Schneider LADN20 Auxiliary Contact Block

Modello: LADN20 Brand: Schneider Electric Product Series: Matching accessories for TeSys D / TeSys Deca contactors Product Type: Front snap-on instantaneous auxiliary contact block Contact Configuration: 2NO (2 Normally Open contacts, no Normally Closed contacts) Metodo di montaggio: Direct snap-fit on contactor front face, tool-free installation Applicable Contactors: LC1D09~LC1D150, CAD control relays, LC1F / CR1F series ...

  • Dettagli del prodotto

Modello: LADN20

Marca: Schneider Electric

Serie di prodotti: Matching accessories for TeSys D / TeSys Deca contactors

Tipo di prodotto: Front snap-on instantaneous auxiliary contact block

Configurazione dei contatti: 2NO (2 Normally Open contacts, no Normally Closed contacts)

Metodo di montaggio: Direct snap-fit on contactor front face, tool-free installation

Applicable Contactors: LC1D09~LC1D150, CAD control relays, LC1F / CR1F series contactors

  1. Scomposizione del codice modello
  2. LADN: General prefix for front-mounted auxiliary contacts of TeSys D series
  3. 2: Total number of contact circuits = 2
  4. 0: Number of NC (Normalmente chiuso) contacts = 0

Full definition: 2 Normalmente aperto, 0 Contatti ausiliari normalmente chiusi

Universal naming rule for the same series:

LADN02: 0NO, 2NC

LADN11: 1NO, 1NC

LADN22: 2NO, 2NC

  1. Contrassegni dei terminali & Wiring Definition

Two independent NO circuits with standard terminal numbers:

1st NO circuit: 53 (ingresso), 54 (produzione)

2nd NO circuit: 63 (ingresso), 64 (produzione)

Terminal structure: Morsetti con morsetto a vite, coppia di serraggio 1.7 N·m

Compatible wire cross-sections:

Single solid wire / ferrule-equipped flexible wire: 1~4 mm²

Two parallel wires: 1~2.5 mm²

  1. Core Electrical Specifications

4.1 Tensione di isolamento nominale Ui

690 V (norma CEI); UL/CSA certified for 600 V

4.2 Conventional Thermal Current Ith

10 UN (ambient temperature 60°C)

4.3 AC-15 AC Control Load (Elettrovalvole / Coils / Indicator Lamps)

120 V e: 6 UN

230 V e: 3 UN

400 V e: 1.8 UN

690 V e: 1.04 UN

4.4 DC-13 DC Inductive Load

125 A DC: 0.55 UN

600 A DC: 0.1 UN

4.5 Minimum Operating Condition (Suitable for Weak Signals)

Minimum switching voltage: 17 V; Minimum switching current: 5 mA

4.6 Contact Operation Timing

No overlap time between make and break: 1.5 SM (NO and NC contacts never conduct simultaneously)

4.7 Protezione & Parametri Ambientali

Classe di protezione: IP20 (for indoor cabinet use only)

Temperatura operativa: -25℃ ~ +60 ℃

Vita meccanica: ≥ 30 milioni di operazioni

Vita elettrica (under standard load): ≥ 1 milioni di operazioni

4.8 Dimensioni & Peso

Dimensioni: 48 (H) × 26 (W) × 42 (D) mm; Net weight ≈ 30 G

  1. Certificazioni & Standard

Certificazioni: CCC, CE, UL, CSA, EAC, UKCA

Compliant Standards: GB/T 14048.5, CEI 60947-5-1, IN 50012

  1. Funzioni & Scenari applicativi
  2. Motor Start-Stop Feedback: Two independent passive NO signals after contactor closure, sent to PLC, indicator lamps and upper computer for operating status collection
  3. Expansion of Electrical Interlocks: Add interlock contacts for dual-motor and forward/reverse control circuits
  4. Multi-channel Alarm Output: One circuit for local panel lamps, one for remote control cabinet signals
  5. Espansione del circuito di controllo: Supplement auxiliary contacts when factory-built contacts are insufficient (LC1D standard configuration only includes 1NO+1NC)

Applicable Industries: Macchine utensili, HVAC, pompe dell'acqua, tifosi, automatic production line control cabinets

  1. Selection Table for LADN Front-Mounted Contacts of the Same Series
ModelloConfigurazione dei contattiApplicazione principale
LADN202NODual-channel operation feedback, no NC signal required
LADN022NCFault shutdown and open-circuit status detection
LADN111NA+1NCOne operation signal + one fault signal (most universal)
LADN222NO+2NCMulti-signal collection and complex interlock circuits
  1. Installazione & Replacement Instructions
  2. Installazione: Align with the front slot of the contactor and press down until a snap sound is heard for locking; for removal, pinch both side latches and pull upward
  3. Installation Limit: A single LC1D contactor can be fitted with maximum 1 front LADN contact block. The LAD8N series side-mount modules are required for additional contacts
  4. Modelli alternativi

Domestic equivalents with identical functions: Delixi F4-20, Chint F4-20

Schneider side expansion contacts: LAD8N20 (side-mounted 2NO contacts)

  1. Strict Usage Prohibitions
  2. Not allowed for main power circuits; only applicable to control signals and small coil loads (AC-15 / DC-13)
  3. Forbidden to operate above the rated insulation voltage of 690 V
  4. Cannot be exposed outdoors or in humid unprotected environments (IP20 rating limited to cabinet interior)
  5. Do not connect multiple 4 mm² wires to one single terminal; maximum cross-section for parallel wiring is 2.5 mm²

Full Application Fields of Schneider LADN20 Auxiliary Contact Block

  1. Automazione industriale generale
  2. Conveying Line Equipment

Collect contactor status for belt conveyors, linee a rulli, transfer machines and lifting positioning mechanisms. Two NO circuits separately transmit local lamp signals and operation data to PLC.

  1. Custom Non-standard Automation Machines

Expand original contactor contacts on assembly machines, inspection equipment and stamping loading/unloading machines to upload equipment running status remotely.

  1. Robot Supporting Control Cabinets

Monitor solenoid valve circuits for robot external axes and fixture clamping; two isolated passive signals avoid mutual interference.

  1. Machine Tool Processing Industry (Principali scenari applicativi)
  2. CNC Lathes, Machining Centers, Milling Machines

Expand contacts for spindle motors, cooling pumps and chip conveyors. One signal feeds local panel running lamps, the other transmits ready signals to the machine tool system.

  1. Grinding Machines & Drill-Tap Centers

Collect start-stop status of lubrication pumps and hydraulic stations to meet the demand for synchronous multi-signal output on machine tools.

  1. Stamping & Sheet Metal Machines

Realize status interlock and signal upload for main hydraulic motors and feeding motors.

  1. HVAC, Fornitura d'acqua & Drenaggio, Building Electromechanical Systems
  2. Fan & Water Pump Control Boxes

For air conditioning fans, ventilatori delle torri di raffreddamento, circulating pumps and sewage pumps, two NO contacts deliver local indication signals and communication data to building BA systems respectively.

  1. Central Air Conditioning Units

Expand contact terminals for chillers and condensate pumps for remote building monitoring.

  1. Fire-fighting Supporting Equipment

Upload operating status of smoke exhaust fans and sprinkler pumps to fire alarm control panels.

  1. Attrezzature di sollevamento, Logistica & Warehousing Machinery
  2. Overhead Cranes & Electric Hoist Control Cabinets

Collect running signals of lifting, cross-travel and long-travel contactors. Two signal channels serve local display and upper warehouse management systems separately.

  1. Automated Warehouses & Impilatori

Transmit status feedback of traveling motors and fork lifting motors for stacker safety interlock judgment.

  1. Energia, HVAC & Environmental Protection Equipment
  2. Air Compressor & Vacuum Pump Control Cabinets

Monitor main loading motors and cooling fans; upload operation data to energy management systems for runtime statistics.

  1. Sewage Treatment Equipment

Multi-channel status collection for aeration fans, dosing pumps and sludge transfer pumps.

  1. PV Auxiliary Equipment

Output start-stop signals for cooling fans and circulating water pumps.

  1. Gomma & Plastica, Confezione & Printing Industry
  2. Stampaggio ad iniezione & Extrusion Machines

Transmit operation feedback of screw motors, mold temperature machine water pumps and conveyor belts.

  1. Confezione & Printing Machines

Two independent signal outputs for film feeding and winding motors to distinguish local alarm and remote monitoring signals.

  1. Transito ferroviario & EV Charging Pile Supporting Systems
  2. Status collection for charging pile cooling fans and main contactors
  3. Signal expansion for station ventilation and water pump electromechanical control cabinets
  4. Application Matching Features (Matching LADN20’s 2NO-only characteristic)

Universal requirement across all industries: only collect power-on running status without open-circuit fault signals; two isolated passive switching signals with separate grounding and no voltage conflict.

Select LADN11 (1NA+1NC) if both running and shutdown fault signals need to be collected simultaneously.