300UN, 600V, 3-phase integrated bypass soft starter from ABB’s PSTX series, providing smooth motor starting and stopping as well as comprehensive motor protection
Parametri chiave: Rated current 300A (AC-53b), rated voltage 208–600V AC, control voltage 100–240V AC, protocolli di comunicazione: ModBus, Ethernet/IP, BACnet
Funzioni principali: Voltage ramp / torque control start, limite attuale (standard / doppio / ramp), soft stop, integrated bypass contactor, full-featured motor protection
Certificazioni: Conforme alla norma IEC/EN 60947-4-2, UL 508, CSA C22.2 No. 14, CE, CCC
- Model Number Explanation
| Codice | Descrizione |
| PSTX | ABB advanced smart soft starter series |
| 300 | Corrente operativa nominale: 300UN (continuous current under AC‑53b) |
| 600 | Tensione operativa nominale: 600V (applicable range: 208–600V AC) |
| 70 | Control voltage range: 100–240V AC (universal for 50/60Hz) |
- Complete Technical Specifications
| Categoria | Dettagli |
| Elettrico | • Rated operational current (AC‑53b): 300UN |
| • Rated operational voltage (Ue): 208–600V AC | |
| • Phase: 3 | |
| • Control voltage (Noi): 100–240V AC (50/60Hz) | |
| • Compatible power: 160kW (400V), 200HP (460V) | |
| • Starting method: Soft start/stop with integrated bypass | |
| • Potere di interruzione: 50IL (600V) | |
| • Overload capacity: 1.1×In (continuous at 40°C) | |
| • Starting current limit: 3 modalità (standard / doppio / ramp), up to 3.5×In | |
| Meccanico & Ambientale | • Ingress protection: IP00 |
| • Mounting: Guida DIN / bolt mounting | |
| • Operating temperature: ‑25°C to +60°C | |
| • Storage temperature: ‑40°C to +80°C | |
| • Relative humidity: 5–95% (senza condensa) | |
| • Dimensioni (L×A×P): 250×368×190mm | |
| • Peso: ca. 12kg | |
| Caratteristiche | • 3‑phase fully controlled thyristor control with integrated bypass contactor (reduces power consumption) |
| • Multiple starting modes: voltage ramp, controllo della coppia, limite attuale | |
| • Soft stop function (prevents water hammer, ideal for pump loads) | |
| • 15 motor protection functions: sovraccarico, rotore bloccato, perdita di fase, phase imbalance, guasto a terra, ecc. | |
| • Modular design, supports DIN rail and door mounting | |
| • Graphic display with 4‑key operation, supports remote monitoring and parameter setting |
- Vantaggi principali
- Integrated bypass design: Automatically switches to bypass contactor after startup, lowers operating power consumption (≤1.5W) and extends thyristor service life
- Comunicazione flessibile: Built-in Modbus RTU/TCP, Ethernet/IP, BACnet for easy integration into industrial networks
- Protezione completa: Full motor, short-circuit and overload protection in compliance with IEC 60947-4-2
- Wide voltage compatibility: 208–600V AC universal input, globally applicable for complex grid conditions
- User-friendly operation: Removable HMI panel supports door mounting; status reading and parameter adjustment without shutdown
- Detailed Applications
4.1 Trattamento delle acque & Fluid Handling
Large pump control: Centrifugal / axial / mixed flow pumps in municipal water supply and wastewater treatment plants; soft stop prevents water hammer and reduces pipeline pressure shock
Submersible sewage pumps: Reduces mechanical stress during startup, avoids cavitation and reverse flow impact, migliora l'affidabilità del sistema
Chemical process pumps: Smooth startup for high-viscosity fluid pumps, minimizes mechanical seal wear and extends service life
4.2 Manufacturing & Movimentazione dei materiali
Compressor systems: Smooth startup for air and refrigeration compressors, reduces grid impact and prevents belt slippage
Crushers / grinders: Heavy-duty crushing equipment in mining and building materials; current-limited startup controls mechanical shock and protects drive systems
Conveyor systems: Long-distance belt conveyors; smooth acceleration avoids material spillage and reduces belt tension stress
Miscelatori / agitatori: Mixers in food and pharmaceutical industries; torque-controlled startup ensures process stability
4.3 Edificio & Infrastrutture
Sistemi HVAC: Grandi tifosi (cooling towers, unità di condizionamento dell'aria) e pompe; soft starting reduces impact on building power grids
Metro / tunnel ventilation: Synchronous soft starting of multiple high-power fans to avoid interference with lighting and signaling systems
Fire pumps: Main and backup pumps in emergency fire systems; ensures reliable startup in compliance with fire safety codes
4.4 Applicazioni industriali speciali
Pulp & carta: Vacuum / pressure fans for paper machines; smooth startup protects precision drive systems
Oilfield production: Pumping units and water injection pumps; adapts to harsh field environments and improves equipment reliability
Port machinery: Auxiliary motors for cranes and handling equipment; soft starting protects hydraulic systems
- Cross-Reference for International Brand Equivalents
| Marca | Serie | Modello | Parametri chiave | Capacità di interruzione | Codice ordine |
| Schneider | ATS48 | ATS48D32Q | 320UN, 208–600V, 100–240V control | 50IL | ATS48D32Q |
| Siemens | 3RW55 | 3RW5546‑6HA14 | 300UN, 208–690V, 24V control | 50IL | 3RW5546‑6HA14 |
| Eaton | DMX | DMX300S600 | 300UN, 208–600V, 100–240V control | 50IL | DMX300S600 |
| Rockwell | SMC‑50 | SMC‑50‑300A‑1 | 300UN, 208–600V, 100–240V control | 50IL | 150‑S300NBD |
| ABB | PST | PST300‑600‑70 | 300UN, 208–600V, 100–240V control | 50IL | PST300‑600‑70 |
- Complete ABB PSTX Series Model List (Standard Order Codes)
The PSTX series is available in various rated currents for different motor powers. Core models are listed below:
| Corrente nominale | Modello | Codice d'ordine standard | Compatible Power (400V) | Compatible Power (460V) |
| 30UN | PSTX30‑600‑70 | 1SFA898104R7000 | 15kW | 20HP |
| 37UN | PSTX37‑600‑70 | 1SFA898105R7000 | 18.5kW | 25HP |
| 45UN | PSTX45‑600‑70 | 1SFA898106R7000 | 22kW | 30HP |
| 60UN | PSTX60‑600‑70 | 1SFA898107R7000 | 30kW | 40HP |
| 72UN | PSTX72‑600‑70 | 1SFA898108R7000 | 37kW | 50HP |
| 85UN | PSTX85‑600‑70 | 1SFA898109R7000 | 45kW | 60HP |
| 105UN | PSTX105‑600‑70 | 1SFA898110R7000 | 55kW | 75HP |
| 142UN | PSTX142‑600‑70 | 1SFA898111R7000 | 75kW | 100HP |
| 170UN | PSTX170‑600‑70 | 1SFA898112R7000 | 90kW | 125HP |
| 210UN | PSTX210‑600‑70 | 1SFA898113R7000 | 110kW | 150HP |
| 300UN | PSTX300‑600‑70 | 1SFA898114R7000 | 160kW | 200HP |
| 370UN | PSTX370‑600‑70 | 1SFA898115R7000 | 200kW | 250HP |
| 470UN | PSTX470‑600‑70 | 1SFA898116R7000 | 250kW | 350HP |
| 570UN | PSTX570‑600‑70 | 1SFA898117R7000 | 315kW | 400HP |
| 720UN | PSTX720‑600‑70 | 1SFA898118R7000 | 400kW | 500HP |
| 840UN | PSTX840‑600‑70 | 1SFA898119R7000 | 450kW | 600HP |
- Selezione & Note applicative
- Carica corrispondenza: 300A fits 160kW motors at 400V and 200HP motors at 460V. Consider load type (fan / pompa / compressore) and starting conditions during selection
- Installation notes: Montaggio su guida DIN standard da 35 mm; keep ≥50mm clearance above and below for heat dissipation; vertical installation recommended
- Communication setup: Modbus RTU supported by default; EtherNet/IP or BACnet can be enabled via parameter settings
- Protection configuration: Set overload curve, protezione del rotore bloccato, protezione dalla perdita di fase, ecc., according to motor parameters to ensure safe operation
- Replacement selection: Match rated current, voltage range, control voltage and protection functions when replacing; prefer equivalent advanced smart soft starters
Applicazioni non idonee
Applications requiring variable frequency speed control (ABB ACS series drives recommended)
Special voltage systems below 100V or above 600V
All'aperto / humid environments requiring IP20 or higher protection (protected version or enclosure required)
Key Differences Between ABB PSTX300-600-70-1 and PSTX300-600-70
- Official Model Definition & Codici d'ordine
Modello standard: PSTX300-600-70, official order code: 1SFA898114R7000
Model with suffix-1: PSTX300-600-70-1, typically corresponds to 1SFA898114R7001 (special configuration version)
- Differenze fondamentali
| Articolo | PSTX300‑600‑70 (Standard) | PSTX300‑600‑70‑1 (‑1 Version) |
| Tensione di controllo | 100–240V AC (50/60Hz universale) | 24A DC (DC control supply) |
| Suffix meaning | “70” indicates standard AC control voltage | “‑1” typically indicates 24V DC control version |
| Applicazione | General industrial and commercial use, standard AC control circuits | Suitable for safety circuits, Controllo PLC, DC control systems and other low‑voltage control applications |
| Comunicazione | Identico: built‑in Modbus RTU/TCP, Ethernet/IP, BACnet | Identico |
| Core ratings | Identico: 300UN, 600V, integrated bypass, operating temp up to 60°C | Identico |
| Physical dimensions | Identico: 250×368×190mm, 12kg, 35mm DIN rail mount | Identico |
- Descrizione dettagliata
- Control voltage difference: This is the fundamental distinction. The standard version uses 100–240V AC control power, while the-1 version uses 24V DC to suit different control system power supplies
- Configuration positioning: The “-1” suffix in ABB soft starter naming generally denotes a 24V DC control version, designed for integration with PLC, DCS and other DC control systems, or safety applications requiring electrical isolation between control and main circuits
- Functional consistency: Except for control voltage, all core functions are identical:
300A rated operational current, suitable for 160kW (400V) / 200HP (460V) motori
3-phase fully controlled thyristor control with integrated bypass contactor (operating power ≤1.5W)
Multiple starting modes: voltage ramp, controllo della coppia, limite attuale
15 motor protection functions: sovraccarico, rotore bloccato, perdita di fase, phase imbalance, guasto a terra, ecc.
Removable graphic HMI panel with 15 language support
- Raccomandazioni per la selezione
- Control supply matching: Select standard version for AC control systems and-1 version for DC control systems
- Safety requirements: For safety applications requiring isolation between control and main circuits, the 24V DC-1 version is preferred
- Spare parts management: Distinguish between the two models to avoid failure due to control voltage mismatch
- Replacement compatibility: Montaggio identico, communication and protection features; interchangeable with appropriate control power supply (subject to system compatibility check)
The only substantive difference between ABB PSTX300-600-70-1 and PSTX300-600-70 is the control voltage: standard version is 100–240V AC, while the-1 version is 24V DC. All other core parameters, functions and physical dimensions are identical. Selection should be based on control system power type and safety requirements.
Contattore,interruttore automatico,inverter solare,contatore elettrico,batterie solari