The ACS580-01-087A-4 is a standard wall-mounted single drive unit から ABB’s ACS580 series, rated for three-phase 380–480V AC input. This drive series features user-friendly operation, high reliability and superior energy efficiency as core advantages. Multiple standard built-in functions eliminate the need for extra optional components, enabling rapid commissioning and deployment. Widely compatible with general industrial loads such as pumps, ファン, conveyors and mixers, it is the preferred solution for light industry, 建物の空調設備, water treatment and other applications.
Breakdown of Model Code
Per ABB official naming convention, each segment of the model designation is defined as follows:
ACS580: 製品シリーズ識別子, representing ABB’s general-purpose standard drive series covering power ratings from 0.75kW to 500kW
-01: Construction type, standing for wall-mounted standard single drive. Standard equipment includes IP21 enclosure rating, Assistant Control Panel, built-in Class C2 EMC filter, 安全トルクオフ (STO), braking chopper and triple-protection coated circuit boards
-087あ: Rated output current marking, indicating the nominal rated output current of the drive is 87A
-4: 電圧クラス, denoting three-phase 380V–480V AC input, compatible with 50/60Hz mains power grids
主要な技術仕様
Electrical Ratings
| パラメータ | 仕様 | 備考 |
| 入力電圧範囲 | 3-phase AC 380V ~ 480V | 許容範囲: +10% / -15% |
| Input Frequency | 50/60Hz | 許容範囲: ±5% |
| 定格出力電流 | 87あ | Nominal value for light-duty applications |
| 適合したモーター出力 (Light Duty) | 45kW | 可変トルク負荷用 (ファン, ウォーターポンプ) |
| 適合したモーター出力 (ヘビーデューティ) | 37kW | For constant-torque loads (運ぶ, mixing) |
| Output Frequency Range | 0 ~ 500Hz | Supports high-speed motor operation |
| Input Power Factor | ≥0.98 | High power factor across full power range |
| Overall Efficiency | ≥98% | At rated operating conditions |
| 過負荷容量 | 150% rated current for 60s | One overload cycle permitted every 10 分 |
| 110% rated current continuously |
コントロール & インターフェース仕様
Motor Control Modes: Scalar V/F control, センサレスベクトル制御; compatible with induction motors, permanent magnet synchronous motors and synchronous reluctance motors
物理的寸法 & Environmental Specifications
フレームサイズ: R5
全体の寸法 (H × W × D): 896mm × 345mm × 293mm
正味重量: 約. 23kg
Enclosure Rating: IP21 (標準); IP55 high-protection version available as option
取付タイプ: 壁取り付け, side-by-side compact installation supported
動作周囲温度: -15℃ ~ +50℃ (40℃以上ではディレーティングが必要)
ストレージ & Transport Temperature: -40℃~+70℃
相対湿度: 5% ~ 95%, 結露しないこと
Altitude Rating: Full power output up to 1000m; 1% power derating per additional 100m above 1000m
HSコード: 85044088
標準構成 & オプションのアクセサリ
Factory Standard Equipment
- ACS-AP-S Assistant Control Panel (Chinese language supported)
- Built-in Class C2 EMC Filter
- Integrated Braking Chopper
- 安全トルクオフ (STO) 関数
- Triple-protection Coated Printed Circuit Boards
- Bottom Cable Entry Compartment
- Multilingual Quick Installation & Commissioning Manual
Common Optional Accessories
Enclosure Upgrade: IP55 protective enclosure, flange mounting kit
Communication Extensions: Fieldbus adapters including Profibus DP, Profinet IO, イーサネット/IP, Modbus TCP
Electrical Options: Input reactors, output reactors, du/dt filters, sine-wave filters, braking resistors
Functional Extensions: I/O expansion modules, temperature sensor interface cards, NETA-21 remote monitoring module
Software Tools: Drive Composer professional commissioning software
典型的なアプリケーションシナリオ
水処理産業: Clean water pumps, sewage pumps, aeration fans, sludge mixers
建物の空調設備: Chilled water pumps, cooling water pumps, supply & exhaust fans for central air conditioning
Light Manufacturing: ベルトコンベア, packaging production lines, mixing & blending equipment, エアコンプレッサー
冶金 & マイニング: Dust extraction fans, material transport belts, mine drainage pumps
Municipal Engineering: Water supply pumping stations, ventilation systems for wastewater treatment plants
Common Troubleshooting Matrix
| 故障現象 | Root Causes | Step-by-Step Remedial Actions |
| Overcurrent Trip (故障コード 0001) | Short circuit in motor/cables, sudden load surge, overly short acceleration time | 1. Cut power and test insulation & wiring of motor and power cables |
| 2. Appropriately extend acceleration time parameter | ||
| 3. Verify consistency between motor rated parameters and drive settings | ||
| DC Overvoltage Trip (故障コード 0002) | Excessively high mains voltage, overly short deceleration time, faulty braking circuit | 1. Measure input mains voltage to confirm it falls within allowable range |
| 2. Extend deceleration time or enable DC braking function | ||
| 3. Check wiring and resistance value of braking resistor for matching | ||
| 不足電圧トリップ (故障コード 0003) | Single-phase power loss, blown input fuses, excessively low mains voltage | 1. Inspect three-phase input power to eliminate phase loss issues |
| 2. Check status of input fuses / サーキットブレーカー | ||
| 3. Confirm on-site mains voltage meets equipment requirements | ||
| Motor Overload Alarm (故障コード 0005) | Jammed mechanical load, incorrect motor parameters, sustained overload operation | 1. Cut power and rotate motor shaft manually to check mechanical smoothness |
| 2. Re-run motor identification auto-tune | ||
| 3. Evaluate actual load conditions and upsize drive model if necessary | ||
| Overheating Fault (故障コード 0009) | 周囲温度が高すぎる, blocked cooling air ducts, faulty cooling fan | 1. Clear dust buildup on drive air intake cooling grille |
| 2. Verify normal operation of cooling fan | ||
| 3. Improve cabinet ventilation and lower ambient temperature |
Detailed List of Standard Accessories for ABB ACS580-01-087A-4 (Frame R5 / IP21 Version)
This model is a standard wall-mounted unit of ACS580 Frame R5. Factory supply contents are split into built-in onboard functions and physical accessories supplied in carton. Below is a detailed breakdown of the official standard supply scope:
- Standard Built-in Onboard Functions (統合された, No Extra Fitting Required)
All functions below are factory pre-configured and ready for direct use without purchasing extra options:
- EMC Components: Built-in Class C2 EMC filter to meet industrial site electromagnetic compatibility requirements
- Braking Circuit: Integrated braking chopper allowing direct connection of braking resistors for fast deceleration
- 安全機能: 安全トルクオフ (STO) compliant with PL e / シル 3 安全レベル
- 環境保護: Full triple-protection coating on control and power boards, resistant to humid, dusty and corrosive gas environments
- Standard Control Interfaces: 6 デジタル入力, 2 デジタル出力, 2 アナログ入力, 1 アナログ出力
- Basic Communications: Embedded RS-485 hardware port with native Modbus RTU protocol support
- 構造設計: Bottom cable entry compartment supporting standardized wiring and cable ingress protection
- Physical Standard Carton Accessories (Separately Packed Inside Shipment Box)
Independent accessories available upon unpacking for installation and basic commissioning:
- ACS-AP-S Assistant Control Panel (Chinese version): Equipped with LCD screen and full-function keys for parameter setup, status monitoring and fault diagnosis; pluggable onto drive front panel and supplied in separate packaging
- Wall Mounting Template: 1:1 paper drilling positioning template for marking mounting hole positions on-site to reduce drilling errors
- Cable Junction Box Assembly: Standard for Frame R5 IP21 units, including power cable grounding brackets, control cable shielding clamps and assembly fasteners
- Mounting Fastener Kit: M6 bolts, nuts and other metal hardware for wall mounting fixation
- Ground Terminals & Cable Crimp Accessories: Dedicated main circuit grounding terminals and auxiliary crimp fittings for control terminals
Ⅲ. Supplied Documentation & Identification Labels
- Quick Installation and Startup Guide: Multilingual edition (中国人も含めて) covering full procedures of wiring, power-up and basic commissioning
- Safety Warning Stickers: Multilingual residual voltage warning labels to be affixed near equipment to alert maintenance personnel
- Product Certificate of Conformity and Warranty Document
注記: Full hardware manuals and firmware parameter manuals are not supplied as standard; downloadable via ABB official website or available as separate printed copies upon order.
- Packaging Auxiliary Protection Materials
Standard industrial shipping packaging for logistics protection, not classified as drive accessories:
VCI vapor corrosion inhibitor anti-rust bag
Paper buffer liners and corner protectors
Strapping bands
Shipping pallet (for full carton industrial packaging specifications)
- Non-Standard Optional Components Requiring Separate Ordering
Items below are excluded from standard supply scope and must be purchased separately per project demands:
Enclosure Upgrade: IP55 protective enclosure, flange mounting kit
Communication Extensions: Fieldbus adapters including Profibus DP, Profinet IO, イーサネット/IP, Modbus TCP
Electrical Matching Components: Input reactors, output reactors, du/dt filters, sine-wave filters, braking resistors
Functional Extensions: I/O expansion modules, encoder interface cards, temperature sensor interface cards, remote monitoring modules
Software Tools: Drive Composer professional commissioning software, USB commissioning cable
コンタクタ,サーキットブレーカー,ソーラーインバーター,電気メーター,太陽電池