Produit: 3TL61 series 7.2 kV medium-voltage vacuum contactor (legacy imported unit, abandonné)
3TL61: 7.2 kV voltage class; 3TL65: 12 kV voltage class. The 3TL platform is an older-generation vacuum contactor manufactured in Berlin. Its successor series is the 3TM.
Décodage du modèle: 3TL6113-0BM4
3TL61: 7.2 kV vacuum contactor base series
13: 3-pôle, rated operating current 250 A
0: Version standard, no mechanical latching
B: Coil control voltage AC 24 V
M4: Configuration des contacts auxiliaires: 4NON + 4NC positively-driven auxiliary switch
Principales spécifications électriques
| Article | Paramètre |
| Rated operating voltage Ue | 7.2 kV |
| Rated operating current Ie | 250 UN |
| Nombre de pôles | 3-pôle |
| Fréquence | 50‑60 Hz |
| Tension de bobine | AC 24 V |
| Closing power | 600 W, holding power 90 W (with economy holding resistor) |
| Endurance mécanique | 3 million operations |
| Vacuum interrupter electrical endurance | 2 million operations |
| Fréquence de fonctionnement maximale | 1200 opérations par heure |
| Contacts auxiliaires | 4NON + 4Caroline du Nord, positively‑driven |
| Power‑frequency withstand voltage (phase‑to‑ground / phase à phase) | 32 kV, 1 min |
| Tension de tenue aux chocs de foudre | 60 kV |
Applications typiques
Switching of high-voltage motors, batteries de condensateurs, transformers and reactors; contactor-fuse combination (FC-circuit) inside KYN28, XGN switchgear cubicles.
Options de remplacement
- Siemens original successor: 3TM3313-0BB40
(7.2 kV-250 A, AC 24 V coil, 4NO+4NC auxiliary contacts, functional drop-in replacement. Cabinet cut-out dimensions require verification.)
- Spare part order numbers:
Interrompre le vide: 3TY5652-0AA00
Operating coil: 3TY5651-0AB00
Economy holding resistor: 3TY5664-0AA00
Notes d'entretien
When procuring spare parts for legacy units, always verify the complete type designation plus serial number from the nameplate; do not rely solely on the order number.
The 3TL61 series uses an economy holding resistor for the coil. Do not remove it during servicing.
Main-circuit resistance shall be ≤ 280 μΩ; measurement is mandatory during overhaul.
The auxiliary switch is positively-driven. Do not substitute with standard auxiliary contacts.