SIRIUS 3RT series 3-pole AC power contactor, Size S6, main circuit busbar connection, AC/DC 220~240V coil, built-in 2NO+2NC auxiliary contacts
- Decodifica del modello
3RT1056-6AP36
3RT: SIRIUS power contactor series
10: Standard contactor (non-safety, non-reversing type)
56: Frame size S6, AC-3 400V 185A
6: Coil voltage 220…240V AC/DC
UN: Collegamento sbarre del circuito principale
P: Screw terminals for auxiliary contacts
36: Contatti ausiliari 2 Normalmente aperto + 2 Normalmente chiuso (2NO+2NC)
- Specifiche elettriche principali
| Articolo | Parametro |
| Number of main poles | 3 poli (3NO) |
| AC-3 (Motor load @400V) | 185UN, 90kW |
| AC-1 (Resistive load @40℃) | 215UN |
| Rated operating voltage Ue | Massimo. 1000V e |
| Coil control voltage Uc | 220~240 V CA/CC (Wide-range AC/DC coil) |
| Contatti ausiliari | 2NO + 2NC, terminali a vite |
| Collegamento al circuito principale | Sbarra collettrice |
| Dimensioni del telaio | S6 |
| Grado di protezione | Front IP00; IP20 with cover installed |
| Impulse withstand voltage | 8kV main circuit / 6kV auxiliary circuit |
| Temperatura ambiente | -25℃ ~ +60 ℃ (Declassamento richiesto sopra i 40 ℃) |
- Ambito di applicazione
On/off control of 3-phase motors such as fans, pompe e compressori dell'acqua
Control cabinets, central air conditioning, industrial production lines and power cabinets
Can be matched with 3RU thermal overload relay for motor overload protection; 3RT19 surge suppressor for coil EMC interference suppression
- Modelli alternativi
- Domestico SIEMENS sostituzione: 3RT5056-6AP36
Funzione identica, current rating and coil specification. Made in China, direct replacement for 3RT1056-6AP36 with identical mounting dimensions, officially recommended replacement model
- Upgraded model in same series: 3RT1064-6AP36 (AC-3 225A, 110kW)
- Downsized model in same series: 3RT1055-6AP36 (AC-3 150A, 75kW)
Nota: 3RT1056 manufactured in Germany; 3RT5056 manufactured domestically. Fully compatible in electrical performance and mounting hole layout, direct interchangeable in projects.
- Installazione & Linee guida per la manutenzione
- Installazione: Montaggio verticale, tilt ≤ ±5°. Heat dissipation clearance required. S6 frame generates considerable heat; derating is required for multiple units mounted side-by-side inside cabinet.
- Circuito principale: Busbar connection, tighten to specified torque per datasheet to prevent overheating and contact burning.
- Bobina: Wide-range AC/DC coil, compatible for AC and DC control. 3RT19 surge suppression module is recommended in parallel to reduce interference to PLC digital outputs.
- Contact life: Under AC-3 motor duty, mechanical life approx. 10 milioni di operazioni; electrical life depends on breaking current.
- Risoluzione dei problemi
Coil energized but no pull-in: Misurare la tensione della bobina, check coil open circuit or mechanical jamming
Pull-in but no continuity on main circuit: Loose busbar or burned main contacts
Chiacchiere / rumore anomalo: Bassa tensione della bobina, accumulated dust on iron core, stanchezza primaverile
- Customs HS Code
85364900 (Electromagnetic contactor)
- Optional Spare Parts & Accessori
Relè termico: 3RU2156 series (for 90kW motor)
Soppressore di sovratensioni: 3RT1955-1CD00 (Circuito RC), 3RT1955-1DG00 (Varistor)
Blocco contatti ausiliari: 3RH1951 (for extra auxiliary contacts)
Arc shield & main contact repair kit: 3RT1956 contact assembly
Tabella comparativa: SIEMENS 3RT1056-6AP36 VS 3RT5056-6AP36
Both models feature identical electrical parameters, mounting dimensions and compatible accessories for direct replacement. The core differences lie in origin, nameplate marking, lead time and applicable certifications.
| Elemento di confronto | 3RT1056-6AP36 (Imported Version) | 3RT5056-6AP36 (Versione domestica) |
| Linea di prodotti | SIRIUS 3RT1, global standard imported version | SIRIUS 3RT5, local domestic version |
| Origine | Amberg Factory, Germania | SIEMENS low voltage plant in China (SEAL) |
| AC-3 @400V | 185UN / 90kW | 185UN / 90kW |
| AC-1 Resistive Load | 215UN | 215UN |
| Specifiche della bobina | 220~240 V CA/CC | 220~240 V CA/CC |
| Contatti ausiliari | 2NO+2NC, terminali a vite | 2NO+2NC, terminali a vite |
| Collegamento al circuito principale | Sbarra collettrice | Sbarra collettrice |
| Dimensioni del telaio | S6 | S6 |
| Dimensione complessiva / Fori di montaggio | Identico, intercambiabile direttamente | Identico, intercambiabile direttamente |
| Vita meccanica | 10 milioni di operazioni | 10 milioni di operazioni |
| AC-3 Electrical Life | Stesso (depends on breaking current) | Stesso (depends on breaking current) |
| Ambient Temperature Range | -25℃ ~ +60 ℃ | -25℃ ~ +60 ℃ |
| Accessori compatibili | Full compatibility: 3RU thermal relay, 3RT19 surge suppressor, contact repair kit, auxiliary contact block | 100% compatible with accessories of 3RT1056 |
| Certificazioni | CCC, CE, UL, CSA, suitable for overseas projects | CCC, CE; UL optional for certain batches, standard for domestic projects |
| Nameplate | tedesco + English marking, Prodotto in Germania | cinese + English marking, made in China |
| Tempi di consegna | Long, mostly forward order with unstable lead time | Corto, domestic stock available with fast delivery |
| Prezzo | Higher | Lower with cost advantage |
| Scenari applicativi | Attrezzature per l'esportazione, overseas projects, high-end foreign-invested projects, cases requiring imported components | Domestic control cabinets, pompe dell'acqua & tifosi, HVAC, general industrial automation |
| Prestazioni elettriche | Identico, no derating difference | Identico, no derating difference |
| Codice SA | 85364900 | 85364900 |
| Model Naming Definition | 3RT10: Global original series | 3RT50: Domestic localized series |
Note chiave
- Intercambiabilità: SIEMENS officially approves direct replacement. No modification required for cabinet cutout, sbarra collettrice, secondary control loop or thermal relay selection. Electrical characteristic curve, temperature rise and contact breaking capacity are identical.
- Guida alla selezione
✅ Choose 3RT5056: Domestic projects, budget control, consegna veloce; preferred for most domestic panel building projects.
✅ Choose 3RT1056: Export machinery, overseas site, specification explicitly requiring German origin, mandatory UL/CSA certification.
- Misconception Clarification: It is NOT a downgraded domestic variant. Same product platform and design, manufactured at different factories under identical design and test standards.
Supplementare: Shared Spare Parts List
Relè termico: 3RU2156 series
Soppressore di sovratensioni: 3RT1955-1CD00 / 3RT1955-1DG00
Main contact repair kit: 3RT1956
Additional auxiliary contact block: 3RH1951
Application Scenarios for 3RT1056-6AP36 and 3RT5056-6AP36
Identical load capacity for both models, rated for 400V, 90kW 3-phase motor direct-on-line start (AC-3, 185UN). Differences are only based on project location, certification requirements and client procurement specification, NOT load capacity.
- Common Applications (Both Models Applicable)
(1) Direct-on-line Motor Starting (Main AC-3 Duty)
Pompe dell'acqua, pompe per fognature, circulating pumps (trattamento dell'acqua, HVAC, edificio, industria chimica)
Compressori d'aria, grandi tifosi, aspiratori fumi
Trasportatori, miscelatori, estrusori, frantoi (cibo, building material, minerario)
Chillers and large refrigeration compressors for central air conditioning
MCC motor control centre drawer units for 90kW motor circuits
(2) AC-1 Resistive Load
High-power heating elements, forni a resistenza
Main circuit switching of high-power circuits inside distribution cabinets
(3) AC-6B Capacitor Switching
Capacitor bank switching for reactive power compensation cabinet (reactor required to suppress inrush current)
Corrispondenza: 3RU thermal relay for motor overload protection; 2NO+2NC auxiliary contacts for PLC running feedback and fault interlock.
- Preferred Scenarios for 3RT5056-6AP36 (Domestic Local Version)
- Domestic panel projects, domestic factories, HVAC, fornitura d'acqua & drenaggio, general factory automation
Complete CCC certification for domestic projects, sufficient stock and cost advantage, preferred by most EPC and cabinet manufacturers.
- Domestic municipal projects: Impianti di trattamento delle acque reflue, municipal pump stations, building HVAC cabinets
- Domestic machinery OEM: Tifosi, compressori d'aria, chiller units sold in domestic market
- Ordinary motor circuits in domestic power plants, metallurgy and chemical plants (no mandatory imported component requirement by client)
- Retrofit replacement for old contactors, tight budget and fast delivery required
✅ Suitable for: Domestic projects without mandatory UL/CSA certification or German origin requirement
- Preferred Scenarios for 3RT1056-6AP36 (German Imported Version)
- Export machinery & equipment (export to Southeast Asia, Middle East, Europe and other overseas sites)
Full set of international certifications CE, UL, CSA to meet overseas owner and customs requirements.
- New construction projects of foreign-invested factories where technical specification explicitly requires SIEMENS components made in Germany
- Overseas EPC projects, control cabinets exported together with equipment, certificate of origin required
- High-end pharmaceutical and semiconductor foreign projects where imported components are specified by client
- Sostituzione di pezzi di ricambio per apparecchiature legacy: Original unit fitted with 3RT1056 and client requires identical OEM spare parts
✅ Suitable for: Export machinery, overseas projects, client specified imported components, mandatory UL/CSA certification
- Evitare le trappole della selezione
- Identical load rating: Both can drive 90kW motors. 3RT5056 has no limitation for heavy-duty applications; only differs in origin and certification documents.
- For domestic projects without “imported contactor” clause in specification, 3RT5056 is preferred for shorter lead time and better price.
- For export to Europe / America del Nord, select 3RT1056 and confirm in advance whether UL/CSA certificates are required.
- Heavy vibration & dusty heavy industry environments (minerario, cement plant): Both have identical mechanical life. Installation and heat dissipation requirements are the same; selection only depends on origin requirement.
- Scenari non applicabili
Direct-on-line starting for motor power exceeding 90kW; soft starter recommended for higher power.
Frequent jogging, frequent forward/reverse AC-4 duty (accelerated contact wear, derating evaluation required)
Safety circuits and emergency stop safety functions (SIEMENS safety contactor 3RT2 series should be adopted)
Contattore,interruttore automatico,sensore,Codificatore,PLC,Convertitore


















NH42-63-318x560.png)