Schneider GVAE11 Auxiliary Contact Block

GVAE11 is a 1NO + 1NC instantaneous auxiliary contact block of Schneider TeSys GV series. It is front-mounted and compatible with GV2/GV3 series motor circuit breakers. With a rated current of 2.5A and IP20 protection degree, it is used for status monitoring and signal feedback of motor control circuits, serving as a standard accessory for ...

  • Détails du produit

GVAE11 is a 1NO + 1NC instantaneous auxiliary contact block of Schneider TeSys GV series. It is front-mounted and compatible with GV2/GV3 series motor circuit breakers. With a rated current of 2.5A and IP20 protection degree, it is used for status monitoring and signal feedback of motor control circuits, serving as a standard accessory for motor control in industrial automation systems.

Segment de codeSignificationDescription
GVAProduct CategoryAuxiliary contact block for GV series
EPosition de montageFront mounting, different from side-mounted models
11Configuration des contacts1 Normalement ouvert (NON) + 1 Normalement fermé (Caroline du Nord) instantaneous contacts with mechanical linkage

Définition complète du modèle: GVAE11 = Schneider GV series, monté à l'avant, 1NO+1NC instantaneous auxiliary contact block

  1. Spécifications techniques de base
CatégorieCaractéristiquesRemarques
General Characteristics
Type de produitInstantaneous auxiliary contact blockMechanically linked, operates synchronously with main contacts of circuit breaker
Configuration des contacts1NON + 1Caroline du Nord (Instantané)NO/NC status switches in sync with the main circuit of the circuit breaker
Compatible DevicesSchneider TeSys GV2/GV3 series motor circuit breakersCompatible with GV2L, GV2LE, GV2ME, GV2P, GV2RT, GV3L, GV3P and other models
Méthode de montageFront snap-on installationTool-free assembly & quick removal with precise positioning
Paramètres électriques
Tension de fonctionnement nominale24–240V AC, 24–60 V CCSuitable for standard voltages of control circuits
Courant opérationnel nominal2.5UN (je)Continuous current carrying capacity
Tension d'isolation nominale690V etComplies with insulation requirements for industrial control circuits
Endurance mécanique100,000 cycles de fonctionnementHigh reliability for frequent operations
Endurance électrique100,000 cycles de fonctionnement (AC-15 2.5A/240V)Meets long-term service requirements of control circuits
Type de borneBornes à visCopper wire cross-section: 0.5–1.5mm²; Couple de serrage: 0.8–1.2Nm
Physique & Paramètres environnementaux
Degré de protectionIP20Empêche l'accès des doigts aux pièces sous tension
Dimensions (L × H × P)45 × 20 × 15mmStructure compacte, no extra installation space required for circuit breakers
Température de fonctionnement-25℃ ~ +60℃Wide temperature range for industrial environments
CouleurGrisMatches the appearance of GV series circuit breakers
CertificationsCCC, UL, ASC, CAEMulti-standard certifications for global application
Informations de commande
Manufacturer Part No.GVAE11Official Schneider model
Standard Order CodeGVAE11Original imported version
Code EAN3.38911E+12International universal commodity code
  1. Liste complète des modèles (GVAE Series Auxiliary Contacts)
ModèleConfiguration des contactsPosition de montageCompatible DevicesApplication principale
GVAE11NO or 1NC (Facultatif)DevantGV2/GV3 SeriesSimple status indication, single signal output
GVAE111NON + 1Caroline du NordDevantGV2/GV3 SeriesStandard status monitoring, output open/close signals simultaneously
GVAE202NONDevantGV2/GV3 SeriesControl circuits requiring multiple NO signals
GVAE022Caroline du NordDevantGV2/GV3 SeriesControl circuits requiring multiple NC signals
GVAE141NON + 1Caroline du NordCôtéGV2/GV3 SeriesSide mounting for space-limited installations
GVAE242NONCôtéGV2/GV3 SeriesSide mounting for multiple NO signal demands
GVAE042Caroline du NordCôtéGV2/GV3 SeriesSide mounting for multiple NC signal demands
  1. Modèles de remplacement & Comparaison des concurrents

4.1 Internal Schneider Replacements

Modèle originalModèle de remplacementDifférencesScénarios d'application
GVAE11GVAE14Different mounting position (side mounting)Insufficient front space, side mounting required
GVAE11GV2ME + Contacts intégrésConception intégrée, no extra assembly neededNew equipment selection for integrated layout
GVAE11GV3P + Contacts intégrésUpgraded series with enhanced functionsHigh-standard applications requiring advanced protection

4.2 Comparaison des concurrents entre marques

MarqueModèleConfiguration des contactsCompatible DevicesPrincipales différences
SchneiderGVAE111NON + 1Caroline du NordGV2/GV3 SeriesPrecise mechanical linkage, Protection IP20, haute compatibilité
ABBMS132-011NON + 1Caroline du NordMS132 SeriesSide mounting, courant nominal 3A, similar price
Siemens3RV2091-1A1NON + 1Caroline du Nord3RV20 SeriesPlug-in mounting, rated current 2A, complete certifications
EatonPKZM0-AUX111NON + 1Caroline du NordPKZM0 SeriesFront mounting, rated current 2.5A, bornes à ressort
ChintNXC-A111NON + 1Caroline du NordSérie NXCRentable, reliable domestic alternative
  1. Environnements d'applications & Cas typiques

5.1 Applications recommandées

Motor Control Circuit: Feedback circuit breaker ON/OFF status for PLC/DCS system monitoring

Alarm System: Trigger audible and visual alarms via NC contacts when the circuit breaker trips

Interlock Control: Prevent simultaneous startup of multiple motors and realize sequence control

Surveillance à distance: Transmit status signals to SCADA system for remote diagnosis

Safety Circuit: Form safety protection circuits together with emergency stop buttons

5.2 Applications non recommandées

Main Circuit Usage: Rated current is only 2.5A, not applicable for motor main circuits

High-frequency Switching: Sur 1000 switching cycles per hour will shorten service life

Severe Electromagnetic Interference Environment: Additional shielding is required to avoid malfunction

Humid/Corrosive Environment: IP20 protection is insufficient; install extra enclosure or select higher protection grade products

5.3 Cas d'application typiques

Cas 1: Pump Unit Control in Wastewater Treatment Plant

Équipement: 15kW submersible pump, GV2P32 circuit breaker + GVAE11 auxiliary contact

Configuration: NO contact of GVAE11 connected to PLC digital input module; NC contact connected to alarm circuit

Résultat: Real-time monitoring of pump operating status, automatic alarm and event recording upon faults

Cas 2: Conveyor System in Automotive Production Line

Équipement: 12 conveyor lines, each equipped with GV2P32 + GVAE11

Configuration: GVAE11 contacts linked with PLC to realize sequential startup and interlock protection for conveyors

Caractéristiques: Mechanical linkage ensures accurate status feedback and reduces misjudgment of control systems

  1. Dépannage & Maintenance Manual

6.1 Défauts courants & Solutions

Phénomène de défautCauses possiblesSolutions
No change of contact signals1. Improper installation of contact block1. Reinstall the block and ensure the clip is fully engaged
2. Damaged mechanical linkage2. Inspect linkage mechanism and replace damaged unit
3. Burned or oxidized contacts3. Clean or replace the contact block
4. Mauvais câblage4. Check wiring and confirm correct connection of NO/NC contacts
Soudage par contact1. Excessive current in control circuit1. Ensure control circuit current ≤ 2.5A
2. Overheating caused by frequent switching2. Reduce switching frequency or select higher-rated contacts
3. Arc erosion3. Replace with a new contact block
Signal interference1. Control wires not separated from main wires1. Separate control wires from main wires (spacing ≥ 100mm)
2. No shielded cable used2. Use shielded cable with single-end grounding
3. Mauvaise mise à la terre3. Inspect and ensure reliable grounding
Installation lâche1. Clip not fully locked1. Reinstall until a click sound is heard
2. Loosening caused by vibration2. Fit shock-absorbing pads or reinforce installation

6.2 Maintenance Procedures

  1. Inspection quotidienne (Hebdomadaire)

Check installation condition and ensure no looseness

Inspect terminals for overheating and looseness

Test contact switching to confirm synchronization with circuit breaker

  1. Entretien courant (Chaque 6 Mois)

Power off and remove dust on the contact block

Mesurer la résistance de contact (shall be ≤ 50mΩ)

Check flexibility of mechanical linkage

  1. Entretien annuel

Replace frequently used contact blocks

Test insulation performance of control circuits

Retighten all electrical connections

6.3 Quick Diagnosis Tips

No signal? Check installation and linkage first.

Contact welded? Limit current and cut switching times.

Signal interference? Separate wires, apply shielding and good grounding.

Loose fitting? Re-clip firmly and add shockproof measures for vibrating sites.

  1. Sélection & Directives d'installation

7.1 Règles de sélection

Compatibilité: Confirm matching with GV2/GV3 series circuit breakers; not applicable for other series

Configuration des contacts: Select 1NO+1NC (GVAE11), 2NON (GVAE20) or 2NC (GVAE02) according to control demands

Position de montage: Choose GVAE11 for front mounting, GVAE14 for side mounting

Correspondance actuelle: Control circuit current shall not exceed 2.5A; select higher-specification products if overloaded

7.2 Notes d'installation

Installation Sequence: Install circuit breaker first, then attach the contact block and fully lock the clip

Wiring Standard: Use 0.5–1.5mm² copper wires with tightening torque of 0.8–1.2Nm; avoid over-tightening

Clear Marking: Label NO/NC contacts to prevent wiring errors

Linkage Test: Manually operate the circuit breaker after installation to verify synchronous contact action

Protection Measures: Install extra enclosures for dusty or humid environments

  1. Production Status & Solutions de remplacement

Current Status of GVAE11: In production, no discontinuation plan (as of June 2026)

Mise à niveau & Replacement Options:

  1. Functional Upgrade: GV3 series models with built-in contacts (no extra assembly, fewer fault points)
  2. Intelligent Upgrade: TeSys T series (with communication function for network-based status transmission)
  3. Alternative nationale: Compatible domestic GVAE11 models (lower cost with equivalent performance)