Nom du produit: TeSys D / Deca Mechanical Latch Block
Fonction: After the contactor closes, it stays closed by mechanical locking; the coil does not need continuous power supply (économie d'énergie). Trip is triggered by pulse signal to terminals E1/E2; manual reset is also available.
- Définition du modèle
LAD6K10: Mechanical latch main body
F = Control voltage: 110~127 V AC/DC (50/60 Hz)
- Contacteurs compatibles
LC1D09~D80A, LC1DT20~DT80A, CAD control relays
⚠️ Not compatible with low-consumption coil contactors
- Paramètres électriques clés
Control voltage Uc: 110–127 V AC / CC
Pulse duration requirement: AC ≥ 100 MS; DC ≥ 250 MS; Max pulse duration ≤ 10 s
AC power consumption: 25 Virginie; DC power consumption: 30 W
Fréquence de fonctionnement maximale: 1200 cycles/heure
Durée de vie mécanique: 500,000 cycles
Tension assignée d'isolement Ui: 690 V
Classe de protection: IP2X
Température de fonctionnement: -25℃ ~ +55℃
Montage: Front snap-on installation; screw terminals E1, E2
Trip modes: Electric pulse trip + réarmement manuel par bouton-poussoir
- Principe de fonctionnement
- Pulse power to contactor A1/A2 → Main contacts close; LAD6K10F mechanically latches and holds the closed state. The contactor remains closed even after the coil power is cut off.
- To open the contactor: Send a 110~127 V pulse to terminals E1-E2 of the latch block → Mechanical unlock, contactor drops out. Manual reset via the front button is also supported.
- Full Voltage Variant List (LAD6K10)
LAD6K10B: 24 V CA/CC
LAD6K10F: 110–127 V AC/DC (ce modèle)
LAD6K10M: 220–240 V AC/DC
LAD6K10Q: 380–415 V AC/DC
LAD6K10L: 200–208 V AC/DC (abandonné)
LAD6K10U: 256–277 V AC/DC (abandonné)
- Applications typiques
Long-term closed loads, systèmes de stockage d'énergie, pompes à eau, gate valves, and circuits requiring coil power cut-off after closing to reduce heating and power consumption.
Câblage & PLC Timing Scheme for LAD6K10F (LC1D, 110~127V AC/DC trip)
Two independent pulse signals; never energize both at the same time. A1/A2 = closing pulse; E1/E2 = trip pulse; pulse duration shall not exceed 10 s.
Définition du terminal
Contacteur: A1, A2 → Closing coil (pulse only; keeps closed after mechanical latch without continuous power)
LAD6K10F: E1, E2 → Trip coil (110–127 V AC/DC for this model)
DIP switch on module: 0 = manual unlock; non-zero = enable mechanical latch (keep on non-zero for normal operation)
Câblage du circuit de commande (PLC version)
Alimentation de contrôle: 110~127 V (match LAD6K10F voltage)
- PLC output Q0: Drive closing pulse → Contactor A1/A2 (use intermediate relay to protect PLC output)
- PLC output Q1: Drive trip pulse → Terminals E1/E2 of LAD6K10F
- Contactor NO auxiliary contact → PLC input I0 (retour d'état)
- Verrouillage: Software interlock between Q0 and Q1; simultaneous output is strictly forbidden.
Simplified wiring description:
L (110V) → KA0 coil → Q0 → N; KA0 main contacts connect to A1/A2
L (110V) → KA1 coil → Q1 → N; KA1 main contacts connect to E1/E2
Contactor NO contact: One side to L, the other to PLC input I0
Recommend intermediate relays; do not drive the coil directly with PLC points, as the DC coil has high inrush current (30 Puissance W).
Timing Requirements (Obligatoire)
AC pulse ≥ 100 MS
DC pulse ≥ 250 MS
Upper pulse limit: ≤ 10 s (coil burnout if exceeded)
Séquence de synchronisation
- Standby: Contactor open, I0=OFF
- Closing command (I1 start): Q0 outputs 200 ms pulse → A1/A2 energized → Contactor closes and latches mechanically. Q0 cuts off after pulse ends; contactor stays closed, I0=ON.
- Holding stage: No output on Q0/Q1, zero power consumption.
- Trip command (I2 stop): Q1 outputs 300 ms pulse → E1/E2 energized for unlock → Contactor opens, I0=OFF; Q1 cuts off after pulse ends.
Logique API (Universal for Siemens / Mitsubishi)
Logic rules:
✅ Closing: Rising edge triggers TON timer for fixed pulse output
✅ Tripping: Rising edge triggers another TON timer for fixed pulse output
✅ Interlock: Block trip pulse while closing pulse is active, et vice versa
✅ Fault detection: If I0 remains OFF 500 ms after closing pulse, trigger alarm.
Sample logic (S7-1200 style):
I1: Start button
I2: Stop button
I0: Contactor auxiliary contact feedback
Q0: Closing pulse
T1: Trip pulse
T37: Closing pulse timer, PT=200 ms
T38: Trip pulse timer, PT=300 ms
- Rising edge of I1 → Start T37; T37.Q = Q0; T37 auto-resets upon timeout.
- Rising edge of I2 → Start T38; T38.Q = Q1; T38 auto-resets upon timeout.
- Normally closed T37.Q in T38 startup circuit; normally closed T38.Q in T37 startup circuit (software interlock).
- Alarme de défaut: If I0=0 after 500 ms of closing pulse, activate alarm.
Dépannage & Erreurs courantes
- DIP switch set to 0: Latch function disabled; contactor opens immediately once A1/A2 power is lost.
- Simultaneous closing & tripping output: Mechanical jamming or coil burnout.
- Pulse too short: CA < 100 ms → latch/trip failure; CC < 250 ms → high failure rate.
- Continuous pulse (no timer): Coil burns out after exceeding 10 s.
- Low-consumption coil contactor: Incompatible with LAD6K10; latching will not work.
Fonctionnement manuel
Switch the DIP switch to 0 to release mechanically without power; used for commissioning and maintenance.
Emergency Stop Extension
Wire E-Stop NC contact in series with the E1/E2 trip circuit. Pressing E-Stop directly sends a trip pulse to open the load immediately.
- Full Model List of Schneider TeSys D Mechanical Latch Blocks (Pulse Latch: LAD6K / LA6DK)
Two series:
LAD6K10 (petit cadre: LC1D09~D80A)
LA6DK20 (large frame: LC1D80~D150)
Suffix letter = trip coil voltage; AC/DC universal pulse trip; terminals E1/E2; front snap-on mounting with manual reset DIP switch.
LAD6K10 (For LC1D09~D80A, LC1DT20~DT80A, CAD relays; Low-consumption coils NOT supported)
| Modèle | Trip Voltage Uc | Remarques |
| LAD6K10B | 24 V CA/CC | Usage général |
| LAD6K10F | 110~127 V AC/DC | Your selected model |
| LAD6K10M | 220~240 V AC/DC | Most common in China |
| LAD6K10Q | 380~415 V AC/DC | 3-phase control circuit |
| LAD6K10L | 200~208 V AC/DC | North American voltage, abandonné |
| LAD6K10U | 256~277 V AC/DC | North American voltage, abandonné |
LA6DK20 (For LC1D80~D150, LC1DT115~DT200 high-current contactors)
| Modèle | Trip Voltage Uc |
| LA6DK20B | 24 V CA/CC |
| LA6DK20F | 110~127 V AC/DC |
| LA6DK20M | 220~240 V AC/DC |
| LA6DK20Q | 380~415 V AC/DC |
Unified Technical Specs
Pulse requirement: AC ≥ 100 MS, DC ≥ 250 MS; Max pulse duration ≤ 10 s
Durée de vie mécanique: 500,000 cycles
Fréquence de fonctionnement maximale: 1200 cycles/heure
Protection: IP2X
⚠️ Distinction importante: LAD9R1 / LAD9R3 are mechanical interlock blocks for two contactors (forward/reverse interlock), NOT pulse hold latches; completely different function, do not select incorrectly.
- Comparaison équivalente entre marques
Key note: LAD6K is an external snap-on electromagnetic mechanical pulse latch exclusive to Schneider TeSys D.
Siemens, ABB, Mitsubishi do NOT manufacture identical front-mounted external latch modules with the same wiring logic.
Two replacement solutions:
- Function-equivalent solution: Bi-stable contactors with built-in mechanical latch or independent pulse latch units (same control logic: pulse close, pulse trip).
- Drop-in aftermarket replacement: Domestic compatible LAD6K modules (direct snap-on fit for LC1D; same terminals E1/E2, same wiring & timing).
❌ Warning: ABB VM, Siemens 3RA19xx, Mitsubishi UN-MLxx are ONLY mechanical interlock pieces for two contactors (forward/reverse interlock), with NO power-hold function; they cannot replace LAD6K.
Equivalent Replacement Table (Pulse Close + Mechanical Hold + Pulse Trip)
| Original Schneider Model | Contacteur compatible | Marque | Modèle de remplacement | Description |
| LAD6K10B/F/M/Q | LC1D09~D80A | Domestic aftermarket | LAD6K10B/F/M/Q (clone version) | Direct snap-on installation; E1/E2 terminals unchanged; câblage & PLC timing unchanged; rentable; verify pulse power consumption |
| LAD6K10* | Série LC1D | Siemens | 3RT bi-stable contactor (3RT10xx-1BP40 etc.) | Integrated built-in latch; no external module required; same pulse control logic; prix plus élevé |
| LAD6K10* | Série LC1D | ABB | AF series bi-stable contactor AFxx-30-00-11RT | RT = latching version; mechanical latch integrated into contactor body, no external accessory |
| LAD6K10* | Série LC1D | Mitsubishi | S-T bi-stable latch type S-TxxRT | RT suffix = built-in mechanical hold |
| LAD6K10* | Série LC1D | Delta | MCxx-RT bi-stable contactor | Integrated mechanical latch |
Non-Equivalent Models (Only Interlock, No Holding Function — Avoid These)
| Marque | Modèle | Type de produit | Rappel des risques |
| ABB | VM19 / VM300/460H | Dual-contactor mechanical interlock piece | Only prevents simultaneous closing of two contactors; no power-off holding function |
| Siemens | 3RA1924-2B, 3RA1954-2A | Mechanical interlock assembly | Forward/reverse interlock only; cannot keep a single contactor closed without coil power |
| Mitsubishi | UN-ML21 / UN-ML80 | Mechanical interlock accessory | Only interlock, no latching hold |
| Chint / Délicieux | CJX2 mechanical interlock piece | Interlock accessory | Same limitation above |
Replacement Selection Advice
- If LC1D contactors remain in use: Choose domestic compatible LAD6K10; no changes to drawings or PLC program.
- If contactor replacement is allowed: Select RT-series bi-stable contactors with integrated latch; fewer spare parts and lower failure rate.
- Never use simple interlock pieces to replace LAD6K; control logic differs completely, and the contactor will drop out once coil power is removed.
- Full Compatibility List (Latch Block vs Contactors)
Règle: Low-consumption coil contactors are NOT compatible with all LAD6K / LA6DK latches.
Same model body fits the same contactor range regardless of voltage suffix (B/F/M/Q).
1) LAD6K10 (LAD6K10F belongs to this group)
Compatible devices:
3-contacteurs de pôles: LC1D09, LC1D12, LC1D18, LC1D25, LC1D32, LC1D38, LC1D40A, LC1D50A, LC1D65A, LC1D80A
4-contacteurs de pôles (with neutral): LC1DT20, LC1DT25, LC1DT32, LC1DT40, LC1DT60A, LC1DT80A
Relais de contrôle: CAD32, CAD50 (standard coil only; low-consumption excluded)
2) LA6DK10 (Mid-size latch block)
Compatible devices:
3-pôle: LC1D40, LC1D50, LC1D65
4-pôle: LC1D65004, LC1D65008, LP1D65004, LP1D65008
3) LA6DK20 (Large-current latch block)
Compatible devices:
3-pôle: LC1D80, LC1D95, LC1D115, LC1D150 (CA & DC coil versions are both acceptable)
4-pôle: LP1D80004, LP1D80008, LC1D115004, LC1DT200A
Tableau récapitulatif
| Latch Block Model | Compatible Contactor Range |
| LAD6K10B/F/M/Q | LC1D09~D80A, LC1DT20~DT80A, CAD32/CAD50 (standard coil) |
| LA6DK10B/F/M/Q | LC1D40/D50/D65, LP1D65 4-pole |
| LA6DK20B/F/M/Q | LC1D80~D150, LP1D80, LC1DT200A |
❌ Incompatible Product List (Pièges de sélection)
- LC1D & CAD relays with low-consumption coils (latching mechanism cannot hold reliably)
- TeSys K, TeSys E, iCT, iC65N contactors / relais
- LC1F, LC1G, LC2D reversing contactors (different housing structure)
- No-name clone LC1D contactors with modified mold
Notes complémentaires
Montage: All snap onto the front face without screws; only wire E1/E2 trip terminals.
Timing rule (universel): AC pulse ≥ 100 MS; DC pulse ≥ 250 MS; max pulse duration strictly ≤ 10 s.
Voltage suffix code (universel):
B=24V, F=110~127V, M=220~240V, Q=380~415V.
Contacteur,disjoncteur,capteur,Encodeur,API,Convertisseur