Contact Phénix 2814113 Programmable Temperature Transmitter

Nom complet du modèle: MCR-T-UI, programmable temperature transmitter (custom ordered version: Pt100, 3-fil, -200~+850℃, 4-20mA output) Statut: Discontinued by manufacturer Basic Specifications Series: MCR-T isolated temperature transmitter, DIN rail mount Input: Pt100 RTD, 3-type de fil, measuring range -200℃ ~ +850℃ Output: 4…20 mA analog output Power supply: 24V DC Mounting: NS35 rail, screw connection Functions: signal ...

  • Détails du produit

Nom complet du modèle: MCR-T-UI, programmable transmetteur de température (custom ordered version: Pt100, 3-fil, -200~+850℃, 4-20mA output)

Statut: Arrêté par le fabricant

Spécifications de base

Série: MCR-T isolated temperature transmitter, Montage sur rail DIN

Saisir: Pt100 RTD, 3-type de fil, measuring range -200℃ ~ +850℃

Sortir: 4…20 mA analog output

Alimentation: 24À DC

Montage: NS35 rail, connexion à vis

Fonctions: signal isolation, temperature transmission, linear conversion, configurable par logiciel (this variant is factory preset with fixed range)

Classe de protection: IP20, for cabinet installation

Cross-reference of models in the same series

2814090: MCR-T-UI (standard programmable version)

2814100: MCR-T-UI-NC

2814113: MCR-T-UI custom fixed-parameter version (Pt100 / 3-fil / -200~850℃ / 4-20mA)

Modèle de remplacement recommandé (nouvelle génération Phénix)

MACX MCR-T-UI-UP, Numéro de commande: 2811394

Supports RTD / thermocouple / tension / current multi-input, enhanced isolation, fully configurable; mechanically compatible for rail installation, the mainstream replacement for this series.

Remarques importantes

  1. 2814113 is a factory pre-configured fixed-range version, not a blank programmable base module. Do not directly replace it with 2814090 because the range settings differ.
  2. When purchasing second-hand spare parts, verify the input type, wiring method and output signal upon receipt.
  3. Logiciel: MCR configuration software can read and verify internal parameters (legacy MCR configuration tool).

Tableau de comparaison: 2814113 (MCR-T-UI-E) VS 2811394 (MACX MCR-T-UI-UP)

Article2814113 MCR-T-UI-E (Original spare part)2811394 MACX MCR-T-UI-UP (Modèle de remplacement)
Numéro de commande.28141132811394
StatutDiscontinué, factory preloaded fixed parameters: Pt100, 3-fil, -200~850℃, 4-20mAProduit actif, all parameters fully configurable
Alimentation18~30 V CC, typical 24VDC, ≤60mA18~30VDC wide-range power supply
Isolement3-manière d'isolement (Saisir / Sortir / Pouvoir)4-manière d'isolement (Saisir, Sortir, Pouvoir, Relay circuit), higher noise immunity
Supported sensorsRTD Pt/Ni/Cu, thermocouple, potentiometer; this unit locked to Pt100 3-wireRTD Pt/Ni/Cu (2/3/4-fil), all common thermocouples, mV, potentiometer
Plage de mesureFixé: Pt100 -200 ~ +850℃Freely configurable: RTD -250~850℃, thermocouple up to 2500℃
Sortie analogiqueFixed 4…20mA4-20mA / 0-20mA / 0-10V / ±10V etc., forward/reverse range selectable
Additional outputNo relay alarm contactIntégré 1 PDT limit relay output (alarme / seuil)
Configuration methodMCR / PI-CONF-WIN legacy software; this unit is factory locked to fixed range and cannot be modified freelyFDT framework software (PACTware) + DTM, online read/write via USB adapter
Safety certificationCE onlySIL2 / PLd, suitable for safety-related circuits
InstallationNS35 DIN rail, bornes à visNS35 DIN rail, bornes à vis; rail footprint compatible for direct mounting
Précision≤0.1%FS≤0.1%FS, better cold junction compensation performance
Disposition des terminauxLegacy MCR terminal definitionDifferent terminal numbering! Cannot be wired directly when swapping, wiring modification is mandatory

✅ Critical Risk Reminder: It fits on the DIN rail mechanically, but terminal pinout is NOT compatible. Do not connect wiring directly without modification!

  1. Standard Wiring for 2814113 (MCR-T-UI-E), Pt100 3-wire

Terminal definition per original drawing

1, 2, 3: Entrée RTD (3-wire Pt100)

1: One end of RTD

2: Compensation wire (for 3-wire measurement)

3: The other end of RTD

5, 6: Analog 4-20mA output (5+, 6-, current loop to PLC AI)

11, 12: Alimentation DC24V (11=24V+, 12=0V/GND)

Remarque: 2814113 is pre-configured, no DIP switch setting required. Power on and ready: -200℃ = 4mA, 850℃ = 20mA

  1. Wiring of Replacement 2811394 MACX MCR-T-UI-UP (Target setting: Pt100 3-wire, -200~850℃, 4-20mA)

RTD 3-wire sensor: 4.1 /4.2 /4.3 (Entrée RTD)

Sortie courant analogique: 2.1(OUT+), 2.2(OUT-) → PLC 4-20mA AI channel

Alimentation: 1.1=24V+, 1.2=GND

2.3/2.4: Threshold relay contacts (leave unused if not required)

Strip length 7mm, couple de serrage 0,5 ~ 0,6 Nm, conductor 0.2~2.5mm²

  1. Commissioning Procedure for On-site Replacement
  2. Éteindre: Cut power to the module, sensor and PLC; mark and label all wire numbers
  3. Remove old module from rail and clip 2811394 to the same rail position
  4. Rewire according to new terminal definition; confirm the 3-wire Pt100 compensation core is not swapped
  5. Prepare PACTware + MACX DTM, Phoenix USB configuration cable (2902829)
  6. Allumer, connect software to module and download parameters:

Capteur: Pt100, CEI60751, 3-fil

Gamme: Lower limit -200℃, upper limit +850℃

Output mode: 4…20mA, forward (low temperature = 4mA, high temperature = 20mA)

Filtre: default 0.5s (increase value for heavy interference)

Relais: disable threshold function if not needed

  1. Étalonnage & verification (obligatoire)

Cold junction check: Compare Pt100 resistance and PLC current reading at ambient temperature

Simulation test: Use resistance box to simulate Pt100 resistance values, verify 4mA /20mA endpoints

  1. Save parameters into module, power cycle and re-test to confirm parameters are retained after power loss
  2. Archive parameter record, replacement complete
  3. Liste de contrôle de dépannage (applies to both old and new modules)

Sortie fixe 4 mA: Circuit ouvert du capteur, broken 3-wire compensation line, loose sensor terminals

Sortie fixe 20 mA: Input short circuit, Pt100 resistance out of upper limit

Instable / fluctuating reading: Sensor cable routed together with power cables, interférence avec le sol; check isolation and single-end shield grounding

New module cannot be detected by software: USB driver, DTM version, tension d'alimentation insuffisante, bornes desserrées

Phoenix Contact Temperature Transmitter Model & Order Number List

Groups: Legacy MCR-T (abandonné, y compris 2814113)|MACX MCR-T (courant dominant actuel, SIL2)|MINI MCR‑2 compact type|Loop-powered TS series (passive OLP)|Explosion-proof EX version

Abbreviation guide:

RDT: Resistance temperature detector Pt100/Pt1000; TC: Thermocouple; Interface utilisateur: Universal input; REL: With relay alarm; UP: Universal power; TP: Push-in connection; C: Customer pre-configured

  1. Legacy MCR-T Series (Discontinué, DIN screw terminal, 3-manière d'isolement)
ModèleNuméro de commande.Brief Description
MCR-T-UI2814090Universal temperature transmitter, blank programmable standard
MCR-T-UI-NC2814100Blank unconfigured, no default parameters
MCR-T-UI-E (your part)2814113Factory fixed config: Pt100 3-wire, -200~850℃, 4-20mA (key item)
MCR-T-UI-E/NC2814126Enhanced isolation, blank unconfigured
  1. MACX MCR‑T Series (Primary replacement, active, 4-manière d'isolement, SIL2/PLd, borne à vis)
ModèleNuméro de commande.Brief Description
MACX MCR-T-UI-UP2811394Universal RTD/TC/mV, sortie analogique (recommended for 2814113 remplacement)
MACX MCR-T-UIREL-UP2811378Universal input + 3 limit alarm relays, SIL2
  1. MINI MCR‑2 Compact Temperature Transmitter (6.2mm slim, vis / Push-in PT)
ModèleNuméro de commande.Description
MINI MCR-2-RTD-UI2902055RTD dedicated, borne à vis, programmable
MINI MCR-2-RTD-UI-C2902053RDT, vis, customer pre-configured
MINI MCR-2-RTD-UI-PT2905249RTD dedicated, Push-in connection
MINI MCR-2-RTD-UI-PT-C2905248RDT, Enfichable, pre-configured
MINI MCR-2-TC-UI2902049Thermocouple TC dedicated, borne à vis
MINI MCR-2-TC-UI-C2902048TC, vis, pre-configured
MINI MCR-2-TC-UI-PT2902052Thermocouple TC dedicated, Enfichable
MINI MCR-2-TC-UI-PT-C2902051TC, Enfichable, pre-configured
MINI MCR-2-T-I2902037Temperature input directly to 4-20mA output, vis
MINI MCR-2-T-I-PT2902038Temperature to 4-20mA, Enfichable
MINI MCR-2-T-REL2909887Température + alarm relay, vis
MINI MCR-2-T-REL-PT2909886Température + alarm relay, Enfichable
MINI MCR-2-T-2RO2906877Dual relay temperature alarm, vis
MINI MCR-2-T-2RO-PT2906876Dual relay temperature alarm, Enfichable
  1. MACX MCR‑TS Loop-powered Type (OLP, 2-wire loop supply, no separate 24V, HART optional)
ModèleNuméro de commande.Description
MACX MCR-TS-I-OLP2908662Loop-powered temperature transmitter, vis, standard
MACX MCR-TS-I-OLP-SP2908664Loop-powered, Version HART
MACX MCR-1TS-I-OLP-SP1145196Monocanal, CERF, Enfichable

5.Explosion-proof EX Intrinsically Safe Version (Zone 0/1/2, chemical hazardous area)

ModèleNuméro de commande.Description
MACX MCR-EX-TS-I-OLP2908660Explosion-proof loop-powered temperature transmitter
MACX MCR-EX-TS-I-OLP-SP2908661Antidéflagrant + CERF
FA MCR-EX-FD-TUI-UI-2REL-UP2907781Field-mounted explosion-proof multi-function temperature module
  1. Matching Configuration Accessories
NomNuméro de commande.But
MCR-PAC-T-USB2309000USB configuration cable for legacy MCR-T (2814xxx)
IFS-USB-PROG2902829Universal USB configuration adapter for MACX / MINI MCR‑2 (PACTware DTM)

Remplacement préféré: 2811394 MACX MCR-T-UI-UP (couverture complète des fonctions, SIL2, configurable for Pt100 3-wire -200~850℃ 4-20mA)

With alarm relay requirement: 2811378

Cabinet space limited, slim type: MINI MCR‑2‑RTD‑UI (2902055)

Passive 2-wire loop power supply: TS-I-OLP (2908662)