3-contacteur AC pôle, rated current 115A (AC-3), 220VAC coil, 1NO+1NC auxiliary contacts, bornes à vis
Numéro de commande: LC1D11500M7C (full model), LC1D115M7C (abbreviated model)
Domestic TeSys D series, phased out (launched in July 2025). Recommended replacements: LC1D115KUEC or LC1E120M5N
Complete certifications: UL, ASC, CEI, CCC, CAE, etc.. Compliant with RoHS/REACh standards
- Explication du code modèle
| Segment | Code | Description |
| Product Category | LC1 | Contactor series |
| Construction Type | D | Série TeSys D (Domestic high-current type) |
| Courant nominal | 115 | Rated operational current 115A (AC-3, ≤440V) |
| Contacts auxiliaires | 0 | Configuration standard: 1NON + 1Contacts auxiliaires NF |
| Coil Rating | M. | 220VAC coil voltage |
| Code de fréquence | 7 | Universal coil for 50/60Hz |
| Manufacturing Code | C | Manufactured by SSIC (gamme: 9~620A) |
Modèle complet: LC1D11500M7C (official standard model), Abbreviated Model: LC1D115M7C
- Main Specifications
| Catégorie | Détails |
| Paramètres de base | 3-pôle (3P.), 3AUCUN contact principal, 1NO+1NC auxiliary contacts, screw terminal connection |
| Courant nominal | AC-1: 200UN (≤440V, ≤60°C); AC-3: 115UN (≤440V, ≤60°C) |
| Tension nominale | Circuit principal: ≤1000VAC; Circuit de commande: 220ACC, 50/60HZ |
| Motor Control Rating | 30kW (220~230V), 55kW (380~400V), 75kW (500V) |
| Durée de vie mécanique | 10 millions d'opérations (AC-3), 10 millions d'opérations (AC-1) |
| Durée de vie électrique | 1 million operations at rated current (AC-3), 1 million operations at rated current (AC-1) |
| Caractéristiques de la bobine | Pick-up power: 1200Virginie; Holding power: 120Virginie; Impedance: 0.6MΩ |
| Montage | 35mm DIN rail mounting or direct panel mounting |
| Dimensions & Poids | Hauteur: 158mm; Largeur: 120mm; Profondeur: 136mm; Poids: environ. 2.5kilos |
| Classe de protection | IP20 (per IEC 60529) |
| Certifications | UL, ASC, CEI, CCC, CAE, Marin, RINA, DNV, etc.. |
- Liste complète des modèles (LC1D Series 115A)
| Modèle | Tension de bobine | Type de borne | Remarques |
| LC1D11500M7C | 220ACC | Vis | Modèle standard (original model) |
| LC1D11500P7C | 380ACC | Vis | Common alternative voltage |
| LC1D11500F7C | 110ACC | Vis | Contrôle basse tension |
| LC1D11500B7C | 24ACC | Vis | Safety extra-low voltage control |
| LC1D115006M7C | 220ACC | Ring terminal | For special wiring requirements |
| LC1D115KUEC | 100~250VAC/DC | Vis | Universal voltage, modèle de remplacement |
| LC1D115ABD | 24VCC | Vis | DC coil version |
| LC1D115ALBD | 24VCC | Vis | Low-power DC coil |
- Cross & Replacement Model List
4.1 Remplacements d'origine Schneider
| Modèle original | Modèle de remplacement | Raison du remplacement | Compatibilité |
| LC1D115M7C | LC1D115KUEC | Universal voltage coil (100~250VAC/DC), higher flexibility | Entièrement compatible, identical mounting dimensions |
| LC1D115M7C | LC1E120M5N | Upgraded TeSys E Series with improved performance | Dimensions de montage identiques; verify auxiliary contact configuration |
| LC1D115M7C | LC1D11500M7C | Full official model, identical to abbreviated version | 100% compatible |
4.2 Remplacements multimarques
| Marque | Modèle de remplacement | Principales différences | Applicability |
| ABB | A145-30-11 | Rated current 145A with larger margin | Different mounting dimensions; layout adjustment required |
| Siemens | 3RT2036-1BB40 | 125UN, AC-3, 220Bobine V | Same auxiliary contact layout, remplacement direct |
| Commutateur Changshu | CJX2-1210 | Alternative nationale, rentable | Slightly lower performance, for general working conditions |
| Chint | NC1-1210 | Alternative nationale, performance à coût élevé | Meets basic requirements, durée de vie plus courte |
- Application & Cas industriels
5.1 Scénarios applicables
Contrôle du moteur: Commencer, stop and reverse control for 30~75kW three-phase squirrel-cage motors
Automatisation industrielle: Control circuits for production lines, convoyeurs, compressors and pumps
Distribution d'énergie: Switching control for non-inductive or weakly inductive loads such as resistance furnaces and heaters (AC-1)
Systèmes CVC: Control of large air conditioning compressors and ventilation fans
Marin & Offshore Engineering: Certified by marine classification societies for offshore equipment
5.2 Non-Recommended Scenarios
Fonctionnement haute fréquence: Plus que 120 starts/stops per minute (use LC1D170 series or dedicated contactors)
Environnements difficiles: Heavy dust, corrosive gas or severe vibration (additional protection required)
DC Loads: Use dedicated DC contactors (par exemple. LC1D115ABD)
High Altitude: Derating required above 2000m (10% derating per additional 1000m)
5.3 Cas d'application typiques
Cas 1: Fan Control in Steel Plant
Operating conditions: 380V, 55kW fan, AC-3, 10 starts per day, 20-hour continuous operation
Solution: LC1D115M7C + LRD3365 thermal overload relay
Avantages: 3 years of stable operation without failure, low maintenance cost
Cas 2: HVAC System in Pharmaceutical Factory
Operating conditions: 400V, 45kW compressor, AC-3, 24-hour continuous operation and frequent cycling
Solution: LC1D115M7C + Contrôle par API + surge suppressor
Avantages: Low noise and power consumption, conforme aux normes GMP
- Dépannage & Maintenance Manual
6.1 Diagnostic de panne courant
| Phénomène de défaut | Causes possibles | Solutions |
| Contactor fails to close | 1. No voltage on coil; 2. Bobine brûlée; 3. Mechanical jam | 1. Measure voltage across terminal A1/A2; 2. Check coil resistance (normale: environ. 320Oh); 3. Power off, inspect mechanism and remove foreign objects |
| Loud noise after closing | 1. Sous-tension; 2. Oil contamination on core contact surface; 3. Anneau d'ombrage cassé | 1. Ensure voltage within ±10% of rated value; 2. Clean core surface; 3. Replace coil assembly |
| Overheated / burnt main contacts | 1. Overload current; 2. Mauvais contact; 3. Failed arc suppression | 1. Check for load overload; 2. Nettoyer ou remplacer les contacts; 3. Inspect arc chute integrity |
| Auxiliary contact malfunction | 1. Contacter l'oxydation; 2. Câblage lâche; 3. Mechanical wear | 1. Nettoyer les contacts; 2. Retighten terminals; 3. Replace auxiliary contact block |
| Repeated coil burnout | 1. Severe voltage fluctuation; 2. Frequent cycling; 3. Excess ambient temperature | 1. Install voltage stabilizer; 2. Replace with high-cycle model; 3. Améliorer la dissipation thermique |
6.2 Calendrier d'entretien & Procedures
| Article d'entretien | Intervalle | Opération |
| Inspection visuelle | Mensuel | Check for overheating marks, abnormal odors and loose parts |
| Contactez-nous | Trimestriel | Mesurer la résistance de contact (<50m惟), check for ablation |
| Coil Inspection | Semestriellement | Measure coil resistance and insulation performance |
| Mechanical Lubrication | Annuellement | Lightly lubricate moving parts (silicone grease recommended) |
| Révision | Chaque 2 années | Disassemble for full inspection, replace worn parts and clean interior |
- Phase-Out & Migration Guide
7.1 Phase-Out Information
Phase-out Plan: Schneider launched the phase-out of domestic high-current TeSys D series (115-170UN) in July 2025
Transition Period: July 2025 – December 2026. Production will cease after the period
Inventaire: Stock is still available via some distributors. Procurement or model replacement is recommended as soon as possible.
7.2 Migration Solutions
| Migration Type | Modèle recommandé | Avantages | Remarques |
| In-Series Upgrade | LC1D115KUEC | Universal voltage coil for wider application | Identical mounting size, no cabinet modification needed |
| Cross-Series Upgrade | LC1E120M5N | TeSys E Series with enhanced performance and longer service life | Auxiliary contact layout may differ; verify control circuit |
| Cost-Saving Replacement | Changshu CJX2-1210 / Chint NC1-1210 | 30-50% réduction des coûts | Slight performance difference; for non-critical applications |
7.3 Migration Steps
- Confirm voltage and current requirements of the original control circuit
- Select suitable replacement model (LC1D115KUEC recommended)
- Verify compatibility of mounting dimensions and fixtures
- Confirm quantity and type of auxiliary contacts
- Replace contactor and conduct commissioning test
- Keep spare parts of the original model until the end of transition period
- Lignes directrices de sélection
Règles de référence rapide
- LC1D: Schneider TeSys D series contactor
- 115: 115Un courant nominal (AC-3), matches 55kW motor at 400V
- M7C: 220VAC 50/60Hz coil, manufactured by SSIC
- 00: Standard 1NO+1NC auxiliary contacts
- Phase-out Notice: Prioritize LC1D115KUEC for replacement since July 2025
- Conformité du fret aérien & Certifications
Transport Classification: Marchandises non dangereuses. No built-in lithium battery / supercapacitor, compliant with IATA regulations
Certification CE: Conforme à la norme EN 60947-4-1, CE marked
Certification environnementale: Compliant with RoHS/REACh directives, Produit Vert Premium
Conditionnement: Individual packaging to prevent damage during transit. Original packaging is recommended.
Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires

























NH42-63-318x560.png)