Contacteur CA ABB A185-30-11-80 - Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-mail: kent@bestcontactor.com

À propos Contact |

 Contacteur CA ABB A185-30-11-80 - Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur

contacteur/

Contacteur CA ABB A185-30-11-80

Numéro de commande: 1SFL491001R8011,Code SH: 85364900 ✅ Model Code Explanation A185: Taille du cadre, AC-3 rated current 185A @400V 30: 3 normally open main poles, 0 normally closed main poles (3-pôle) 11: Auxiliary contacts 1NO + 1Caroline du Nord 80: Coil code → AC220~230V 50Hz / AC230~240V 60Hz ✅ Key Electrical Parameters Main circuit rated voltage: 690V (CEI), UL ...

  • Détails du produit

Numéro de commande: 1SFL491001R8011,Code SH: 85364900

✅ Explication du code modèle

A185: Taille du cadre, AC-3 rated current 185A @400V

30: 3 normally open main poles, 0 normally closed main poles (3-pôle)

11: Auxiliaire contacts 1NO + 1Caroline du Nord

80: Coil code → AC220~230V 50Hz / AC230 ~ 240 V 60 Hz

✅ Key Electrical Parameters

Main circuit rated voltage: 690V (CEI), UL 600V

AC-3 (Charge du moteur):

380/400V: 185UN, for 90kW motor

690V: 170UN, for 132kW motor

AC-1 (Charge résistive): 275A @690V (40℃)

Courant thermique conventionnel Ith: 275UN

Tension d'isolement Ui: 1000V; Tension de tenue aux chocs Uimp: 8kV

Durée de vie mécanique: 5 millions d'opérations; Durée de vie électrique AC-3: maximum 300 opérations/heure

Courant de tenue de courte durée: 2000A for 1s; 1500A for 10s

✅ Coil Parameters (220ACC)

Inrush power: 550Virginie (50Hz) / 600Virginie (60Hz)

Sealed holding power: 35Virginie (50Hz) / 40Virginie (60Hz), holding power consumption 12.5W

Plage de fonctionnement de la bobine: 0.85~1.1×Uc, max ambient temperature 70℃

✅ Wiring & Dimensions

Main circuit copper cable: 6~185mm²; Aluminium cable 25~150mm²; Wiring torque 18N·m

Dimension hors tout: W111.5 × D160 × H196 mm, Net weight 2.9kg

Protection: Coil terminals IP20, main terminals IP00

✅ Replacement Information (Important)

A185 belongs to the old A series, abandonné; Direct upgrade replacement model: AX185-30-11-80 (série AX, même note, same coil, drop-in replacement)

✅ Optional Accessories

Relais de surcharge thermique: TA200DU (for 185A range)

Auxiliary contact blocks: CA5, CAL5 series

Suppresseur de surtension, verrouillage mécanique, barrière de phase, terminal protective cover

Comparaison: ABB A185-30-11-80 VS AX185-30-11-80

Suffixe -80 same definition: AC220 ~ 230 V 50 Hz / AC230 ~ 240 V 60 Hz; Mounting hole position, main terminal layout and auxiliary contact definition are fully compatible, direct on-site replacement

ArticleA185-30-11-80 (Old A series, Discontinué)AX185-30-11-80 (New AX series, Actif)Remarques
Numéro de commande.1SFL491001R80111SFL491074R8011Different part numbers, do not mix for ordering
Statut du produitDiscontinué, stock consumption onlyProduction de masse, available from stockOfficial recommended upgrade replacement
Configuration des contacts principaux3 NO main poles3 NO main polesIdentique
Contacts auxiliaires intégrés1NON+1NC1NON+1NCIdentique
AC-3@400V185UN / 90kW185UN / 90kWSame motor capacity
Conventional thermal current Ith @40℃275UN250UNA185 has larger margin for AC-1 resistive loads
Tension d'isolement Ui1000V (CEI)690V (CEI)A185 supports up to 1000V applications; AX rated max 690V
Impulse withstand Uimp8kV8kVIdentique
Short-time withstand Icw (1s)2000UN1800UNA185 has slightly higher short-circuit withstand capability
Dimension W×H×D111.5 × 196 × 160 mm111.5 × 196 × 162.3 mmMême largeur & hauteur, only 2.3mm deeper, no impact on mounting
Poids net2.9 kilos3.2 kilosAX with optimized housing & magnetic circuit, slightly heavier
Durée de vie mécanique5 millions d'opérations5 millions d'opérationsIdentique
Max AC-3 operation frequency300 ops/hour300 ops/hourIdentique
Spécification de la bobineAC coil 220~230V 50HzAC coil 220~230V 50HzSame code -80; appel & holding power close
MontageRail DIN + fixation par visSame mounting layoutDirect swap, no cabinet drilling or busbar modification
Compatible thermal relayTA200DUTA200DUThermal relay interchangeable
AccessoiresCA5, CAL5 aux blocks, VM interlock, barrière de phaseCompatible with VM, CA5, CAL5Most accessories compatible; few new accessories only for AX
OrigineEarly Sweden, later domestic madeMainly domestic madeAX is optimized domestic version
AttestationCCC, ULCCC, ULShared UL file, mutually recognized
Design featureClassic A-series magnetic system, thicker silver contactOptimized arc chamber, faible bruit, anti-chatter, conservative temperature rise controlAX preferred for continuous long-run & low-noise cabinet requirements

⚠️ Critical Replacement Notes

  1. Motor load AC-3 (90kW): No impact, remplacement direct
  2. Long-term AC-1 resistive load near 250A: Evaluate carefully; A185 Ith=275A provides larger margin
  3. Circuit voltage >690V: AX is not suitable, cannot replace
  4. Extra 2.3mm depth: Check clearance if contactor is fitted tight against cable trunking or door plate
  5. Stratégie pièces de rechange: New projects specify AX185 only; A185 only for emergency maintenance with existing stock
  6. This list applies to Axxx-30-11-80 (3-pôle, built-in 1NO+1NC auxiliary, Bobine AC220V, discontinued old A series); suffixe -80 = 220VAC coil
  7. AX replacement: AXxxx-30-11-80, official direct upgrade for A series
  8. Comparison basis: AC-3 @400V motor duty; 220Bobine V, built-in 1NO+1NC for Schneider LC1D and Siemens 3RT5/3RT6
  9. Note: Only electrical equivalent rating, not mechanically interchangeable; trous de montage, busbar and accessories are not compatible; HS code unified 85364900
  10. ABB Old A Series Contactor List (Discontinué, 30-11-80, 220ACC)
ModèleAC-3@400VMotor kWNuméro de commande.AX Replacement ModelAX Order No.Compatible Thermal Relay
A9-30-11-809UN41SBL141001R8011AX09-30-11-801SBL141074R8011TA25DU
A12-30-11-8012UN5.51SBL151001R8011AX12-30-11-801SBL151074R8011TA25DU
A16-30-11-8016UN7.51SBL161001R8011AX18-30-11-801SBL161074R8011TA25DU
A26-30-11-8026UN111SBL241001R8011AX25-30-11-801SBL241074R8011TA25DU
A32-30-11-8032UN151SBL291001R8011AX32-30-11-801SBL291074R8011TA42DU
A40-30-11-8040UN18.51SBL321001R8011AX40-30-11-801SBL321074R8011TA42DU
A50-30-11-8050UN221SBL351001R8011AX50-30-11-801SBL351074R8011TA75DU
A63-30-11-8063UN301SBL361001R8011AX65-30-11-801SBL361074R8011TA75DU
A75-30-11-8075UN371SBL371001R8011AX80-30-11-801SBL371074R8011TA75DU
A95-30-11-8095UN451SBL391001R8011AX95-30-11-801SBL391074R8011TA110DU
A110-30-11-80110UN551SBL401001R8011AX115-30-11-801SBL401074R8011TA110DU
A145-30-11-80145UN751SFL461001R8011AX150-30-11-801SFL461074R8011TA200DU
A185-30-11-80185UN901SFL491001R8011AX185-30-11-801SFL491074R8011TA200DU
A210-30-11-80210UN1101SFL501001R8011AX205-30-11-801SFL501074R8011TA200DU
A260-30-11-80260UN1321SFL521001R8011AX260-30-11-801SFL521074R8011TA450DU
A300-30-11-80300UN1601SFL541001R8011AX300-30-11-801SFL541074R8011TA450DU

Remarque: A series also includes A370, A400, A500 larger frames, rarely used for general projects. A series is different from AF series (AF = wide-voltage coil type, not included here)

  1. Cross-Brand Equivalent Rating Table (AC-3 400V, 220Bobine V, built-in 1NO+1NC)
ABB Old AABB New AXSchneider TeSys D LC1DSiemens SIRIUS 3RT5Motor kW @400V
A9-30-11-80AX09-30-11-80LC1D09M7C3RT6023-1AN204
A12-30-11-80AX12-30-11-80LC1D12M7C3RT6024-1AN205.5
A16-30-11-80AX18-30-11-80LC1D18M7C3RT6025-1AN207.5
A26-30-11-80AX25-30-11-80LC1D25M7C3RT6026-1AN2011
A32-30-11-80AX32-30-11-80LC1D32M7C3RT6027-1AN2015
A40-30-11-80AX40-30-11-80LC1D40M7C3RT5034-1AN2018.5
A50-30-11-80AX50-30-11-80LC1D50M7C3RT5035-1AN2022
A63-30-11-80AX65-30-11-80LC1D65M7C3RT5036-1AN2030
A75-30-11-80AX80-30-11-80LC1D80M7C3RT5044-1AN2037
A95-30-11-80AX95-30-11-80LC1D95M7C3RT5045-1AN2045
A110-30-11-80AX115-30-11-80LC1D115M7C3RT5046-1AN2055
A145-30-11-80AX150-30-11-80LC1D150M7C3RT5054-1AN2075
A185-30-11-80AX185-30-11-80LC1D170M7C3RT5056-1AN2090
A210-30-11-80AX205-30-11-80LC1D205M7C3RT5064-1AN20110
A260-30-11-80AX260-30-11-80LC1D245M7C3RT5065-1AN20132
A300-30-11-80AX300-30-11-80LC1D300M7C3RT5066-1AN20160
  1. Important Replacement Reminders
  2. A → AX is the only drop-in compatible upgrade: Same mounting pitch, terminal layout and auxiliary contact logic; no busbar modification required
  3. Schneider LC1D and Siemens 3RT5: Only electrical equivalent, not mechanically interchangeable. Rail DIN, trous de montage, terminal spacing and thermal relay interfaces are incompatible
  4. Coil code rules (common for A & HACHE):

80: AC220 ~ 230 V 50 Hz / 230~240 V 60 Hz

84: AC110~120V

83: AC48V

85: AC380~400V

  1. If you need other coil voltages (par exemple. -84 for 110V), I can export a full list with -84 numéros de pièces
  2. Thermal relays: TA series is ABB dedicated. Schneider LRD and Siemens 3RU cannot clip directly onto A / AX contactors

Old ABB A series: Larger contact margin, tenue aux courts-circuits plus élevée, rated up to 1000V insulation; suitable for heavy duty, AC-4 frequent reversing, high voltage and high-reliability legacy equipment. Drawbacks: abandonné, scarce stock, higher coil noise, shrinking accessory ecosystem.

Schneider LC1D (TeSys D): Rich accessory portfolio, wide coil options, stable stock, cost competitive. Optimized for standard AC-3 motor duty, OEM mass production, CVC, elevators and standardized automation projects. Lower overload margin for extreme heavy shock loads.

Application Scenario Difference between Old ABB A series and Schneider LC1D

✅ Preferred applications for Old ABB A series

  1. Réparation & overhaul of legacy original panels (old ABB packaged cabinets, large air compressors, extrudeuses, papier & metallurgy lines; drawing specification locked to A series, no busbar / cabinet modification allowed)
  2. AC-4 frequent reversing, jogging, heavy shock loads: palans, grues, concasseurs, tables à rouleaux, extruder main motors. Thicker silver contacts, higher thermal margin and superior 1s short-time withstand against current surges.
  3. 690V motor circuits, high-power fans/pumps, high AC-1 resistive loads: Ui=1000V, higher Ith rating, suitable for continuous full resistive loading such as heating elements, furnace banks and bus transfer.
  4. Process-critical equipment requiring high short-circuit withstand and Type 2 coordination: Production lines where contact welding is unacceptable.
  5. Integrated ABB motor control packages: Matched with ABB MCB, Tmax MCCB and TA thermal relays for factory-tested protection coordination.

❌ Not recommended for A series

Nouveaux projets, mass OEM, budget serré, heavy custom accessory requirements, stable lead time demand. A series is discontinued with rising premium and shrinking stock.

Weakness: Audible coil noise relatively high; fewer accessory choices vs LC1D; large frame stock volatile.

✅ Preferred applications for Schneider LC1D (TeSys D)

  1. Nouveaux projets, OEM batch equipment, standard control cabinets: Lignes de convoyage, machines d'emballage, general fans & pompes, HVAC chillers. Good versatility, stable supply and favorable bulk pricing.
  2. Ascenseur, crane auxiliary circuits, door motors, frein & star-point control: Mature industry adoption, contacts auxiliaires abondants, verrouillages mécaniques, timer blocks and mirror NC contacts.
  3. Solutions requiring complex accessory combinations: Verrouillage mécanique, pneumatic timer, suppresseur de surtension, extra auxiliary blocks, reversing contactor sets and star-delta modules. TeSys D has the broadest accessory range among the three brands.
  4. Wide coil selection demand: AC24V, DC24V, DC110V, wide voltage coils, ideal for direct PLC DC output driving.
  5. Export equipment with multi-certification requirements: UL, ASC, marine approvals widely available.
  6. Standard AC-3 duty, operation frequency ≤300 times/hour, without frequent jogging or heavy surges for general motors.

❌ Not recommended for LC1D

Continuous operation above 690V

High-frequency AC-4 heavy duty with repeated current surges (lower contact margin than old A series at same rating)

Direct replacement into legacy ABB cabinets (requires rework of mounting, busbars and thermal relay interface)

Tableau de comparaison

ArticleABB Old A SeriesSchneider LC1D
Load PreferenceAC-4, jogging, inversion, shock loads, high AC-1 resistive, 690V circuitsStandard AC-3 motor, general fan/pump, CVC, ascenseur, convoyeur
Core StrengthOversized contact margin, tenue élevée aux courts-circuits, 1000V insulation, matched ABB protection suiteMassive accessory library, full coil portfolio, stable stock, competitive bulk price
État de l'approvisionnementDiscontinué, residual stock onlyActive mainstream product, stable lead time; largest frames gradually phased out
Cabinet RetrofitDirect swap with AX; first choice for old ABB cabinet maintenanceNot drop-in; high modification cost
Project FitLegacy maintenance, critical heavy-duty process machinesNew panel build, OEM mass production, standard cabinets, équipement d'exportation
Niveau de bruitRelatively highModerate, newer D variants improved
ÉcosystèmeTA thermal relay, CA5 auxiliary blocks, limited accessoriesLRD thermal relay, full LA accessory range, ready reversing & star-delta kits

Guide de sélection rapide

Old ABB cabinet repair, crane/crusher frequent reversing, 690V motor, no busbar change → Prefer A stock or AX

New cabinet, mass OEM, elevator/HVAC, reversing/star-delta, budget focus, stable supply → LC1D

Heavy shock loads and long-term stocking: Avoid A on new projects; choose AX. LC1D if budget limited and margin acceptable.

Important distinction: AX is the compatible upgrade for A (même empreinte, conservative performance de-rating). LC1D is only electrically equivalent, not mechanically interchangeable.

I can provide AC-4 derating margin recommendation for A, AX and LC1D if you require.

Précédent:

Laisser une réponse

Laisser un message