Basic Model Definition
Catalog Number: 440R-N23114
Internal Model Code: MSR126.1T
Marca: Allen-Bradley (Rockwell Automazione), Guardmaster Minotaur Series
Ciclo vitale: Active production model, manufactured in Czech Republic, standard 1-year warranty
- Core Electrical Specifications
2.1 Alimentazione elettrica
Tensione nominale: 24V CA/CC, raggio d'azione: 0.85~1.1× rated voltage (20.4~26,4 V)
Consumo energetico: 4W, compatibile con 50/60Hz
Terminals A1/A2: Power input
2.2 Safety Inputs (Dual-channel 4-wire with cross short-circuit detection)
2 normalmente chiuso (NC) safety input paths (S11-S12 / S21-S22)
Supports dual-channel emergency stop, safety door switches and safety light curtains; built-in cross-channel short-circuit fault diagnosis
Maximum input loop resistance: ≤90Ω
2.3 Reset Circuit (S33-S34)
MSR126.1T supports automatic reset and manual reset dual modes
- Ripristino automatico: Short S33 and S34; outputs close automatically after faults are cleared
- Ripristino manuale: Connect an external normally open reset pushbutton to S33-S34; manual push is required to restore outputs
Difference from MSR126.1R: MSR126.1R only provides monitored manual reset without automatic reset function
2.4 Safety Output Contacts (Force-guided safety contacts complying with IEC 61810-3)
2 safety normally open (NO) contatti: 13-14, 23-24
Load Ratings:
DC-13: 6A/24V DC; 3A/24V DC (for frequent switching)
AC-15: 5A/250 V CA
Tempo di risposta: ca. 15SM; Recovery Time: 100SM
No auxiliary alarm contacts
- Safety Certification Ratings (Top Industry Standards)
ISO 13849-1: Categoria 4 / PL e
CEI 61508 / CEI 61511: SIL 3
IN 954-1: Categoria di sicurezza 4, Categoria 0 Fermare
Certificazioni: CE, cULus, CCC, BG, C-Tick
- Mechanical Dimensions & Montaggio
Larghezza: 22.5mm (compact DIN rail mounting)
Dimensione complessiva: 110mm (H) ×75 mm (D) × 22.5mm (W)
Peso: 160G
Terminali: Fixed screw terminals (non-pluggable), Grado di protezione IP20
Temperatura operativa: -25℃ ~ +70 ℃
- Front Panel LED Indicator Meanings
- PWR (Verde): Steady on when power supply is normal
- CH1 (Verde): Illuminated when Channel 1 input circuit is closed
- CH2 (Verde): Illuminated when Channel 2 input circuit is closed
All three LEDs on → Safety output contacts closed; Any single channel open → Outputs cut off
- Scenari applicativi tipici
- Dual-channel emergency stop button circuit monitoring
- 4-wire safety door switches (with short-circuit detection)
- Safety light curtain / light screen safety circuits
- Safety cut-off for machine tools, automated production lines and packaging equipment
Suitable for equipment requiring high safety ratings of PL e / SIL3
- Series Model Comparison for Selection
| Catalogo n. | Internal Code | Modalità di ripristino | Alimentazione elettrica | Configurazione del canale |
| 440R‑N23114 | MSR126.1T | Selectable Auto/Manual Reset | 24V CA/CC | Dual-channel 4-wire |
| 440R‑N23113 | MSR126.1R | Monitored Manual Reset Only | 24V CA/CC | Dual-channel 4-wire |
| 440R‑N23112 | MSR126T | Auto/Manual Reset | 230V e | Dual-channel 4-wire |
- Brief Wiring Logic
- Connect 24V AC/DC power to terminals A1/A2
- Wire two NC safety switches (arresto di emergenza / interruttori delle porte) in series to S11-S12 and S21-S22 respectively
- Short-circuit S33-S34 for automatic reset; connect an NO pushbutton in series for manual reset
- Wire the safety coil of main contactors in series across terminals 13-14 E 23-24
- Disconnection of any safety input or cross-channel short-circuit will simultaneously open both NO outputs to cut power supply
- Troubleshooting Guidelines
- LED PWR spento: Power phase loss, insufficient voltage or loose wiring
- Single CH1/CH2 LED off: Corresponding channel switch open or circuit wire breakage
- Both CH1 and CH2 LEDs lit but outputs fail to close: Cross-channel short-circuit fault; power cycle to reset, or reset circuit not shorted / reset button not pressed
- Saldatura dei contatti: Excessive output load; replace contactors with higher capacity
Full Specifications of Safety Output Contacts for Allen-Bradley 440R-N23114
- Basic Contact Structure
- Quantità & Tipo: 2 independent redundant safety normally open (NO) contacts at terminals 13-14 E 23-24; no auxiliary alarm contacts or delayed outputs
- Contact Construction: Force-guided safety contacts (CEI 61810-3), dual-channel redundant mechanical interlock. Single contact welding cannot maintain circuit conduction, fulfilling Category 4 / PL e / SIL3 safety architecture
- Materiale di contatto: AgSnO₂ silver tin oxide, resistente all'arco elettrico e antisaldatura
- Minimum Conducting Current: 10mA (ensures reliable circuit detection by contacts)
- Rated Load Currents (Official Standard Load Categories)
2.1 AC Load (AC-15, standard load for electromagnetic contactors)
250V e: 6UN (inductive-resistive load, cosφ=0.35)
UL B300 certified rating: 5UN / 250V e
2.2 DC Load (DC-13, elettrovalvole / Bobine CC)
Frequent switching at 24V DC: 3UN (standard switching rating)
Low-frequency light load (0.1Hz) at 24V DC: Massimo. 6A for short-term use (long-term high-frequency operation not recommended)
2.3 Continuous Thermal Current Ith (static carrying current without switching)
Maximum static continuous current per single contact: 6UN (only for permanent conduction with rare break operations)
- Resistenza elettrica & Operating Timing
- Resistenza elettrica (220V e / 4UN / cosφ=0.35)
6A breaking capacity: 100,000 operazioni
4A light load: 500,000 operazioni
- Safety Operation Timing
Response time from safety input open to contact break: ≤15ms
Contact pull-in recovery time after fault clearance: ca. 100SM
- Dielectric Withstand Voltage
Withstand voltage across open contacts: AC750V for 1 minuto
Resistenza di isolamento (DC500V test): ≥1000MΩ
- External Protection & Wiring Limitations
- Recommended Fuse for Output Circuit
Slow-blow fuse: 6UN; Fast-acting fuse: 10UN. Over-rated fuses are prohibited to prevent contact ablation and welding
- Applicable Wire Gauge: 0.2~2.5mm² solid / stranded copper wires; fixed non-pluggable screw terminals
- Maximum Operating Voltage: 250V e / 30A DC; overvoltage is strictly forbidden
- Contact Performance Matching Safety Ratings
ISO 13849-1: Categoria 4, PL e (independent cut-off via dual redundant contacts)
CEI 61508: SIL3; single contact failure will not disable safety cut-off function
Stop Category: IN 60204-1 Categoria 0 hard cut-off stop
- Quick Load Selection Table
| Tipo di carico | Voltaggio | Corrente nominale | Scenari applicativi |
| AC-15 | 250V e | 6UN | AC contactor coils |
| DC‑13 | 24A DC | 3UN | DC solenoid valves, DC contactors |
| Static Continuous | ≤250VAC / 30VCC | 6UN | Circuits with permanent conduction and minimal breaking operations |
tic Continuous | ≤250VAC / 30VCC | 6UN | Circuits with permanent conduction and minimal breaking operations |
Contattore,interruttore automatico,inverter solare,contatore elettrico,batterie solari


















NH42-63-318x560.png)