Fluke 376-FC AC/DC Clamp Meter - Contacteur,disjoncteur,onduleur solaire,compteur électrique,capteur,Encodeur,API

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-mail: kent@bestcontactor.com

À propos Contact |

 Fluke 376-FC AC/DC Clamp Meter - Contacteur,disjoncteur,onduleur solaire,compteur électrique,capteur,Encodeur,API

compteur d'électricité/

Fluke 376-FC AC/DC Clamp Meter

FC Meaning: Fluke-Connect, Bluetooth wireless connection, supporting mobile APP data logging, trend graphing and on-site report generation. Part of the 370-FC series industrial-grade clamp meters. Supplied standard with an 18-inch iFlex flexible current probe (optional for 375-FC). Core Specifications Item Specifications Jaw AC/DC Current 0‑1000A (True‑RMS) iFlex Flexible Probe AC Current 0‑2500A AC AC/DC Voltage ...

  • Détails du produit

FC Meaning: Patte-Connect, Bluetooth wireless connection, supporting mobile APP data logging, trend graphing and on-site report generation.

Part of the 370-FC series industrial-grade clamp meters. Supplied standard with an 18-inch iFlex flexible current probe (optional for 375-FC).

Spécifications de base

ArticleCaractéristiques
Jaw AC/DC Current0‑1000A (True‑RMS)
iFlex Flexible Probe AC Current0‑2500A AC
AC/DC Voltage0‑1000V AC/DC
Fréquence5‑500Hz (for both meter jaw and iFlex)
Résistance0‑60kΩ with continuity test
Capacitance0‑1000μF
DC Millivolts500mV range
Jaw Opening34 mm
Cote de sécuritéCAT‑III 1000V / CAT‑IV 600V
Alimentation4 × Piles AA
Garantie3‑year

Principales fonctionnalités

  1. VFD Low-pass Filter: Optimized for VFD output measurements, suppresses carrier-frequency interference for accurate motor-drive readings; not available on 374-FC.
  2. In-Rush Surge / Starting Current Mode: Filters noise to accurately capture motor inrush current, matching real-world conditions seen by protective devices.
  3. Fluke-Connect Bluetooth Wireless: Remote readings via mobile device, enregistrement de données, trend curves, on-site PDF report generation; ShareLive video call for collaborative troubleshooting, keeping users away from arc-flash hazards.
  4. Min. / Max. / Average recording: Captures intermittent fault fluctuations.
  5. iFlex Flexible Coil: Enables measurements in confined spaces and on large-diameter cables without cable disconnection.

Liste de colisage standard

376-FC clamp meter main unit

i2500-18 iFlex flexible current probe (18-pouce)

Test leads and test probes

TPAK magnetic hanging strap

Étui de transport souple

User manual and safety manual

Comparaison des séries (374-FC / 375-FC / 376-FC)

ModèleJaw AC/DC CurrentiFlex IncludedVFD FilterDC‑mV
374‑FC600UN❌ Optional
375‑FC600UN❌ Optional
376‑FC1000UN✅ Standard

Conseil de sélection: Choose 376-FC for 1000A AC/DC, frequent VFD testing, high-current work and wireless logging. Choose 375-FC for applications within 600A.

Applications typiques

Moteurs industriels, variateurs de fréquence, distribution panels, UPS, Onduleurs photovoltaïques

Plant electrical maintenance, equipment commissioning, diagnostic de panne, motor inrush-current testing

On-site remote reading, data archiving and test-report generation

Usage & Notes d'entretien

  1. The iFlex flexible coil measures AC only, DC measurements must use the meter’s physical jaws.
  2. Enabling the VFD filter reduces bandwidth; disable it for standard power-frequency measurements.
  3. In-Rush mode captures transient startup events and shall not be used for steady-state readings.
  4. Second-hand inspection checklist: Undamaged jaws, intact iFlex coil, functional Bluetooth, sound lead insulation, valid calibration status.

Fluke 375-FC vs 376-FC Key Differences

Both support Fluke-Connect Bluetooth, VFD filter, In-Rush mode, DC-mV and True-RMS, with identical safety ratings. Differences lie in jaw current range, iFlex inclusion and crest factor.

Article de comparaisonFluke 375‑FCFluke 376‑FC
Jaw AC/DC Current600A AC/DC1000UN (999.9UN) CA/CC
iFlex Flexible ProbeFacultatif, max 2500A ACStandard i2500‑18 (18‑inch), max 2500A AC
Plage de tension1000V CA/CC1000V CA/CC
VFD Filter✅ Pris en charge✅ Pris en charge
In‑Rush Motor Surge✅ Pris en charge✅ Pris en charge
DC‑mV 500mV✅ Pris en charge✅ Pris en charge
Bluetooth FC Wireless✅ Pris en charge✅ Pris en charge
Crest Factor (FC)3 @ 600A3 @ 500A; 2.5 @ 1000A, better distorted‑current performance at high current
Jaw Opening34 mm34 mm
Garantie3‑year3‑year

Plain-language Explanation

  1. 375-FC: 600A upper limit

Suitable for most low-voltage distribution panels, motors and loads up to 400A. iFlex coil is sold separately. Cost-effective for routine plant maintenance where 600A is sufficient.

  1. 376-FC: 1000A jaw + factory-fitted iFlex

Designed for 800-1000A loads, jeux de barres, high-power UPS and high-power VFDs. Ready-to-measure up to 2500A AC out-of-box with no extra probe purchase.

⚠️ Remarque: iFlex flexible coil measures AC only. High DC current must be measured by the meter’s built-in jaws.

Guide de sélection

Most operating conditions ≤600A, rare high-AC-current work → 375-FC

Frequent 800-1000A measurements, regular large-AC-current testing, no wish to buy iFlex separately → 376-FC

Second-hand Purchase Notes

Many used 375-FC units do not include iFlex. Genuine complete 376-FC units come with the i2500-18 flexible coil.

For both models verify: VFD filter function, In-Rush mode, Bluetooth connectivity, jaw movement and lead insulation integrity.

Différences d'application: Fluke 375-FC vs 376-FC

Feature sets are nearly identical: VFD filter, In-Rush surge, Fluke-Connect Bluetooth and DC-mV are all present. Application gaps stem from two core points:

① Maximum jaw current: 600A AC/DC for 375-FC; 1000A AC/DC for 376-FC

② iFlex is factory-supplied on 376-FC but must be purchased separately for 375-FC.

🟢 375-FC Application Scope (600A jaw, iFlex optional)

For general-purpose plant maintenance with steady-state load current ≤600A and rare >600A DC measurements.

  1. Medium-small VFD-driven motors: 30-200 kW motors, MCC cabinets; measure operating current, startup inrush and VFD output (VFD filter enabled).
  2. General low-voltage distribution panels: Feeder circuits, ≤400A molded-case breaker loops; routine inspection and preventive maintenance with data logging.
  3. DC-side work: DC power panels, small-capacity UPS and DC busbars, for DC currents no higher than 600A.
  4. Bâtiments commerciaux, HVAC and general equipment commissioning: iFlex probe may be purchased later if occasional high-AC-current measurement is needed.
  5. Maintenance teams: Majority circuits sit below 600A; cost-optimized choice when iFlex is not used daily.

⚠️ 375-FC Limitations

Jaw DC measurement is capped at 600A. DC above this value cannot be measured (iFlex works for AC only).

Flexible coil is not supplied; extra procurement required for large cables or tight-fit busbar measurements.

🔴 376-FC Application Scope (1000A jaw, iFlex standard)

Targets high-current scenarios, frequent 600-1000A AC/DC measurements and regular flexible-probe usage for large cables / jeux de barres.

  1. Heavy-duty industrial motors: 200-450 kW motors with operating current at or above 600A; motor inrush testing and high-power VFD circuit diagnostics.
  2. High-power UPS, low-voltage busbars and incoming cabinets: Transformer secondary and 800-1000A incoming-feed circuits; direct high-DC-current readings via main jaws.
  3. PV and energy-storage PCS converters: Mixed AC-DC environments; capable of near-1000A DC readings which cannot be achieved by the 375-FC.
  4. Frequent iFlex-probe deployments: Congested cable trays, busbars and oversized cables that cannot fit within standard jaws; 2500A-AC measurement capability available immediately out-of-box.
  5. System integration, project commissioning & EPC sites: Mixed-spec loads covering low-ampere loops through kilo-ampere incoming feeds; one-meter coverage; remote readings for test-reporting and arc-flash hazard mitigation.

⚠️ 376-FC Caveat

iFlex remains AC-only; 1000A DC is measured exclusively through the physical meter jaws.

Référence de sélection rapide

État de fonctionnementModèle préféré
Most circuits ≤600A, seldom encounter high‑current loads, infrequent iFlex use375‑FC
Regular >600A AC/DC loads (incoming cabinets, high‑power PCS, gros moteurs)376‑FC
Frequent large‑cable / busbar work, want iFlex included as standard376‑FC
DC current routinely exceeds 600A (energy‑storage, heavy‑duty DC busbars)376‑FC only (iFlex cannot measure DC)
Budget‑constrained, iFlex can be procured later on demand375‑FC

Common Field Pitfall Reminder

The iFlex flexible probe measures AC only.

👉 High DC current must always use the meter’s hard jaws regardless of model; flexible coils offer no DC capability.

Therefore for energy-storage / PCS DC-side currents above 600A, the 375-FC will overflow; 376-FC is mandatory.