LUCA05BL Spécifications du produit - Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-mail: kent@bestcontactor.com

À propos Contact |

LUCA05BL Spécifications du produit - Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur

onduleur solaire/électrique/contacteur/

LUCA05BL Spécifications du produit

LUCA05BL is a standard control unit of Schneider’s TeSys U series, suitable for three-phase motors. It features an adjustable rated current of 1.25–5A, a control voltage of 24V DC, and a Class 10 thermal overload rating. Equipped with protection against overload, court-circuit, perte de phase, phase interruption, and ground fault, it is designed for direct-on-line ...

  • Détails du produit

LUCA05BL is a standard control unit of Schneider’s TeSys U series, suitable for three-phase motors. It features an adjustable rated current of 1.25–5A, a control voltage of 24V DC, and a Class 10 thermal overload rating. Equipped with protection against overload, court-circuit, perte de phase, phase interruption, and ground fault, it is designed for direct-on-line starting control of motors below 1.5kW (400V).

ParamètreValeurDescription
Série compatibleTeSys UStandard control unit (Série LUCA)
Courant nominal (Et)1.25-5ARéglable; rated continuous current (ui)=5A
Tension de contrôle24À DCOperating voltage of the control circuit
Thermal Overload ClassClasse 10Conforme à la CEI 60947-4-1
Tension du circuit principal≤690 V CAConvient aux moteurs triphasés
Puissance du moteur (400V)≤1.5kWTriphasé, 50/60Hz
Protection contre les courts-circuits65UN (instantané)Non réglable
Fonctions de protectionOverload/Short Circuit/Phase Loss/Current Unbalance/Ground FaultManual reset required
Dimensions (L×H×P)45×66×60mmStandard modular installation
Lieu d'origineFranceOriginal imported product

Positionnement du produit & Applications

– As a standard control unit of the TeSys U series, it combines with compatible power bases (par ex., LUB05) to form a direct-on-line starter, providing basic control and protection for three-phase motors.

Scénarios d'application: Light to medium-load working conditions such as pumps, les fans, compresseurs, and small conveyor lines, suitable for industries including textile, fabrication du papier, génie chimique, and food & boisson.

Differentiation from Series Peers: Unlike LUCB (advanced type with alarm/test functions) and LUCC (communication type), LUCA only provides basic protection with a lower cost.

Sélection & Remplacement

Bases compatibles: LUB05, LUB05BL, etc.. The base must match the rated current of the control unit.

Replacement References: Equivalent models from Chint NJR2 series and ABB MS116 series. Cependant, interface and protection logic differences exist; it is necessary to verify installation dimensions and control circuit parameters.

Installation & Directives d'entretien

  1. Install via DIN rail or screw mounting; modular plug-and-play design enables quick replacement.
  2. The control circuit requires an external 24V DC power supply. Set Ir (1.25-5A) on the main circuit according to the motor’s rated current.
  3. Manual reset is required after a fault. Ground fault protection is only for equipment and does not replace personal safety protection.
  4. Plage de température de fonctionnement: -25~+60℃. Avoid dusty, humide, et environnements corrosifs; regularly check wiring and terminal tightness.

Approvisionnement & Fournir

Common Channels: Schneider authorized distributors, industrial e-commerce platforms. Reference price: approximately €60–100 (taxe incluse). In-stock delivery typically takes 2–5 working days.

Accessoires compatibles: Can be paired with LUFDA local alarm module and LULC remote signal module to expand status monitoring functions.

Detailed Comparison Between Schneider TeSys U Series LUCA05BL and LUCB05BL

Dimension de comparaisonLUCA05BL (Modèle standard)LUCB05BL (Advanced Type)
Positionnement de baseBasic motor protection & direct-on-line starting controlProtection améliorée + alarme de panne + test functions
Plage de courant nominal1.25-5A1.25-5A
Tension de contrôle24À DC24À DC
Thermal Overload ClassClasse 10 (CEI 60947-4-1)Classe 10 (CEI 60947-4-1)
Puissance moteur compatible (400V)≤1.5kW≤1.5kW
Tension du circuit principal≤690 V CA≤690 V CA
Fonctions de protection de baseSurcharge, court-circuit, perte de phase, déséquilibre de courant, défaut à la terreSame as LUCA05BL, plus overload pre-alarm function
Fonctionnalités spécialesManual reset only; no alarm/test functions1. Fault alarm output: Relay contact signal, connectable to indicator lights or PLC
2. Manual test function: Simulate faults without power supply to verify protection logic
3. Indication d'état: Multi-color LED distinguishes running/overload/short circuit/phase loss status
Méthode de réinitialisationManual reset onlyRéinitialisation manuelle + external remote reset signal support (accessories required)
Compatibilité des accessoires modulairesSupports basic bases only (par ex., LUB05)Compatible with LUFDA local alarm module and LULC remote signal module; supports expansion
Méthode d'installationDIN rail/screw mounting; prêt à l'emploiSame as LUCA05BL; dimensions d'installation cohérentes
Scénarios d'applicationLight/medium-load conditions without remote monitoring needs (par ex., petites pompes, les fans)Scenarios requiring fault pre-alarm and status monitoring (par ex., lignes de production automatisées, chemical equipment)
Cost Reference€60–100 (taxe incluse)€120–180 (taxe incluse), approximately twice the price of LUCA05BL
Compatibilité de remplacementBase-compatible with LUCB05BL; direct plug-and-replaceDownward compatible with LUCA05BL replacement; redundant functions but higher cost

Key Difference Summary

  1. Différences fonctionnelles: The core advantages of LUCB05BL are overload pre-alarm + alarme de panne + manual test, which can detect motor overload trends in advance to avoid downtime losses. En revanche, LUCA05BL only provides post-fault protection with no pre-alarm capability.
  2. Capacité d'extension: LUCB05BL can be connected to external alarm lights, Automates, or remote monitoring modules to adapt to automated systems; LUCA05BL has no expansion interface and only meets basic control needs.
  3. Coût & Rentabilité: LUCA05BL is suitable for cost-sensitive scenarios with simple working conditions; LUCB05BL is ideal for industrial scenarios requiring high reliability. Although it has a higher price, it can reduce fault troubleshooting time and maintenance costs.

Recommandations de sélection

– If end customers only require “basic motor protection against damage”, prioritize LUCA05BL for higher cost-effectiveness.

– If customers operate in scenarios such as automated factories and production lines that require fault pre-alarm and remote monitoring, recommend LUCB05BL to improve equipment operation rate.

Cross-Brand Selection Comparison Table: Schneider LUCA05BL/LUCB05BL vs. Chint NJR2-5 vs. ABB MS116-5

Dimension de comparaisonSchneider LUCA05BLSchneider LUCB05BLChint NJR2-5ABB MS116-5
Positionnement des séries de produitsTeSys U standard control unitTeSys U advanced control unitNJR2 series thermal overload relayMS116 series motor starter protection circuit breaker
Plage de courant nominal1.25-5A (réglable)1.25-5A (réglable)1.6-5A (réglable)1.6-5A (réglable)
Tension de contrôle24À DC24À DCNo control circuit (passive)No control circuit (passive)
Thermal Overload ClassClasse 10Classe 10Classe 10Classe 10
Puissance moteur compatible (400V)≤1.5kW≤1.5kW≤1.5kW≤1.5kW
Tension du circuit principal≤690 V CA≤690 V CA≤660V AC≤690 V CA
Fonctions de protection de baseOverload/Short Circuit/Phase Loss/Current Unbalance/Ground FaultOverload+Short Circuit+Phase Loss+Current Unbalance+Ground FaultSurcharge, Phase Interruption, Current UnbalanceSurcharge, Court-circuit, Perte de phase, Current Unbalance
Overload Pre-Alarm, Fault Alarm OutputNo short circuit/ground fault protectionNo ground fault protection
Fonctionnalités spécialesRéinitialisation manuelleManual/remote resetManual/automatic reset optionKnob-type current adjustment
Modular plug-and-playFault alarm contactTaille compacte, faible coûtIntegrated circuit breaker function
Manual test functionManual closing/opening operation
Accessory expansion support
Méthode d'installationDIN rail/screw mountingDIN rail/screw mountingMontage sur rail DINMontage sur rail DIN
Requires TeSys U base (par ex., LUB05)Compatible with full range of TeSys U basesDirect combination with contactorsConception intégrée, no base required
Scénarios d'applicationLight-load conditions, cost-sensitive scenariosLignes de production automatisées, fault pre-alarm required scenariosDomestic industrial supporting, low-end equipment supportingMid-to-high-end industrial scenarios requiring integrated circuit breaker functions
Petites pompes/ventilateursChemical/textile equipmentDistribution boxes/pumps & les fansProduction lines/compressors
Cost Reference (Tax Included)€60–100€120–180RMB 80–150€90–160
Compatibilité de remplacementBase-compatible with TeSys UBase-compatible with LUCA05BLCâblage simple; cross-brand replacement of international models requires mounting hole adjustmentConception intégrée; cross-brand replacement requires main circuit wiring matching
Cross-brand replacement requires wiring modificationDirect replacement for LUCA05BL

Key Selection Conclusions

  1. Chint for Cost Priority: NJR2-5 has the lowest price, suitable for domestic low-end equipment supporting, but lacks short circuit and ground fault protection and needs to be used with additional circuit breakers.
  2. ABB for Integrated Control: MS116-5 is an integrated protection circuit breaker with built-in closing/opening functions, requiring no base matching, suitable for scenarios with high integration requirements.
  3. Schneider LUCB for Automated Scenarios: Equipped with alarm and test functions, it can be connected to PLCs for remote monitoring, reducing fault troubleshooting time, ideal for high-end production lines.
  4. Schneider LUCA for Basic Protection: Balanced functions with a lower price than LUCB and ABB, suitable for overseas small and medium-sized customers without monitoring needs.

Export Adaptation Tips (For Markets Such as Algeria)

– Both Schneider and ABB products are certified by IEC and CE, directly meeting the import certification requirements of African countries such as Algeria.

– Chint NJR2-5 requires additional local access documents such as SASO certification. Some channels can handle the certification on behalf of customers, with a cost increase of approximately 10%–15%.

Précédent:

Suivant:

Laisser une réponse

Laisser un message