Schneider A9DA2616 (Acti9 iDD40T 1P+N C16 30mA AC) Interruttore automatico a corrente residua con protezione da sovracorrente (RCBO)
- Interpretazione del modello
A9DA2616 = Acti9 Series iDD40T Product Type 1P+N Pole Configuration C-type Tripping Curve 16A Rated Current 30mA Residual Current AC-type Residual Current Detection
- Parametri tecnici fondamentali (Compliant with IEC 61009-1/GB 16917.1)
| Parametro | Specifica |
| Tipo di prodotto | Residual Current Operated Circuit Breaker with Overcurrent Protection (RCBO, integrating three protections: sovraccarico, cortocircuito, e corrente residua) |
| Configurazione del palo | 1P+N (1 Pole + Neutro, phase line breaks, neutral line remains conducting permanently) |
| Corrente nominale (In) | 16UN |
| Curva di intervento | Tipo C (intervento istantaneo a 5~10 In), adatto per l'illuminazione, PRESA, e carichi generali del motore |
| Corrente operativa residua nominale (IΔn) | 30mA (personal safety protection level) |
| Residual Current Type | AC-type (detects sinusoidal AC leakage current, suitable for conventional environments) |
| Tensione nominale (Ue) | 230V e (1P+N), 50/60Hz |
| Potere di interruzione in cortocircuito (Inc) | 6IL (400V) / 4500UN (230V) |
| Rated Residual Operating Time (at IΔn) | ≤0,3 s |
| Vita utile meccanica | 10,000 operazioni |
| Vita utile elettrica | 5,000 operazioni |
| Metodo di montaggio | 35Guida DIN da mm (18larghezza mm) |
| Specifiche di cablaggio | Solid wire: 1~25mm²; Flexible wire: 1~16mm² (with cable lugs) |
| Coppia terminale | 2.0 N·m |
| Temperatura operativa | -25℃ ~ +70 ℃ |
| Classe di protezione | IP20 (for use inside distribution boxes) |
| Tensione nominale di resistenza all'impulso (Ump) | 4kV |
- Funzioni & Applicazioni
Funzioni principali
Protezione da sovraccarico: Realizes inverse-time protection via the thermal bending of bimetallic strips.
Protezione da cortocircuito: Achieves instantaneous protection through electromagnetic release.
Protezione corrente residua: Rapidly trips within ≤0.3s when detected residual current exceeds 30mA, preventing electric shock accidents.
Scenari applicativi tipici
- Branch circuit protection for residential/commercial buildings (per esempio., lighting and socket circuits)
- Electrical safety protection for crowded places such as offices and shops
- Power supply protection for small household appliances and office equipment
- Replacement for traditional MCB + RCCB combinations, risparmio di spazio nella scatola di distribuzione
Suggerimenti per la selezione
AC-type is suitable for pure AC load environments, such as traditional lighting and resistive loads.
For loads containing DC components (per esempio., switching power supplies, LED lighting), A-type or B-type residual current circuit breakers are recommended.
30mA is the standard value for personal safety protection and shall not be used for equipment protection (300mA is usually selected for equipment protection).
- Installazione & Punti chiave della manutenzione
- Specifiche di cablaggio: Dall'alto verso il basso (bidirectional wiring with bottom-in top-out supported). Connect phase line to L pole and neutral line to N pole; il collegamento inverso è severamente vietato.
- Residual Current Test: Dopo l'installazione, premere il pulsante di prova (T button) to confirm the normal operation of the residual current protection function.
- Ispezione regolare: Press the test button once a quarter to verify the effectiveness of the residual current protection function.
- Gestione dei guasti:
Overload/Short-circuit Tripping: Troubleshoot load or line faults before closing the breaker directly.
Residual Current Tripping: First disconnect all loads, check for leakage points one by one, and close the breaker only after repairs; forced closing with faults is strictly prohibited.
- Spacing Requirement: Maintain a gap of ≥3mm from adjacent components to ensure heat dissipation and wiring space.
- Corresponding Chint Product & Confronto di sostituzione
Chint Equivalent Model: NXBLE-63 1P+N C16 30mA AC
| Categoria dei parametri | Schneider A9DA2616 | Chint NXBLE-63 1P+N C16 30mA | Compatibilità di sostituzione |
| Core Protection | Sovraccarico + Cortocircuito + Corrente residua (RCBO) | Sovraccarico + Cortocircuito + Corrente residua (RCBO) | ✅ Fully Matched |
| Pole Configuration/Tripping Curve/In | 1P+N/C-type/16A | 1P+N/C-type/16A | ✅ Fully Matched |
| IΔn/IΔ Type | 30mA/AC | 30mA/AC | ✅ Fully Matched |
| Capacità di interruzione | 6IL | 6IL | ✅ Fully Matched |
| Dimensioni di installazione | 18mm (larghezza) × 91mm (altezza) × 65 mm (profondità) | 18mm (larghezza) × 91mm (altezza) × 65 mm (profondità) | ✅ Identical Dimensions |
| Specifiche di cablaggio | Solid wire: 1~25mm² | Solid wire: 10~16mm² | ⚠️ Schneider Terminals Have Larger Capacity |
| Temperatura operativa | -25℃ ~ +70 ℃ | -30℃ ~ +70 ℃ | ✅ Chint Has Better Low-temperature Adaptability |
| Funzioni aggiuntive | VisiTrip Fault Indication | Red-Green Window Indication (Red for Closed, Green for Open) | ⚠️ Different Indication Methods |
| Periodo di garanzia | 24 Mesi | 18 Mesi | ⚠️ Differenza di garanzia |
Precauzioni per la sostituzione delle chiavi
- ✅ Installation Compatibility: Entrambi sono montati su guide DIN da 35 mm con larghezza 18 mm, enabling direct interchange.
- ✅ Protection Characteristics: C-type curve, 16Una corrente nominale, and 30mA residual current protection are fully consistent; no load adjustment is required.
- ⚠️ Wiring Adaptation: Schneider terminals support larger wire diameters; keep the original wire diameter during replacement to avoid loose connections.
- ⚠️ Function Identification: The VisiTrip indication window of Schneider shows red after tripping; it is necessary to train operators to recognize the new marks.
- Riepilogo & Raccomandazioni per la selezione
Schneider A9DA2616 is a 1P+N 16A RCBO in the Acti9 series iDD40T product line. It integrates triple protection functions and is suitable for personal safety protection in conventional environments.
Raccomandazioni per la selezione:
For international brand reputation and reliable performance: Choose Schneider A9DA2616, che fornisce un'indicazione di guasto più completa e funzioni di cablaggio bidirezionale.
For cost-effectiveness: Choose Chint NXBLE-63 1P+N C16 30mA, which features more favorable pricing and performance meeting national standards.
For special environments (per esempio., low temperature < -25℃): Prioritize Chint products for their better low-temperature adaptability.
Contattore,interruttore automatico,inverter solare,contatore elettrico,batterie solari