Serie: Modicon X80 (PLC M340)
Model explanation: BMXDDI3202KH = BMXDDI3202K + H; H = Conformal Coating version for harsh environments. Electrical specifications are identical to BMXDDI3202K. Only the PCB is coated with conformal coating for moisture-proof, mould-proof and salt-spray resistance, suitable for ports, impianti chimici, underground sites, high-humidity and dusty conditions.
✅ Specifiche di base
Tipo: 32-channel isolated digital input module, Lavello (positive logic)
Tensione in ingresso: 24VCC, sensor supply range 19~30VDC
Input current per channel: 2.5mA @24V
Logica 1: ≥11V / ≥2mA; Logica 0: ≤5 V / ≤0.5mA
Impedenza di ingresso: 9600OH
Tempo di risposta: Typical 4ms, maximum 7ms
Isolamento: Channel-to-channel isolation, resistenza di isolamento >10MΩ at 500VDC
Cablaggio: Compatible with 2-wire / 3-wire proximity switches (IEC61131-2 Type3, IEC60947-5-2). Input parallel connection is not allowed
Connettore: Single 40-pin FCN interface, single slot, supporto hot-swap
Consumo energetico: ≤3.9W; Typical backplane 3.3V consumption 121mA
Protezione della custodia: IP20
📌 Matching Cables (40-pin FCN)
- BMXFCWxxx3: Pre-wired loose cables (3m/5 m/10 m: BMXFCW303 / BMXFCW503 / BMXFCW1003)
- BMXFCCxxx3: Pre-assembled HE10 terminal cables (0.5/1/2/3/5/10M)
🧩 Compatible CPUs
Full Modicon M340 series: BMXP34xx00, BMXP34xx20 (including H versions). General X80 rack, configured via Unity Pro software.
⚖️ Model Comparison
BMXDDI3202K: Versione standard, no conformal coating, for conventional control cabinets
BMXDDI3202KH: Conformal coated version for harsh environments. Fully interchangeable in program, pinout and cabling.
📎 Alternative Selection Reference
Same-platform replacement: No drop-in equivalent. For fewer points, refer to BMXDDI1602K(H) (16-point Sink DI).
Sostituzione domestica: Verify sink logic, isolation and filter time, suitable for domestic PLC remote IO modules.
⚠️ Troubleshooting Tips
- No input signal: Check 24V supply, sensor polarity (Lavello, signal connects to 0V), broken pins in prefabricated cables.
- Lampeggiante / falso innesco: Check voltage drop and shielding. This module uses fixed hardware filter; filter parameters cannot be modified by software.
- Prefer KH version for humid and corrosive environments; standard K version is prone to PCB corrosion under long-term high humidity.
Schneider Ingresso digitale (DI) Module List by Platform
Nota: Suffix H = Conformal coating for harsh environments. X80 platform compatible with M340 / M580; Sink = sinking input, Source = sourcing input; AC = AC input.
- Modicon X80 (BMX series, M340 / M580)
Ingresso digitale CC (BMXDDI)
| Modello | Punti | Descrizione |
| BMXDDI1602K / BMXDDI1602KH | 16 | 24VCC, Lavello |
| BMXDDI1603K / BMXDDI1603KH | 16 | 48VCC, Lavello |
| BMXDDI1604T | 16 | 125VCC, Lavello, ampia temperatura |
| BMXDDI3202K / BMXDDI3202KH | 32 | 24VCC, Lavello (the model you enquired) |
| BMXDDI3203K / BMXDDI3203KH | 32 | 48VCC, Lavello |
| BMXDDI3232K / BMXDDI3232KH | 32 | 12/24VCC, Sink/Source configurable |
| BMXDDI6402K / BMXDDI6402KH | 64 | 24VCC, Lavello |
AC Digital Input (BMXDAI)
| Modello | Punti | Descrizione |
| BMXDAI0805 | 8 | 220VCA |
| BMXDAI0814 | 8 | 100~120VAC |
| BMXDAI1602 | 16 | 24VAC/24VDC, Fonte |
| BMXDAI1603 | 16 | 48VCA |
| BMXDAI1604 | 16 | 100~120VAC |
| BMXDAI1614 | 16 | 220VCA |
X80 Safety DI (Safety PLC dedicated)
| Modello | Punti | Descrizione |
| BMXSDI1602 | 16 | Safety digital input, 24VCC |
- TM3 Series (Expansion for M221/M241/M251/M262 Compact PLC)
| Modello | Punti | Descrizione |
| TM3DI8 | 8 | 24VCC, terminali a vite |
| TM3DI8G | 8 | 24VCC, spring clamp terminals |
| TM3DI8A | 8 | 120VCA |
| TM3DI16 | 16 | 24VCC, terminali a vite |
| TM3DI16G | 16 | 24VCC, spring clamp terminals |
| TM3DI16K | 16 | 24VCC, HE10 connector |
| TM3DI32K | 32 | 24VCC, HE10 connector |
- Advantys STB Distributed Remote IO
| Modello | Punti | Descrizione |
| STBDDI3725 | 16 | 24VDC Sink |
| STBDDI3420 | 8 | 24VDC Sink |
| STBDDI3610 | 4 | 24VDC Sink |
| STBDAI0200 | 2 | 100~240 VCA |
| STBDAI0400 | 4 | 100~240 VCA |
- Note supplementari
- X80 naming rule: `BMXDDI` = DC DI; `BMXDAI` = AC DI; `K` standard, `KH` conformal coated.
- K and KH variants of the same model are fully interchangeable in pinout, programming and backplane interface, only differing in PCB protection.
- Mixed I/O modules (DI+DO) such as BMXDDM16022 are excluded from this table.
Application Scenarios of Schneider Digital Input (DI) Moduli (X80/STB/TM3, ecc.)
Core function of DI modules: Collect binary switch signals, transfer ON/OFF status from external dry contacts, sensori, pulsanti, limit switches and auxiliary contacts of contactors to PLC. It only detects on/off status and does not process analog signals. The following is sorted by industry and signal type, applicable to BMXDDI3202KH and other X80 modules.
- General Signal Acquisition (Used across all industries)
- Pulsanti, selettori, pulsanti di arresto di emergenza
Local cabinet operation, remote control boxes, E-stop signals (general E-stop; safety E-stop should use dedicated safety DI module BMXSDI1602).
- Interruttori di limite, interruttori di viaggio, interruttori di prossimità, sensori fotoelettrici
Equipment position detection: cylinder confirmation, interruttori delle porte, baffle limit for material level, object presence detection.
BMXDDI3202KH is 24VDC Sink, compatible with mainstream NPN proximity switches.
- Auxiliary contacts of contactors / relè, circuit breaker status feedback
Motor running feedback, VFD ready feedback, circuit breaker open/close status, thermal relay fault signals.
- Dry contact signals
Fire alarm systems, controllo degli accessi, damper/valve position feedback in HVAC, float level switches.
- HVAC
Corsa / fault feedback of fans and water pumps
Differential pressure switches, frost protection switches, air damper / water valve end-position feedback
Filter differential pressure alarm, high/low float level switches
Feedback of smoke exhaust dampers and fire dampers
Conformal coated KH versions (BMXDDIxxxxKH) are preferred for humid and dusty machine rooms.
- Trattamento delle acque, Fornitura d'acqua & Drenaggio, Impianti di acque reflue
Level switches (alto livello, basso livello, overflow)
Pump run, colpa, hand-auto status
Limit signals for bar screens and sludge scrapers
Pulse signals from flow meters (high-speed pulses require dedicated high-speed counter modules; standard DI is not suitable for high-frequency pulses)
Valve open / closed position feedback
KH coated modules are widely used in corrosive, high-humidity wastewater sites.
- Confezione, Linee di assemblaggio & Linee di produzione automatizzate
Photoelectric detection for material presence / missing material
Cylinder and clamp confirmation signals
Conveyor belt jam and deviation switches
Barcode detection, silo level switches
Safety gate and guard door status signals
BMXDDI6402K (64-point DI) is commonly used for high-point-count lines to save slots.
- Crane Systems, Trasmettere & Warehouse Logistics
Crane travel limits, upper/lower hard limits, buffer switches
Pallet in-position, bay detection
Roller conveyor deviation and E-stop loop feedback
Roller shutter and guard door status
- Power Distribution Rooms & Energy Monitoring
Circuit breaker and disconnector open/close position feedback for high-voltage cabinets
Cabinet door interlock, earthing switch status
Transformer thermostat switches, cooling fan feedback
DC panel fault alarm dry contacts
BMXDAI AC DI modules are often used for 220VAC cabinet signals.
- Olio & Gas, Industria chimica, Porti (Ambienti difficili)
Valve position feedback, pump status, dry contact output of combustible gas detectors
Limit switches and door interlocks for trestle and quay equipment
Salt spray, high humidity and condensation → select KH conformal coated versions (BMXDDI3202KH etc.). Standard K versions are vulnerable to corrosion.
- Automazione degli edifici, Fire Protection & Stazioni di pompaggio
Dry contact alarms from fire host, sprinkler pressure switches
Elevator interlock signals, smoke exhaust fan status
Rainwater pumps, sump tank level monitoring
✅ Quick Selection Guide by Scenario
Normal indoor control cabinet, ambiente secco: BMXDDIxxxK
Chimico / porta / elevata umidità & nebbia salina: BMXDDIxxxKH (rivestimento conforme)
220VAC contact signals: BMXDAI AC DI
Circuiti di sicurezza, cancelli di sicurezza, safety E-stop: BMXSDI safety DI
Piccole macchine, low I/O count: TM3DI series
Distributed remote IO with scattered field points: STB Advantys remote DI
⚠️ Scope Limitations (What DI modules cannot do)
- Cannot directly measure 4-20mA or temperature (AI analog modules required)
- Standard DI is not suitable for high-frequency pulse counting (high-speed counter module required)
- Safety functions shall not be implemented via ordinary DI; dedicated safety DI modules are mandatory.
Contattore,interruttore automatico,sensore,Codificatore,PLC,Convertitore