MBS5100: Heavy-duty industrial, high overpressure rating for heavy hydraulics and high-pressure systems; thick diaphragm, not suitable for 0~1bar micro pressure measurement.
- MBS9200: Differential pressure transmitter for measuring pressure difference between two points, cannot replace gauge pressure MBS3000.
✅ Replacement Selection Checklist (for 060G1113)
Vérifier 4 parameters at the same time:
- Pressure type: Jauge, measuring range 0~1 bar
- Sortir: 2-wire 4-20mA
- Raccordement à pression: G1/4 external thread
- Electrical connector: Angular DIN connector
Danfoss MBS3000 060G1113 Installation Instructions (0~1bar, G1/4, Angular DIN)
Divided into mechanical installation, installation électrique, moyen & operating condition, pre-commissioning check and prohibited operations, tailored for this low-range gauge transmitter.
- Installation mécanique (G1/4 external thread)
- Couple de serrage: Recommended ≤25 N·m. Never use wrench on black plastic DIN connector; only clamp the metal hexagon for tightening. Excessive torque creates residual stress on diaphragm, zero drift and permanent sensor damage.
- Thread sealing: G1/4 is non-sealing cylindrical pipe thread. PTFE tape or thread sealant is recommended. Wrap PTFE tape on external thread, do not wrap tape to thread tip to prevent debris entering pressure cavity and blocking diaphragm. Thick gaskets for lifting transmitter are prohibited.
- Orientation de montage
Liquid pipeline: Mount diaphragm horizontally or facing downward to avoid air bubbles trapped on diaphragm surface causing signal noise.
Gas pipeline: Mount diaphragm upward to prevent condensate accumulating on diaphragm.
Cable entry of angular DIN plug points downward, preventing rainwater / condensate flowing into plug and breaking IP65 protection.
- Pressure tap selection
Tap hole on side of pipeline, avoid bottom (sediment accumulation blocking diaphragm) or top (gas accumulation).
Add short nipple and support bracket for high vibration pipeline to reduce vibration transfer to transmitter.
- Pressure protection (this model only 0~1bar range)
Max continuous overpressure 4 bar. Burst pressure is much higher, but instantaneous water hammer spike can easily rupture diaphragm. MBS3000 has no built-in snubber, switch to MBS3050 if pressure spike / water hammer exists.
Remove transmitter or isolate with shut-off valve before pipeline hydro test. Never perform pipeline purging with transmitter mounted, high-speed particles scratch 316L diaphragm.
- Thermal isolation: Fit cooling nipple / heat dissipation sleeve when medium temperature approaches upper limit 85℃, reduce heat conduction to transmitter body and avoid thermal drift.
- Installation électrique (Angular DIN EN175301-803-A, 2-wire 4-20mA)
- Power-off wiring rule: Disconnect 24V power before wiring or plug/unplug DIN connector. Arcing under live condition may damage internal circuit.
- Affectation des broches: Pin1 = 24V+; Pin2 = signal return (-); Pin3 unused. Polarity must be correct. Reverse polarity protected but no output.
- Cable selection & shielding
Recommandé: 0.5~0.75mm² shielded twisted pair cable; use 0.75mm² for distance >100m.
Bouclier: Ground shield only at control cabinet end, leave shield floating at transmitter DIN plug side. Grounding at both ends creates ground loop and signal noise.
Separate signal cables from power cables, minimum distance ≥30cm; cross perpendicularly, avoid parallel routing.
- Loop load: Max allowable loop resistance approx. 600Ω at DC24V supply; PLC AI module internal resistance ≤250Ω normally, meets requirement.
- Classe de protection: IP65 only when DIN plug fully tightened and intact sealing gasket fitted. Manquant / damaged gasket causes water ingress and terminal corrosion.
- Moyen & Ambient Requirements
- Wetted material AISI316L stainless steel: Medium must be compatible with 316L. Clean water and compressed air are acceptable. Not suitable for strong acid, strong alkali or high chloride corrosive medium. Medium cannot contain large solid particles to avoid diaphragm scratch.
- Plage de température
Température moyenne: -40 ~ +85℃
Température ambiante: -40 ~ +85℃
Temperature out of range increases thermal drift significantly or permanently damages sensing element.
- Environnement: Avoid direct long-time sunlight, strong vibration, strong electromagnetic equipment (onduleur, contacteur) installed nearby. Transmitter housing can connect protective earth.
- Pre-commissioning Check List
- Mécanique: Confirm thread leak-free, correct tightening torque, pressure shut-off valve closed.
- Électrique: Verify wiring with multimeter, no short / circuit ouvert; double check Pin1/Pin2 polarity before power-up.
- No-load calibration after power on: Vent to atmospheric pressure (0bar), loop current should read 4mA.
- Slowly open pressure valve and pressurize gradually, sudden full opening causing pressure shock is prohibited. Check current 20mA at full scale 1bar.
- Monitor reading for 5~10 minutes, confirm stable reading without drift or noise.
- Opérations interdites
❌ Do NOT tighten transmitter by clamping black plastic DIN connector with wrench
❌ Do NOT perform pipeline purging or pressure test with transmitter mounted
❌ Do NOT subject to sustained pressure over 4 bar or instantaneous water hammer shock
❌ Do NOT ground cable shield at both ends
❌ Do NOT exceed medium temperature limit 85℃
❌ Do NOT touch diaphragm with hard objects; scratched or dented diaphragm is permanently damaged
❌ MBS3000 has no local zero adjustment knob, do NOT disassemble transmitter for calibration
- Recommended Accessories for Installation
Pressure shut-off valve (for isolation and transmitter replacement online)
Cooling nipple (high temperature medium)
PTFE thread tape
Shielded twisted pair cable
Spare sealing gasket for DIN plug
Danfoss Industrial Pressure Transmitter Product List (MBS / DST / AKS)
Grouped by application, highlight difference vs MBS3000 (060G1113) for model selection & remplacement
- Main MBS Industrial Series
- MBS1200 / MBS1250|Compact OEM for mobile hydraulics
MBS1200: No pulse snubber; MBS1250: Built-in pulse snubber
Application: Construction machinery, mobile hydraulics, on-board equipment; high vibration & résistance aux chocs
Sortir: Mostly ratiometric voltage output, few 4-20mA types; Max medium temp 125℃
Gamme: 0~10bar to 0~600bar
- MBS1700 / MBS1750|Economical general transmitter
MBS1700: No snubber; MBS1750: With pulse snubber
Application: CVC, air compressor, traitement de l'eau, low-cost alternative for MBS3000
Précision: ±0,5 % PE; 316Diaphragme L; angular DIN plug, similar outline to MBS3000
- MBS3000 / MBS3050【Your reference series】
MBS3000: No pulse snubber, fast response ≤4ms; reference model 060G1113 (0~1bar gauge, G1/4, angular DIN, 4-20mA)
MBS3050: Same outline, built-in pulse snubber, suppress water hammer and pressure spikes; preferred for pump outlet
Sortir: 4-20mA, 0-10V; jauge / absolute pressure optional; range 0~1bar~0~600bar; wetted AISI316L
Typical industry: CVC, air compressor, clean water, low-pressure process
- MBS3100 / MBS3150|Compact small size
MBS3100 no snubber, MBS3150 with snubber; compact footprint for limited mounting space
Protection IP67; better vibration resistance than MBS3000; multiple thread options; logement différent, cannot mechanically replace MBS3000 without verification
- MBS3200 / MBS3250|High temperature type
MBS3200 no snubber, MBS3250 with snubber; high medium temperature version
Suitable for hot water, heat traced pipeline, high temperature process medium
- MBS3300 / MBS3350|Compact high temperature
Dedicated high temperature application; withstand higher medium temperature; 316L wetted part; eau chaude & hot oil circuit
- MBS33 / MBS33M|Marine high accuracy
MBS33M: Marine certified version, high vibration & Immunité CEM, class certification; range 0~1bar~600bar
Accuracy ±0.3%FS; 4-20mA; jauge / pression absolue; seawater and marine pipeline pressure monitoring
- MBS4000 / MBS4050|High accuracy general industrial
MBS4000 no snubber; MBS4050 with snubber; accuracy ±0.3%FS; support field zero & span adjustment
Industrial process, precision pressure monitoring; higher accuracy than MBS3000
- MBS4201 / MBS4251|Explosion-proof (Ex)
MBS4201 no snubber; MBS4251 with snubber; intrinsically safe certified for hazardous area (chimique, gaz)
4-20mA 2-wire; 316Diaphragme L; 普通MBS3000 cannot be used in explosion hazardous area
- MBS4500 / MBS4510|High accuracy field calibratable
MBS4500: Basic high accuracy; MBS4510: With flush diaphragm; accuracy ±0.25%FS
Built-in zero and span adjustment; lab & precision process; coût plus élevé
- MBS4701 / MBS4751|Explosion-proof high accuracy
MBS4701 no snubber; MBS4751 with snubber; antidéflagrant + haute précision; chemical hazardous process
- MBS5100 / MBS5150|Heavy-duty industrial / heavy hydraulics
MBS5100 no snubber; MBS5150 with snubber; thick diaphragm, high overpressure rating; heavy hydraulics, exploitation minière, high pressure pump station
Range starts from high pressure, not suitable for 0~1bar micro pressure measurement
- MBS8200 / MBS8250|New generation heavy-duty high performance
MBS8200 no snubber; MBS8250 with snubber; superior EMC immunity (100V/m); max medium temp 125℃; functional safety available
Mobile hydraulics, high pressure shock application
- MBS9200 / MBS9300|Differential pressure transmitter
Differential pressure measurement (pressure difference between two points), not gauge pressure; couler & level DP measurement; cannot replace gauge pressure MBS3000
- DST Series New Generation Digital / Corrosion Resistant Transmitter
- DST P300 / DST P30M: General digital pressure sensor, 4-20mA / digital signal, compact form
- DST P40M: Stainless steel general model
- DST P40I: Titanium wetted part, for corrosive medium (seawater, chemical brine), corrosion upgrade alternative for 316L
- AKS Series (CVC & Refrigeration dedicated Danfoss product line)
Mainly for chiller, chambre froide, refrigerant pressure monitoring, not recommended for general water / compressed air process
AKS 32: Refrigeration pressure transmitter, 4-20mA
AKS 33: Refrigeration high/low pressure, dedicated for R-series refrigerant
AKS 4100: Refrigerant pressure sensor
EMP2 Embedded Pressure Sensor
OEM miniature pressure sensor, built-in equipment installation, rarely used as standalone field transmitter
📋 Quick Selection Comparison Table
| Série | Snubber | Précision | Application principale | Replace MBS3000 060G1113? |
| MBS3000 | Non | ±0,5 % PE | CVC, air compressor, clean water low pressure | ✅ Direct mechanical replacement if parameters match |
| MBS3050 | Built-in pulse snubber | ±0,5 % PE | Pipeline with water hammer & pressure spike | ✅ Same mechanical interface, signal unchanged, réponse plus lente |
| MBS1700 | Non | ±0,5 % PE | Economical HVAC & air compressor | ✅ Similar outline, verify thread & connector |
| MBS4500 | Non | ±0.25%FS | Precision process | ❌ Different outline, une plus grande précision & coût |
| MBS5100 | Facultatif | ±0,5 % PE | Heavy-duty high pressure hydraulics | ❌ Diaphragm design unsuitable for 0~1bar micro pressure |
| MBS4201 | Facultatif | ±0,5 % PE | Explosion hazardous area | ❌ Explosion-proof model, unnecessary for normal area |
| MBS9200 | Pression différentielle | ±0.3%FS | DP measurement | ❌ Different measuring principle, cannot replace gauge pressure |
✅ 4 Parameters to Verify for MBS3000 060G1113 Replacement
- Pressure type: Jauge, measuring range 0~1 bar
- Sortir: 2-wire 4-20mA
- Raccordement à pression: G1/4 external thread
- Electrical connector: Angular DIN connector