Siemens 3TL6113-0BM4

Produit: 3TL61 series 7.2 kV medium-voltage vacuum contactor (legacy imported unit, abandonné)

3TL61: 7.2 kV voltage class; 3TL65: 12 kV voltage class. The 3TL platform is an older-generation vacuum contactor manufactured in Berlin. Its successor series is the 3TM.

Décodage du modèle: 3TL6113-0BM4

3TL61: 7.2 kV vacuum contactor base series

13: 3-pôle, rated operating current 250 A

0: Version standard, no mechanical latching

B: Coil control voltage AC 24 V

M4: Configuration des contacts auxiliaires: 4NON + 4NC positively-driven auxiliary switch

Principales spécifications électriques

ArticleParamètre
Rated operating voltage Ue7.2 kV
Rated operating current Ie250 UN
Nombre de pôles3-pôle
Fréquence50‑60 Hz
Tension de bobineAC 24 V
Closing power600 W, holding power 90 W (with economy holding resistor)
Endurance mécanique3 million operations
Vacuum interrupter electrical endurance2 million operations
Fréquence de fonctionnement maximale1200 opérations par heure
Contacts auxiliaires4NON + 4Caroline du Nord, positively‑driven
Power‑frequency withstand voltage (phase‑to‑ground / phase à phase)32 kV, 1 min
Tension de tenue aux chocs de foudre60 kV

Applications typiques

Switching of high-voltage motors, batteries de condensateurs, transformers and reactors; contactor-fuse combination (FC-circuit) inside KYN28, XGN switchgear cubicles.

Options de remplacement

  1. Siemens original successor: 3TM3313-0BB40

(7.2 kV-250 A, AC 24 V coil, 4NO+4NC auxiliary contacts, functional drop-in replacement. Cabinet cut-out dimensions require verification.)

  1. Spare part order numbers:

Interrompre le vide: 3TY5652-0AA00

Operating coil: 3TY5651-0AB00

Economy holding resistor: 3TY5664-0AA00

Notes d'entretien

When procuring spare parts for legacy units, always verify the complete type designation plus serial number from the nameplate; do not rely solely on the order number.

The 3TL61 series uses an economy holding resistor for the coil. Do not remove it during servicing.

Main-circuit resistance shall be ≤ 280 μΩ; measurement is mandatory during overhaul.

The auxiliary switch is positively-driven. Do not substitute with standard auxiliary contacts.

If you have a nameplate photo, I can help verify full compatibility. I can also compile dimension comparison tables for 3TL61 and 3TM33.

 