The Schneider MGK Series 757316 Medium-Voltage Fuse is a current-limiting fuse specially designed for motor protection in compliance with UTE standards. Its core specifications are 7.2 kV / 160 UN / 438 mm, applied for short-circuit protection of indoor medium-voltage motor circuits.
| Article | Valeur | Description |
| Modèle | 757316 | Schneider Merlin Gerin Fusarc MGK Series |
| Tension nominale | 7.2 kV | Medium-voltage class, suitable for 6–7.2 kV systems |
| Courant nominal | 160 UN | Continuous operating current capacity |
| Rated Short-Circuit Breaking Capacity | 50 le | Fault breaking capability for system short circuits |
| DC Resistance | 2.4 kΩ | Measured at 20°C (±10%) |
| Taper | MGK, IND | Indoor type with fiberglass housing |
| Longueur | 438 mm | Overall fuse body length |
| Poids | Environ. 4.1–4.24 kg | Slight deviation among suppliers |
| Normes | CEI 60282-1, UTE | Compliant with international and French standards |
| Catégorie d'application | Protection du moteur | MGK series optimized exclusively for medium-voltage motors |
- Caractéristiques du produit & Applications
- Dedicated Motor Protection: Optimized for short-circuit protection of 7.2 kV medium-voltage motors, effectively preventing motor damage caused by dynamic and thermal effects of short-circuit current.
- Current-Limiting Technology: Cuts off the circuit rapidly before short-circuit current reaches its peak, reducing fault energy release and protecting motor windings and insulation systems.
- Indoor Installation: Adopts fiberglass housing, designed for installation in indoor power distribution cabinets or fuse compartments with reliable protection performance.
- Haute fiabilité: Built on Schneider medium-voltage fuse technology platform, meeting long-term stable operation requirements for industrial environments and compatible with various medium-voltage motor control solutions.
- Opération & Directives d'installation
- Appareils correspondants: Must be used with dedicated MGK series fuse bases/brackets to ensure secure electrical connection.
- Environnement d'installation: Restricted to dry indoor locations; avoid exposure to humidity, poussières et gaz corrosifs.
- Fonctionnement sûr: Power disconnection is mandatory during installation and replacement; insulated tools must be used to prevent electric shock hazards.
- Maintenance Recommendation: Regularly inspect fuse appearance and connection points. Replace immediately if overheating marks or damage are found.
- Related Series Models
Complete 7.2 kV motor protection fuse lineup of MGK series:
757314: 100 UN
757315: 125 UN
757316: 160 UN (Current model)
757317: 200 UN
757318: 250 UN
- Référence de sélection
Key considerations for MGK fuse selection:
- Motor rated voltage and power
- Niveau de courant de court-circuit du système
- Installation space dimensions (438 mm length requirement)
- Protection coordination: time-current characteristic matching with medium-voltage circuit breakers, contactors and other equipment
Complete List of Schneider Medium-Voltage Fuse Models (3.6 kV–36 kV)
Schneider medium-voltage fuses are mainly divided into four core series, covering motor protection, transformer protection, voltage transformer protection and general power distribution protection. They comply with UTE/DIN standards and meet indoor/outdoor installation demands. Below is the full model list and key parameters.
- MGK Series (Protection du moteur, UTE Standard, Intérieur)
Positionnement de base: Customized for short-circuit protection of 7.2 kV medium-voltage motors with optimized current-limiting performance, fiberglass housing and overall length of 438 mm.
| Modèle | Tension nominale | Courant nominal | Longueur | DC Resistance (20C) | Capacité de coupure de court-circuit |
| 757314 | 7.2 kV | 100 UN | 438 mm | 3.8 kΩ | 50 le |
| 757315 | 7.2 kV | 125 UN | 438 mm | 3.0 kΩ | 50 le |
| 757316 | 7.2 kV | 160 UN | 438 mm | 2.4 kΩ | 50 le |
| 757317 | 7.2 kV | 200 UN | 438 mm | 1.9 kΩ | 50 le |
| 757318 | 7.2 kV | 250 UN | 438 mm | 1.5 kΩ | 50 le |
- Soléfuse Series (Transformer Protection, UTE Standard, Intérieur)
Positionnement de base: Applied for 3.6–36 kV power transformer and distribution network protection, with or without strikers, fiberglass housing and approx. 2 kg weight.
2.1 7.2 kV Specification (Model Prefix: 757328)
| Model Suffix | Courant nominal | Striker | Longueur | Remarques |
| BE | 16 UN | With | 438 mm | Modèle standard |
| BH | 31.5 UN | With | 438 mm | – |
| BJ | 40 UN | With | 438 mm | – |
| BK | 50 UN | With | 438 mm | – |
| BN | 63 UN | With | 438 mm | – |
| BP | 80 UN | With | 438 mm | – |
| BR | 100 UN | With | 438 mm | – |
| BT | 125 UN | With | 438 mm | – |
2.2 12/24 kV Specification (Model Prefix: 757328 / 757331)
| Modèle | Tension nominale | Courant nominal | Striker | Longueur |
| 757328EK | 12/24 kV | 63 UN | With | 520 mm |
| 757328EL | 12/24 kV | 80 UN | With | 520 mm |
| 757328EM | 12/24 kV | 100 UN | With | 520 mm |
| 757331GC | 12/24 kV | 6.3 UN | Without | 520 mm |
| 757331GD | 12/24 kV | 10 UN | Without | 520 mm |
| 757331GE | 12/24 kV | 16 UN | Without | 520 mm |
2.3 36 kV Specification (Model Prefix: 757328)
| Model Suffix | Courant nominal | Striker | Longueur |
| FH | 31.5 UN | With | 520 mm |
| FI | 40 UN | With | 520 mm |
| FJ | 50 UN | With | 520 mm |
| FK | 63 UN | With | 520 mm |
- Tépéfuse Series (VT Protection, UTE Standard)
Positionnement de base: Developed for 3.6–36 kV voltage transformer (Vermont) protection; striker-free design, fiberglass housing for indoor use and ceramic housing for outdoor use.
| Modèle | Tension nominale | Courant nominal | Type de montage | Longueur |
| 757334AA | 3.6 kV | 0.5 UN | Intérieur | 292 mm |
| 757334AB | 7.2 kV | 0.5 UN | Intérieur | 292 mm |
| 757334CA | 12 kV | 0.5 UN | Intérieur | 292 mm |
| 757334AD | 24 kV | 0.5 UN | Intérieur | 292 mm |
| 757334AE | 36 kV | 0.5 UN | Intérieur | 292 mm |
| 757335AA | 3.6 kV | 1 UN | Intérieur | 292 mm |
| 757335AB | 7.2 kV | 1 UN | Intérieur | 292 mm |
| 757335CA | 12 kV | 1 UN | Intérieur | 292 mm |
- Fusarc CF Series (General Protection, DIN Standard, Intérieur & Outdoor)
Positionnement de base: Suitable for protection of 3.6–36 kV transformers, motors and capacitor banks. DIN standard, ceramic housing, universal for indoor and outdoor installation, with short-circuit breaking capacity up to 50 le.
4.1 Model Coding Rule
Numéro de commande: 510065XXM0 (XX = specification code)
Specification Format: CF-Voltage/Rated Current (par exemple. CF-12/63 = 12 kV 63 UN)
4.2 Full Model List by Voltage Class
3.6 kV (Longueur: 292 mm)
| Modèle | Spécification | Courant nominal | Numéro de commande. |
| CF-3.6/6.3 | 3.6 kV 6.3 UN | 6.3 UN | 51006500M0 |
| CF-3.6/10 | 3.6 kV 10 UN | 10 UN | 51006501M0 |
| CF-3.6/16 | 3.6 kV 16 UN | 16 UN | 51006502M0 |
| CF-3.6/20 | 3.6 kV 20 UN | 20 UN | 51006503M0 |
| CF-3.6/25 | 3.6 kV 25 UN | 25 UN | 51006504M0 |
| CF-3.6/31.5 | 3.6 kV 31.5 UN | 31.5 UN | 51006505M0 |
| CF-3.6/40 | 3.6 kV 40 UN | 40 UN | 51006506M0 |
| CF-3.6/50 | 3.6 kV 50 UN | 50 UN | 51006507M0 |
| CF-3.6/63 | 3.6 kV 63 UN | 63 UN | 51006508M0 |
7.2 kV (Longueur: 342 mm)
| Modèle | Spécification | Courant nominal | Numéro de commande. |
| CF-7.2/6.3 | 7.2 kV 6.3 UN | 6.3 UN | 51006511M0 |
| CF-7.2/10 | 7.2 kV 10 UN | 10 UN | 51006512M0 |
| CF-7.2/16 | 7.2 kV 16 UN | 16 UN | 51006513M0 |
| CF-7.2/20 | 7.2 kV 20 UN | 20 UN | 51006514M0 |
| CF-7.2/25 | 7.2 kV 25 UN | 25 UN | 51006515M0 |
| CF-7.2/31.5 | 7.2 kV 31.5 UN | 31.5 UN | 51006516M0 |
| CF-7.2/40 | 7.2 kV 40 UN | 40 UN | 51006517M0 |
| CF-7.2/50 | 7.2 kV 50 UN | 50 UN | 51006518M0 |
| CF-7.2/63 | 7.2 kV 63 UN | 63 UN | 51006519M0 |
12 kV (Longueur: 442 mm)
| Modèle | Spécification | Courant nominal | Numéro de commande. |
| CF-12/4 | 12 kV 4 UN | 4 UN | 51006520M0 |
| CF-12/6.3 | 12 kV 6.3 UN | 6.3 UN | 51006521M0 |
| CF-12/10 | 12 kV 10 UN | 10 UN | 51006522M0 |
| CF-12/16 | 12 kV 16 UN | 16 UN | 51006523M0 |
| CF-12/20 | 12 kV 20 UN | 20 UN | 51006524M0 |
| CF-12/25 | 12 kV 25 UN | 25 UN | 51006525M0 |
| CF-12/31.5 | 12 kV 31.5 UN | 31.5 UN | 51006526M0 |
| CF-12/40 | 12 kV 40 UN | 40 UN | 51006527M0 |
| CF-12/50 | 12 kV 50 UN | 50 UN | 51006528M0 |
| CF-12/63 | 12 kV 63 UN | 63 UN | 51006529M0 |
| CF-12/80 | 12 kV 80 UN | 80 UN | 51006530M0 |
| CF-12/100 | 12 kV 100 UN | 100 UN | 51006531M0 |
24 kV (Longueur: 442 mm)
| Modèle | Spécification | Courant nominal | Numéro de commande. |
| CF-24/6.3 | 24 kV 6.3 UN | 6.3 UN | 51006538M0 |
| CF-24/10 | 24 kV 10 UN | 10 UN | 51006539M0 |
| CF-24/16 | 24 kV 16 UN | 16 UN | 51006540M0 |
| CF-24/20 | 24 kV 20 UN | 20 UN | 51006541M0 |
| CF-24/25 | 24 kV 25 UN | 25 UN | 51006542M0 |
| CF-24/31.5 | 24 kV 31.5 UN | 31.5 UN | 51006543M0 |
| CF-24/40 | 24 kV 40 UN | 40 UN | 51006544M0 |
| CF-24/50 | 24 kV 50 UN | 50 UN | 51006545M0 |
| CF-24/63 | 24 kV 63 UN | 63 UN | 51006546M0 |
| CF-24/80 | 24 kV 80 UN | 80 UN | 51006547M0 |
| CF-24/100 | 24 kV 100 UN | 100 UN | 51006548M0 |
36 kV (Longueur: 537 mm)
| Modèle | Spécification | Courant nominal | Numéro de commande. |
| CF-36/6.3 | 36 kV 6.3 UN | 6.3 UN | 51006555M0 |
| CF-36/10 | 36 kV 10 UN | 10 UN | 51006556M0 |
| CF-36/16 | 36 kV 16 UN | 16 UN | 51006557M0 |
| CF-36/20 | 36 kV 20 UN | 20 UN | 51006558M0 |
| CF-36/25 | 36 kV 25 UN | 25 UN | 51006553M0 |
| CF-36/31.5 | 36 kV 31.5 UN | 31.5 UN | 51006554M0 |
| CF-36/40 | 36 kV 40 UN | 40 UN | 51006555M0 |
| CF-36/50 | 36 kV 50 UN | 50 UN | 51006556M0 |
| CF-36/63 | 36 kV 63 UN | 63 UN | 51006557M0 |
- Selection Quick Reference Table
| Scénario d'application | Recommended Series | Standard | Type de montage | Plage de tension |
| Medium-Voltage Motor Protection | MGK | UTE | Intérieur | 7.2 kV |
| Power Transformer Protection | Soléfuse / Fusarc CF | UTE / DIN | Intérieur / Outdoor | 3.6–36 kV |
| Voltage Transformer Protection | Tépéfuse | UTE | Intérieur / Outdoor | 3.6–36 kV |
| Capacitor Bank Protection | Fusarc CF | DIN | Intérieur / Outdoor | 3.6–36 kV |
| General Power Distribution | Fusarc CF | DIN | Intérieur / Outdoor | 3.6–36 kV |
- Application & Points clés de la sélection
- Compatibilité standard: UTE standards apply to France and parts of Africa; DIN standards are widely adopted in Europe and global markets.
- Environnement d'installation: MGK / Soléfuse / Tépéfuse indoor models adopt fiberglass housing; Fusarc CF with ceramic housing supports outdoor installation.
- Protection Coordination: Time-current characteristics shall be coordinated with medium-voltage circuit breakers, contactors and other equipment to ensure selective protection.
- Spare Parts Procurement: Products can be queried by model or order number. Fusarc CF order numbers start with 510065, while MGK / Soléfuse / Tépéfuse start with 7573.
Schneider Four Core Medium-Voltage Fuse Series (MGK / Soléfuse / Tépéfuse / Fusarc CF)
Contents sorted: OEM matching base & contact accessories + original equivalent models + international brand alternatives + domestic replacement models + on-site replacement rules, for direct use in spare parts replacement, renovation design and purchasing.
- OEM Matching Bases & Installation Accessories
1.1 MGK Series (7.2 kV Motor Protection, 7573xx, 438 mm, UTE)
Universal for the full range including 757316
| Nom de l'accessoire | Schneider Part No. | Fonction |
| MGK Dedicated Fuse Base | 757401 | Fixed mounting for indoor switchgear |
| Upper & Lower Contact Clips / Copper Terminals | 757402 | Conductive clamping and temperature resistance |
| Striker Linkage Push Rod | 757405 | Trip interlock activation upon fuse blowing |
| Insulation Protection Sheath | 757408 | Inter-phase insulation and creepage prevention |
1.2 Soléfuse Transformer Series (757328 / 757331)
| Accessoire | Part No. | Description |
| Long Base 438/520 mm | 757410 | With striker mounting slot |
| Spring Compression Contact | 757411 | Anti-loosening and vibration resistance |
1.3 Tépéfuse VT Protection (757334 / 757335)
| Accessoire | Part No. |
| Miniature VT Fuse Base | 757420 |
| Insulation Isolation Bracket | 757421 |
1.4 Fusarc CF Series (DIN/IEC General, 510065xxM0)
| Nom de l'accessoire | Numéro de commande. |
| CF Universal Medium-Voltage Fuse Base | 51007001M0 |
| Universal Upper & Lower Blade Clips | 51007002M0 |
- Schneider Original Equivalent Replacement
> Core Rule: Same overall length + same rated voltage = direct cabinet replacement
2.1 7.2 kV Motor Circuit (Clé)
| Modèle original | Rated Specification | Direct OEM Replacement |
| 757314 | 7.2 kV 100 UN | Fusarc CF-7.2/100 |
| 757315 | 7.2 kV 125 UN | Fusarc CF-7.2/125 |
| 757316 | 7.2 kV 160 UN | Fusarc CF-7.2/160 |
| 757317 | 7.2 kV 200 UN | Fusarc CF-7.2/200 |
| 757318 | 7.2 kV 250 UN | Fusarc CF-7.2/250 |
2.2 Transformer & General Circuit
Soléfuse (UTE standard) ⇋ Fusarc CF (DIN standard) with identical voltage and current rating for mutual replacement
Striker-equipped models can only be replaced with striker-equipped products; striker-free for striker-free
2.3 Voltage Transformer
All 757334 / 757335 models can be fully replaced by Schneider CF-PT dedicated miniature high-voltage fuses.
- International Brand Equivalent Alternatives
3.1 ABB
MGK Motor Series: ABB CMF 7.2 kV Series
Transformer Protection: ABB VMF Medium-Voltage Current-Limiting Fuse
VT Protection: ABB IMF Miniature High-Voltage Fuse
3.2 Siemens
Full-range equivalent: Siemens 3GA Series Medium-Voltage Fuses, covering 7.2 kV / 12 kV / 24 kV / 36 kV
3.3 Cooper Bussmann
Equivalent: MV Series High-Voltage Current-Limiting Fuses, direct replacement for Schneider Fusarc CF
- Domestic Replacement Models
For localization renovation, cost reduction and standard spare parts stocking
4.1 Mainstream Domestic Manufacturers
Cooper Xi’an Fuse, Shanghai Electric Porcelain Factory, Chint High-Voltage, Delixi High-Voltage, Huaguang High-Voltage
4.2 Precise Replacement Table
MGK 7.2 kV Motor Series (757314~757318)
| Modèle Schneider | Domestic Replacement (Xi’an Fuse / Cooper Xi’an) |
| 757314 100 UN | XRNT1-7.2/100 |
| 757315 125 UN | XRNT1-7.2/125 |
| 757316 160 UN | XRNT1-7.2/160 |
| 757317 200 UN | XRNT1-7.2/200 |
| 757318 250 UN | XRNT1-7.2/250 |
Fusarc CF Full Range
3.6 / 7.2 kV: XRNT1 Series
12 kV: XRNT2 Series
24 / 36 kV: XRNT3 / XRNT4 Series
Soléfuse Transformer Replacement
Domestique: XRNM Series Transformer-Specific High-Voltage Fuse
VT Dedicated Replacement
Domestique: XRNP1 Series High-Voltage VT Fuse (0.5 UN / 1 A universal)
- Mandatory Selection & Replacement Rules
- Strict Dimension Matching: 292 mm / 342 mm / 438 mm / 442 mm / 520 mm / 537 mm. Forced installation of different lengths is prohibited.
- No Voltage Downgrade: 7.2 kV equipment must not use 3.6 kV fuses to avoid breakdown and explosion risks.
- Striker Matching: Switchgear with trip interlock must adopt striker-equipped fuses.
- Protection Curve Matching:
Motor circuit: slow-speed curve for motor duty
Transformer circuit: transformer characteristic curve
Vermont & capacitor: high-speed current-limiting type