(Altivar Process ATV650)
Model code explanation: ATV650 = Altivar Process IP55 wall-mounted conduire; D30 = 30 kW normal duty rating; N4 = 3-phase 380~480V, without integrated input disconnect switch (version with switch carries suffix E: ATV650D30N4E)
✅ Core Electrical Specifications
Puissance nominale: 30 kW normal duty / 22 kW heavy duty (40HP / 25HP)
Fournir: 3-phase 380…480V, 50/60 Hz
Output current, service normal: 61.5 UN; heavy duty current: 39.2 UN (4 kHz carrier frequency)
Taille du cadre: Frame B (Frame B covers 30~45 kW range)
Évaluation du boîtier: IP55, wall-mounted design for local field installation, no additional control cabinet required
Refroidissement: Refroidissement par air forcé
Moteurs compatibles: Asynchronous motors, synchronous reluctance motors
Filtre CEM intégré: Classe C2 (motor cable ≤50 m), Class C3 (motor cable ≤150 m)
✅ Interfaces & Communication
Integrated Dual-port Ethernet (Modbus-TCP) + Modbus RS485
E/S numériques: 8 DEPUIS, 3 configurable relay outputs
E/S analogiques: IA / AU; on-board process PID, flow estimation, energy metering dashboard
Expansion: Supports Profibus-DP, Profinet, EtherNet/IP communication option cards
Accessoires standards: Chinese graphic keypad, QR code for maintenance access, equipment asset monitoring, drift alarm, Arrêt&Go energy-saving function
✅ Applications typiques
Water supply pumps, pompes à eaux usées, HVAC fans, tours de refroidissement, chemical fluid handling, air compressors and other process fluid loads. Focused on energy saving, asset management and predictive maintenance; adapté aux environnements poussiéreux, humid field environments (IP55)
✅ Cross-series Comparison & Remplaçants
1. ATV650D30N4E: Same power rating, with integrated load disconnect switch
2. ATV630D30N4: Same power rating, IP20 cabinet-mounted bare drive (no outer enclosure)
3. Remplacement de mise à niveau: ATV660D30N4; for heavy-duty impact loads, select ATV950
✅ Important Notes
IP55 units have stricter heat dissipation requirements; reserve vertical ventilation clearance above and below when wall mounting
Dual rating mode (Service normal / Robuste) can be switched in parameter group 5.2
Commissioning software: Alors bouge, firmware version V4.6IE47
VTT650 (Altivar Process ATV600 Series) Fault Code List
1. Fournir & Input Side Faults
1. IPF / IPL Input phase loss / 3-déséquilibre de phase
Cause: Phase d'entrée manquante, fusible grillé, severe 3-phase voltage unbalance, 3-phase detection enabled incorrectly for single-phase supply
Remède: Check incoming circuit breaker / fusibles; set IPL to nO to disable phase loss detection if running on single-phase supply
2. OVF DC bus overvoltage
Cause: Mains voltage too high, deceleration time too short, regenerative energy from high-inertia loads
Remède: Augmenter le temps de décélération; fit braking resistor; activate adaptive deceleration brA
3. ObF Overvoltage stall (trip due to excessive DC bus voltage)
Cause: Décélération rapide, high load inertia, excessive regenerative energy
Remède: Prolonger le temps de décélération; enable stall prevention; installer l'unité de freinage + resistor
4. UVF DC bus undervoltage
Cause: Mains dip, momentary power loss, loose incoming connections, contactor chatter
Remède: Vérifier l'alimentation; extend undervoltage delay; improve wiring connections
5. PHF Supply phase sequence error
Remède: Swap any two incoming phases L1/L2/L3
2. Sortir & Motor Side Faults
1. OCF Output overcurrent
Cause: Motor locked rotor, shorted output cable, motor insulation breakdown, rapid acceleration/deceleration
Remède: Disconnect motor and run no-load test; reduce acceleration/deceleration ramps; test cable insulation to earth with megger
2. SCF Output short-circuit / défaut à la terre
Cause: Damaged motor cable shorted to earth, motor winding earth fault, failed drive IGBT
Remède: Disconnect motor and test drive output separately; measure motor winding insulation to earth
3. OPF2 / OPF Output phase loss (motor phase loss)
Cause: Loose motor terminals, open output contactor, small motor running at light load
Remède: Tighten motor wiring; disable OPL phase loss detection if an output contactor is used; disable phase loss protection for small motors
4. OLF Motor thermal overload
Cause: Continuous overloading, rotor bloqué, motor thermal current ITH parameter set too low
Remède: Réduire la charge; adjust motor thermal current ITH; wait for motor to cool before reset
5. OLC Drive hardware current limit overload
Remède: Réduire la charge; check output for short circuits; lower carrier frequency
6. OTF1 / OTF2 Motor PTC thermistor overheat
Cause: Motor winding overtemperature, broken or shorted PTC probe
Remède: Check motor temperature; measure PTC resistance; disable this protection if no temperature probe is fitted
3. Drive Overheating Faults
1. OHF Drive heatsink overtemperature (common fault)
Cause: Failed cooling fan, clogged filter, insufficient mounting clearance, température ambiante élevée, heavy dust accumulation
Remède: Clean air filter; check cooling fan; set fan permanent ON mode; maintain vertical ventilation clearance; monitor heatsink temperature parameter THD
2. OHFd DC reactor overtemperature
Remède: Réduire la charge; improve enclosure ventilation
4. Braking Circuit Faults
1. bUF Braking circuit fault
Cause: Open braking resistor, failed braking IGBT, câblage lâche
Remède: Check braking resistor resistance and connections; test braking unit at no load
2. bOF Braking resistor overload
Remède: Select higher resistance braking resistor; prolonger le temps de décélération
5. Safety Circuit Faults (Arrêt sécurisé du couple STO)
1. SAFF STO safety circuit fault
Cause: Mismatched timing between STOA and STOB (time difference >1 s), câblage cassé, internal hardware fault
Remède: Check both STO wiring paths; ensure STOA and STOB switch simultaneously; both paths must be shorted together for bypass
2. SdF Safety function active (normal stop, not a hardware fault)
Statut: STO terminals open, drive locked; reset only after restoring STO wiring
6. Communication & Analog Signal Faults
1. CnF1~CnF4 Communication link fault (Modbus-TCP / RS485)
Cause: Damaged Ethernet cable, incorrect termination resistor, Conflit d'adresse IP, electrical noise interference
Remède: Inspect cables; use shielded communication cable; verify IP settings; reduce baud rate
2. AIF Analog input wire break (4–20 mA current signal)
Cause: Broken sensor cable, circuit ouvert, signal below 4 mA
Remède: Check transmitter and signal wiring; lower wire-break threshold if required
3. AOF Analog output fault
7. Internal Hardware Faults (InF series, generally hardware damage)
1. InF8 Internal power supply fault (power board supply abnormal)
Remède: Full power cycle; repeated fault = replace power board
2. InFL (InF21) Real-time clock fault, keypad communication failure
Remède: Remove keypad, remove battery and re-power; replace keypad; if fault persists, replace control board
3. InF1~InF7, InF9~InF30 Other internal hardware errors
Remède: Cycle d'alimentation; fault cannot be cleared → control board / power board damaged, requires repair or replacement
8. Process-specific Faults (Pompe / fluid functions exclusive to ATV650)
1. iPPF Low inlet pressure protection (dry-run / low suction protection)
Cause: Insufficient inlet pressure, faulty pressure transmitter, protection threshold set too high
Remède: Check pipeline suction pressure; calibrate pressure transducer; reduce low-pressure threshold
2. HPF High pressure protection, LPF Low pressure protection, FLF Flow fault
3. DryF Dry-run protection (pump running without fluid)
Remède: Verify pump suction availability; adjust dry-run current threshold
9. Other General Faults
1. FrF Frequency feedback fault (encoder wire break)
2. USF Motor autotune failed on power-up
3. CLF Cooling circuit fault (water-cooled versions only)
4. tJF Motor stall protection
10. Fault Reset Methods
1. Réinitialisation automatique: Enable automatic retry via parameter Atr
2. Réinitialisation manuelle: Assign DI terminal function rSF for remote reset; reset via keypad
3. Internal hardware faults (InF codes): Require full power cycle; some faults need board replacement
Model Prefix Rules
VTT650: Altivar Process IP55 wall-mounted variable speed drive (3-phases 380~480V)
U: Low power range (0.75~7.5 kW); D: Medium power range (11~90 kW); C: High power floor-standing unit (110 kW et plus, IP54)
N4: Without integrated disconnect switch; N4E: With integrated load disconnect switch
Évaluation du boîtier: All wall-mounted units = IP55; floor-standing C models = IP54
Wall-mounted IP55 Full Model List (N4 without switch / N4E with switch, main domestic variants)
Frame A (0.75~22 kW)
| Puissance nominale | Model without switch | Model with switch |
| 0.75 kW | ATV650U07N4 | ATV650U07N4E |
| 1.5 kW | ATV650U15N4 | ATV650U15N4E |
| 2.2 kW | ATV650U22N4 | ATV650U22N4E |
| 3 kW | ATV650U30N4 | ATV650U30N4E |
| 4 kW | ATV650U40N4 | ATV650U40N4E |
| 5.5 kW | ATV650U55N4 | ATV650U55N4E |
| 7.5 kW | ATV650U75N4 | ATV650U75N4E |
| 11 kW | ATV650D11N4 | ATV650D11N4E |
| 15 kW | ATV650D15N4 | ATV650D15N4E |
| 18.5 kW | ATV650D18N4 | ATV650D18N4E |
| 22 kW | ATV650D22N4 | ATV650D22N4E |
Frame B (30~45 kW, includes your D30N4)
| Puissance nominale | Model without switch | Model with switch |
| 30 kW | ATV650D30N4 | ATV650D30N4E |
| 37 kW | ATV650D37N4 | ATV650D37N4E |
| 45 kW | ATV650D45N4 | ATV650D45N4E |
Cadre C (55~90 kW)
| Puissance nominale | Model without switch | Model with switch |
| 55 kW | ATV650D55N4 | ATV650D55N4E |
| 75 kW | ATV650D75N4 | ATV650D75N4E |
| 90 kW | ATV650D90N4 | ATV650D90N4E |
High Power Floor-standing Units (C range, IP54, installation verticale)
Model format: ATV650CxxN4F (all fitted with disconnect switch)
110/132/160/200/250/315 kW:
ATV650C11N4F, C13N4F, C16N4F, C20N4F, C25N4F, C31N4F
Confusable Series Comparison
1. VTT650: IP55 wall-mounted, for local field installation (the series you are using)
2. VTT630: Same power rating, IP20 cabinet bare drive, no outer enclosure
3. ATV660: Newer generation, upgrade replacement for ATV650
4. VTT950: Heavy-duty drive, for shock loads other than fans and pumps
Additional Key Information
Suffix U = low power; D = medium power; C = high power floor-standing
Suffix E = integrated load disconnect switch; no E = no switch
Standard features for all units: Dual-port Modbus TCP + RS485, built-in Class C2/C3 EMC filter, Chinese graphic keypad, Arrêt sécurisé du couple STO