Schneider LC1D115M7C Contactor - Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires

Wechat: +86-13184948252 WhatsApp: 0086-13811255435 E-mail: kent@bestcontactor.com

À propos Contact |

Schneider LC1D115M7C Contactor - Contacteur,disjoncteur,onduleur solaire,compteur électrique,batteries solaires

contacteur/

Schneider LC1D115M7C Contactor

3-contacteur AC pôle, rated current 115A (AC-3), 220VAC coil, 1NO+1NC auxiliary contacts, screw terminals Order Number: LC1D11500M7C (full model), LC1D115M7C (abbreviated model) Domestic TeSys D series, phased out (launched in July 2025). Recommended replacements: LC1D115KUEC or LC1E120M5N Complete certifications: UL, ASC, CEI, CCC, CAE, etc.. Compliant with RoHS/REACh standards Model Code Explanation Segment Code Description ...

  • Détails du produit

3-contacteur AC pôle, rated current 115A (AC-3), 220VAC coil, 1NO+1NC auxiliary contacts, bornes à vis

Numéro de commande: LC1D11500M7C (full model), LC1D115M7C (abbreviated model)

Domestic TeSys D series, phased out (launched in July 2025). Recommended replacements: LC1D115KUEC or LC1E120M5N

Complete certifications: UL, ASC, CEI, CCC, CAE, etc.. Compliant with RoHS/REACh standards

  1. Explication du code modèle
SegmentCodeDescription
Product CategoryLC1Contactor series
Construction TypeDSérie TeSys D (Domestic high-current type)
Courant nominal115Rated operational current 115A (AC-3, ≤440V)
Contacts auxiliaires0Configuration standard: 1NON + 1Contacts auxiliaires NF
Coil RatingM.220VAC coil voltage
Code de fréquence7Universal coil for 50/60Hz
Manufacturing CodeCManufactured by SSIC (gamme: 9~620A)

Modèle complet: LC1D11500M7C (official standard model), Abbreviated Model: LC1D115M7C

  1. Main Specifications
CatégorieDétails
Paramètres de base3-pôle (3P.), 3AUCUN contact principal, 1NO+1NC auxiliary contacts, screw terminal connection
Courant nominalAC-1: 200UN (≤440V, ≤60°C); AC-3: 115UN (≤440V, ≤60°C)
Tension nominaleCircuit principal: ≤1000VAC; Circuit de commande: 220ACC, 50/60HZ
Motor Control Rating30kW (220~230V), 55kW (380~400V), 75kW (500V)
Durée de vie mécanique10 millions d'opérations (AC-3), 10 millions d'opérations (AC-1)
Durée de vie électrique1 million operations at rated current (AC-3), 1 million operations at rated current (AC-1)
Caractéristiques de la bobinePick-up power: 1200Virginie; Holding power: 120Virginie; Impedance: 0.6MΩ
Montage35mm DIN rail mounting or direct panel mounting
Dimensions & PoidsHauteur: 158mm; Largeur: 120mm; Profondeur: 136mm; Poids: environ. 2.5kilos
Classe de protectionIP20 (per IEC 60529)
CertificationsUL, ASC, CEI, CCC, CAE, Marin, RINA, DNV, etc..
  1. Liste complète des modèles (LC1D Series 115A)
ModèleTension de bobineType de borneRemarques
LC1D11500M7C220ACCVisModèle standard (original model)
LC1D11500P7C380ACCVisCommon alternative voltage
LC1D11500F7C110ACCVisContrôle basse tension
LC1D11500B7C24ACCVisSafety extra-low voltage control
LC1D115006M7C220ACCRing terminalFor special wiring requirements
LC1D115KUEC100~250VAC/DCVisUniversal voltage, modèle de remplacement
LC1D115ABD24VCCVisDC coil version
LC1D115ALBD24VCCVisLow-power DC coil

 

  1. Cross & Replacement Model List

4.1 Remplacements d'origine Schneider

Modèle originalModèle de remplacementRaison du remplacementCompatibilité
LC1D115M7CLC1D115KUECUniversal voltage coil (100~250VAC/DC), higher flexibilityEntièrement compatible, identical mounting dimensions
LC1D115M7CLC1E120M5NUpgraded TeSys E Series with improved performanceDimensions de montage identiques; verify auxiliary contact configuration
LC1D115M7CLC1D11500M7CFull official model, identical to abbreviated version100% compatible

4.2 Remplacements multimarques

MarqueModèle de remplacementPrincipales différencesApplicability
ABBA145-30-11Rated current 145A with larger marginDifferent mounting dimensions; layout adjustment required
Siemens3RT2036-1BB40125UN, AC-3, 220Bobine VSame auxiliary contact layout, remplacement direct
Commutateur ChangshuCJX2-1210Alternative nationale, rentableSlightly lower performance, for general working conditions
ChintNC1-1210Alternative nationale, performance à coût élevéMeets basic requirements, durée de vie plus courte
  1. Application & Cas industriels

5.1 Scénarios applicables

Contrôle du moteur: Commencer, stop and reverse control for 30~75kW three-phase squirrel-cage motors

Automatisation industrielle: Control circuits for production lines, convoyeurs, compressors and pumps

Distribution d'énergie: Switching control for non-inductive or weakly inductive loads such as resistance furnaces and heaters (AC-1)

Systèmes CVC: Control of large air conditioning compressors and ventilation fans

Marin & Offshore Engineering: Certified by marine classification societies for offshore equipment

5.2 Non-Recommended Scenarios

Fonctionnement haute fréquence: Plus que 120 starts/stops per minute (use LC1D170 series or dedicated contactors)

Environnements difficiles: Heavy dust, corrosive gas or severe vibration (additional protection required)

DC Loads: Use dedicated DC contactors (par exemple. LC1D115ABD)

High Altitude: Derating required above 2000m (10% derating per additional 1000m)

5.3 Cas d'application typiques

Cas 1: Fan Control in Steel Plant

Operating conditions: 380V, 55kW fan, AC-3, 10 starts per day, 20-hour continuous operation

Solution: LC1D115M7C + LRD3365 thermal overload relay

Avantages: 3 years of stable operation without failure, low maintenance cost

Cas 2: HVAC System in Pharmaceutical Factory

Operating conditions: 400V, 45kW compressor, AC-3, 24-hour continuous operation and frequent cycling

Solution: LC1D115M7C + Contrôle par API + surge suppressor

Avantages: Low noise and power consumption, conforme aux normes GMP

  1. Dépannage & Maintenance Manual

6.1 Diagnostic de panne courant

Phénomène de défautCauses possiblesSolutions
Contactor fails to close1. No voltage on coil; 2. Bobine brûlée; 3. Mechanical jam1. Measure voltage across terminal A1/A2; 2. Check coil resistance (normale: environ. 320Oh); 3. Power off, inspect mechanism and remove foreign objects
Loud noise after closing1. Sous-tension; 2. Oil contamination on core contact surface; 3. Anneau d'ombrage cassé1. Ensure voltage within ±10% of rated value; 2. Clean core surface; 3. Replace coil assembly
Overheated / burnt main contacts1. Overload current; 2. Mauvais contact; 3. Failed arc suppression1. Check for load overload; 2. Nettoyer ou remplacer les contacts; 3. Inspect arc chute integrity
Auxiliary contact malfunction1. Contacter l'oxydation; 2. Câblage lâche; 3. Mechanical wear1. Nettoyer les contacts; 2. Retighten terminals; 3. Replace auxiliary contact block
Repeated coil burnout1. Severe voltage fluctuation; 2. Frequent cycling; 3. Excess ambient temperature1. Install voltage stabilizer; 2. Replace with high-cycle model; 3. Améliorer la dissipation thermique

6.2 Calendrier d'entretien & Procedures

Article d'entretienIntervalleOpération
Inspection visuelleMensuelCheck for overheating marks, abnormal odors and loose parts
Contactez-nousTrimestrielMesurer la résistance de contact (<50m惟), check for ablation
Coil InspectionSemestriellementMeasure coil resistance and insulation performance
Mechanical LubricationAnnuellementLightly lubricate moving parts (silicone grease recommended)
RévisionChaque 2 annéesDisassemble for full inspection, replace worn parts and clean interior
  1. Phase-Out & Migration Guide

7.1 Phase-Out Information

Phase-out Plan: Schneider launched the phase-out of domestic high-current TeSys D series (115-170UN) in July 2025

Transition Period: July 2025 – December 2026. Production will cease after the period

Inventaire: Stock is still available via some distributors. Procurement or model replacement is recommended as soon as possible.

7.2 Migration Solutions

Migration TypeModèle recommandéAvantagesRemarques
In-Series UpgradeLC1D115KUECUniversal voltage coil for wider applicationIdentical mounting size, no cabinet modification needed
Cross-Series UpgradeLC1E120M5NTeSys E Series with enhanced performance and longer service lifeAuxiliary contact layout may differ; verify control circuit
Cost-Saving ReplacementChangshu CJX2-1210 / Chint NC1-121030-50% réduction des coûtsSlight performance difference; for non-critical applications

7.3 Migration Steps

  1. Confirm voltage and current requirements of the original control circuit
  2. Select suitable replacement model (LC1D115KUEC recommended)
  3. Verify compatibility of mounting dimensions and fixtures
  4. Confirm quantity and type of auxiliary contacts
  5. Replace contactor and conduct commissioning test
  6. Keep spare parts of the original model until the end of transition period
  7. Lignes directrices de sélection

Règles de référence rapide

  1. LC1D: Schneider TeSys D series contactor
  2. 115: 115Un courant nominal (AC-3), matches 55kW motor at 400V
  3. M7C: 220VAC 50/60Hz coil, manufactured by SSIC
  4. 00: Standard 1NO+1NC auxiliary contacts
  5. Phase-out Notice: Prioritize LC1D115KUEC for replacement since July 2025
  6. Conformité du fret aérien & Certifications

Transport Classification: Marchandises non dangereuses. No built-in lithium battery / supercapacitor, compliant with IATA regulations

Certification CE: Conforme à la norme EN 60947-4-1, CE marked

Certification environnementale: Compliant with RoHS/REACh directives, Produit Vert Premium

Conditionnement: Individual packaging to prevent damage during transit. Original packaging is recommended.

Précédent:

Suivant:

Laisser une réponse