ABB ACS880-01-246A-4 Variable Frequency Drive

The ACS880-01 series is ABB’s flagship wall-mounted industrial single-drive variable frequency drive. Equipped with self-developed DTC Direct Torque Control technology, it supports multiple motor types including asynchronous motors, permanent magnet synchronous motors and synchronous reluctance motors. Integrated with safety, communication and energy efficiency management functions, it serves as the standard drive solution for general industrial ...

  • 製品詳細

The ACS880-01 series is ABB’s flagship wall-mounted industrial single-drive variable frequency drive. Equipped with self-developed DTC Direct Torque Control technology, it supports multiple motor types including asynchronous motors, permanent magnet synchronous motors and synchronous reluctance motors. Integrated with safety, communication and energy efficiency management functions, it serves as the standard drive solution for general industrial and process industries.

  1. Breakdown of Model Code

`ACS880-01-246A-4`

  1. ACS880: All-compatible industrial single-drive VFD series with standard DTC Direct Torque Control, power coverage ranging from 0.55 キロワットから 3200 kW across the full lineup.
  2. -01: Wall-mounted single drive module design, available for direct wall mounting or cabinet installation with a compact single-drive form factor.
  3. 246あ: Rated continuous output current of the VFD, 246 あ, the core reference parameter for motor matching and overload protection.
  4. -4: Voltage class identifier, nominally designed for 480 V three-phase power grids, supporting wide input voltage from 380 V to 500 V for various power supply scenarios at home and overseas.
  5. Core Electrical Technical Specifications
  6. Power and Current Ratings
パラメータ項目価値備考
Rated Power for Constant Torque (CT / ヘビーデューティ)132 kW (400 V grid) / 160 kW (480 V grid)For continuous heavy-duty loads such as conveyors and mixers
Rated Power for Variable Torque (VT / Light Duty)160 kW (400 V grid) / 200 kW (480 V grid)For square-torque loads such as fans and water pumps
Rated Continuous Output Current246 あNominal value under 40 °C ambient temperature
過負荷容量110% 定格電流 60 s / 150% 定格電流 10 sOne overload cycle lasts 5 分
Input Power Supply3-phase 380~500 V AC ±10%, 50/60 Hz ±5%Wide voltage design compatible with domestic and overseas power grids
Output Frequency Range0 ~ 598 HzSupports high-speed special motor applications
Fundamental Power Factor0.98Low harmonic interference to the grid and low reactive power loss
Nominal Overall Efficiency≥98%Complies with high-efficiency drive standards to reduce operating energy consumption
  1. 制御性能

制御モード: DTC ダイレクトトルク制御, V/f Scalar Control, センサーレスベクトル制御

Torque Step Response: <5 ms in open-loop mode with minor speed fluctuation under load disturbance

Speed Control Accuracy: ±10% rated slip (open-loop); ±0.01% rated speed (closed-loop)

Compatible Motor Types: Asynchronous Induction Motors, Permanent Magnet Synchronous Motors, Synchronous Reluctance Motors, High-Speed Motors

Ⅲ. Mechanical and Hardware Specifications

アイテムパラメータ値
フレームサイズR8
Standard Protection ClassIP20 (standard for cabinet installation)
Optional Protection ClassesIP21 (with cable entry box), IP55 (standalone cabinet type)
全体の寸法 (IP21 with Cable Entry Box)H 963 mm × W 681 mm × D 386 mm
正味重量58.6 kg (IP21 version)
冷却方法Forced air cooling with intelligent temperature-controlled variable-speed fan for low-noise operation
動作周囲温度-10 ℃~ +50 ℃; derating required above 50 ℃, maximum withstand temperature +60 ℃
Maximum Installation Altitude≤4000 m; 1% current derating per 100 メートル上 1000 メートル
設置方法Vertical wall mounting, side-by-side installation without gaps allowed
  1. Standard Built-in Functions
  2. 安全機能: Standard STO Safe Torque Off function with SIL 3 / PL e safety level, no additional safety relays required.
  3. Hardware Integration: Built-in Class C3 EMC filter, DC reactor and braking chopper, greatly reducing procurement and wiring work for peripheral accessories.
  4. ストレージ & 試運転: Removable STC storage unit for one-click migration of parameters and programs; standard multi-language assistant control panel with Chinese language support.
  5. Basic I/O Interfaces: 6 デジタル入力 (から), 3 デジタル出力 (する), 2 アナログ入力 (AI), 2 Analog Outputs (へ), reserved expansion interface for encoders.
  6. Communication Capability: Built-in Modbus RTU protocol and embedded web server, supporting remote monitoring and parameter configuration over local area networks.
  7. Energy Efficiency Management: Built-in energy optimizer and energy consumption statistics, supporting sleep/wake-up and automatic energy-saving operation modes.
  8. Comprehensive Protection Mechanisms: Complete protection against overcurrent, 過電圧, 不足電圧, 過負荷, 過熱, 地絡, 短絡, モーター欠相, 等.
  9. Comparison of Adjacent Models with the Same Voltage Class (-4 シリーズ)
フルモデル定格出力電流CT Rated Power (480 V)VT Rated Power (480 V)フレームサイズ
ACS880-01-206A-4206 あ110 kW132 kWR7
ACS880-01-246A-4246 あ132 kW160 kWR8
ACS880-01-293A-4293 あ160 kW200 kWR8
  1. Core Selection Differences Between Suffix -3 そして -4

Voltage suffixes must be distinguished carefully for domestic project selection to avoid mismatching motors and power grids:

比較項目ACS880-01-246A-3ACS880-01-246A-4
入力電圧範囲380~415 V AC380~500 V AC
Nominal Applicable GridStandard domestic 380 V industrial power gridOverseas 480 V power grids, foreign-owned production lines
Rated Voltage of Applicable Motors標準 380 V domestic motors400/460/480 V imported / export-oriented motors
CT Power at 400 V132 kW132 kW
Full-Load Operation at 480 VNot supported for long-term full-load runningSupports full-load operation of 160 kW-class motors
典型的なアプリケーションシナリオDomestic general industry, 都市工学, 冶金, 水処理Supporting export complete equipment, overseas engineering projects, ship supporting systems

> 選択のヒント: Prioritize models with suffix -3 for standard domestic 380 V grids; サフィックス -4 is mandatory for export equipment and 480 V power supply scenarios.

Ⅶ. 典型的なアプリケーションシナリオ

General Machinery: ベルトコンベア, screw feeders, ミキサー, 破砕機, overhead travelling cranes

Fluid Equipment: Centrifugal fans, axial fans, centrifugal water pumps, 真空ポンプ, スクリューコンプレッサー

プロセス産業: Chemical reaction kettles, metallurgical roller tables, 鉱山ホイスト, municipal water treatment, food packaging lines

特別なシナリオ: Export complete sets of equipment, production line renovation for overseas factories, mine and ship projects with 480 V power supply

VIII. Common Fault Troubleshooting Matrix

故障コード故障現象根本的な原因Step-by-Step Solutions
F0001Output Overcurrent TripShort circuit of motor/cable, sudden load change, excessively short acceleration time, mismatched motor parameters1. Disconnect power and test insulation resistance of motor and power cables; 2. Extend acceleration time parameter; 3. Verify Group 99 motor rated parameters
F0002DC Bus OvervoltageExcessively high grid voltage, excessively short deceleration time, disconnected or over-resistive braking resistor1. Measure three-phase input voltage; 2. 減速時間を延長する; 3. 配線を確認してください, resistance and power matching of braking resistor
F0011Motor Overload Warning / 旅行機械的負荷の固着, モーター欠相, low overload protection setting1. Rotate motor shaft manually to check mechanical jamming; 2. Verify balanced three-phase motor current; 3. Check overload protection threshold parameters
F0021DC Bus UndervoltageInput phase loss, ヒューズが切れた, loose input terminals, excessively low grid voltage1. Inspect three-phase input voltage and phase sequence; 2. Replace blown input fuses; 3. Tighten main circuit wiring terminals
F0030Heatsink OvertemperatureExceeded ambient temperature, blocked cooling air duct, faulty cooling fan1. Clean dust on VFD air intake and cooling fins; 2. Check fan operating status; 3. Lower ambient temperature or run with derated capacity
  1. Ordering and Accessories Description

The order number of the base unit shall comply with results from ABB official selection tools; suffix coding rules for all series accessories are universal.

Common accessory suffixes:

+D150: Upgrade to ACS-AP-W Bluetooth assistant control panel for wireless commissioning via mobile phones/tablets

+B056: Standard factory-matched braking resistor

+E202: Upgrade to Class C2 EMC filter for harsh electromagnetic environments

+K475: PCB conformal coated board for humid, dusty and corrosive harsh environments

+N5050: Built-in Profinet industrial Ethernet communication module

+L502: Incremental encoder interface module for high-precision closed-loop speed control

Full Packing List of Standard Factory Package for ABB ACS880-01-246A-4 (R8 Frame, IP21 Standard Unit)

  1. Core Main Unit (Fully Pre-Integrated from Factory)
  2. ACS880-01-246A-4 Wall-Mounted VFD Main Unit (R8 Frame, IP21)

Factory pre-installed standard internal hardware:

ZCU-12 Main Control Unit (equipped with standard I/O terminals, STO Safe Torque Off circuit, RS485 Modbus and USB commissioning port)

Built-in DC Choke (DCL, standard for R5~R9 frames to suppress harmonics)

Built-in braking chopper (standard for R8 frame, only external braking resistor required)

Conformal coated control board (all standard deliveries come with coated boards)

Complete main power circuit, cooling fans and power terminal copper busbars

Integrated dedicated IP21 cable entry box with separate compartments for main circuit and control cables

  1. ACS-AP-W Bluetooth Assistant Chinese Control Panel (標準, Detachable)

Supports Bluetooth connection with Drive Composer commissioning software, Chinese/English language switching, parameter setting and fault log viewing.

  1. Matching Installation Hardware Kit (Separate Small Packaging Bag)
  2. Wall-mount fixing bolts and expansion screws for wall installation
  3. Sealing cover for cable entry box, dustproof buckles, rubber cable sealing gaskets
  4. Insulated protective cover for main power terminals and protective cover for control terminals
  5. Lifting eye bolts (special for heavy-duty R6/R7/R8 frames for transportation and hoisting)
  6. Extension mounting buckles for control panel (for external panel mounting on cabinet doors if needed)

Ⅲ. Paper Documentation Package (Multi-Language Including Chinese)

  1. ACS880-01 Quick Installation and Startup Guide (Chinese Version)
  2. Multi-language safety warning manual (electrical safety, capacitor discharge, hoisting warnings)
  3. Overall dimension drawings and terminal wiring schematic diagrams
  4. Factory inspection certificate and product nameplate parameter sheet
  5. Brief instructions for optional expansion modules (fieldbus cards, encoder cards, I/O expansion cards)
  6. Electronic Documentation CD

Full files contained in the CD:

  1. Complete ACS880-01 hardware manual and firmware parameter manual (中国語 & English PDF)
  2. Drive Composer PC commissioning software installation package
  3. Supporting manuals and wiring drawings for all optional modules
  4. Fault code lookup document and motor parameter identification guide
  5. Protective Packaging Auxiliary Materials
  6. Reinforced factory hard carton, load-bearing wooden pallet at bottom (standard wooden pallet for heavy-duty R8 frames for forklift handling)
  7. Shockproof foam corner protectors and bottom buffer foam for the main unit
  8. Plastic moisture-proof dust wrapping film and binding straps

重要な注意事項: Optional Accessories Not Included in Standard Package (Separate Order Required)

  1. External braking resistors and braking units
  2. External EMC input/output filters
  3. Fieldbus adapters (FENA-01 プロフィネット, FPBA-01 プロフィバス, 等)
  4. FEN-xx encoder interface modules, I/O expansion modules
  5. IP55 protection enclosure kit (order code +B056)
  6. Extension cables for cabinet door-mounted control panels
  7. Input/output AC line reactors
  8. Special customized kits for marine certification, explosion-proof and low-temperature applications

Supplementary Remarks

  1. This list applies to base units with standard IP21 wall-mounted design without additional +Bxx/Cxx special options; if +Bxx/Cxx special options are added during ordering, corresponding accessory assemblies will be included in the package.
  2. R8 frame (including 246A-4) features a heavy main unit with a standard wooden pallet in factory packaging; small frames R1-R5 are supplied without wooden pallets.
  3. ACS-AP-W control panel is a mandatory factory standard accessory and will not be shipped separately. If the economical basic ACS-AP-S panel is required as replacement, specify it during ordering.

Official Overload Capacity Parameters of ACS880-01-246A-4 (標準動作条件: 40 °C Ambient Temperature, Altitude ≤1000 m)

The overload capacity of this model is divided into two operation modes based on load characteristics: Light Overload (Variable Torque VT) and Heavy Overload (Constant Torque CT). All overload cycles last 5 分, with a hardware-limited instantaneous maximum current ceiling. The marking `246A` represents the VFD’s rated output current; voltage suffixes such as -3/-4 do not alter overload current parameters, only the matching motor power.

動作モードBaseline Continuous CurrentOverload MultiplierTypical Matching Motor Power at 480 VTypical Load Scenarios
Rated Non-Overload246 あN/A160 kWGeneral loads with stable long-term operation
Light Overload (VT Mode)234 あ110%160 kWSquare-torque loads such as fans, centrifugal pumps and screw compressors with minor short-term overload
Heavy Overload (CT Mode)206 あ150%132 kWImpact constant-torque loads such as belt conveyors, ミキサー, crushers and hoisting mechanisms
Instant Startup PeakN/AN/AN/AMotor locked rotor during startup, short-term extreme impact conditions

Key Supplementary Explanations

  1. Hardware Current Limit Constraint: The peak output current of all operating scenarios is capped by IGBT hardware at maximum 350 あ; の 150% overload current of 309 A under heavy-duty mode is below this ceiling and fully deliverable.
  2. Derating Rules:

If ambient temperature exceeds 40 ℃, the rated output current is derated by 1% あたり 1 °C rise (max withstand temperature 60 ℃), with synchronous reduction of overload capacity.

If installation altitude exceeds 1000 メートル, the rated output current is derated by 1% あたり 100 m elevation gain.

  1. 保護メカニズム: When overload duration or current exceeds specifications, the VFD will trigger an overload warning first; sustained violation will lead to `F0011` motor overload trip, combined with heatsink overtemperature protection for dual safety coverage.
  2. モード切り替え: The two overload modes can be switched via parameter `22.02`. The selected mode must match actual load characteristics; prolonged operation beyond rated overload specifications accelerates aging of power components.

Full Cross-Brand Comparison Table for ABB ACS880-01-246A-4 (132 kW Heavy Duty / 246 活動)

Reference Unit: ACS880-01-246A-4

Core Reference Specifications: 380~500 V wide voltage, 132 kW CT heavy duty, heavy-duty rated current 206 あ, 150% 過負荷 60 s; 160 kW VT light duty, light-duty current 234 あ, 110% 過負荷 60 s; built-in DC reactor + EMCフィルター + braking chopper + STO safety function.

  1. High-End Foreign Brand Counterparts (Original Imported / Top European & American Brands, Direct Replacement for Heavy-Duty Applications)
ブランドフルモデルHeavy-Duty CT Rated CurrentHeavy-Duty PowerLight-Duty VT PowerCore Comparison Description
ABBACS880-01-246A-4206 あ132 kW160 kWReference unit with DTC direct drive, standard STO, built-in reactor, filter and braking unit
シーメンスSINAMICS G120C 6SL3210-1KE32-4UB1205 あ132 kW160 kWIntegrated compact unit with built-in STO, suitable for production lines/fans/pumps; cabinet-mounted G130 model 6SL3310-1GE32-6AA3 shares identical specifications
シュナイダーエレクトリックATV630D132N4202 あ132 kW160 kWHigh-performance process drive with built-in DC reactor and EMC filter, standard STO, ideal for water treatment and heavy industry
YaskawaGA800 CIPR-GA80B0260ABBA208 あ132 kW160 kWHigh-torque vector control with excellent permanent magnet motor compatibility, dedicated for hoisting and roller table applications
三菱電機FR-A840-03250-2-60234 あ132 kW160 kWA800 high-performance vector drive with built-in filter and multi-protocol communication, for compressors and mixing equipment
ロックウェル・オートメーションPowerFlex755 20G4ADN260AA0NNNNN260 あ132 kW160 kWMatched for automated production lines with native EtherNet/IP support, for heavy-duty impact loads
  1. Domestic High-End Industrial Counterparts (Domestic Replacement with Equivalent Performance & Lower Cost)
ブランドフルモデルHeavy-Duty CT Rated CurrentHeavy-Duty PowerLight-Duty VT PowerCore Comparison Description
革新MD880-132-4206 あ132 kW160 kWHigh-end domestic industrial drive benchmarked against ACS880, DTC-like torque control, 内蔵ブレーキユニット, optional STO
InvtCHV200-132-4205 あ132 kW160 kWHeavy-duty vector drive for mining, mixing and conveying equipment
Delta ElectronicsCH2000 132043A204 あ132 kW160 kWUniversal for permanent magnet and asynchronous motors, wide 380~480 V voltage range, 内蔵EMCフィルター
HervitV6-H-4T132G208 あ132 kW160 kWSpecial heavy-duty model for hoisting, wire drawing and mixing applications
  1. Key Replacement Selection Differences & リスク警告
  2. Critical Voltage Matching Notes

Reference ACS880-01-246A-4: 380~500 V wide voltage, dedicated for export and overseas 480 V equipment;

The equivalent current model for standard domestic 380 V applications is ACS880-01-246A-3 (380~415 V).

For replacement selection, all matching models must carry suffix 4 (400 V wide voltage); narrow-range 380 V models are forbidden.

  1. Built-in Hardware Differences (Key Points for Retrofit Replacement)
  2. Standard built-in configuration of ABB ACS880: DC reactor + Class C3 EMC filter + braking chopper + STO
  3. Siemens G120C and Schneider ATV630 come with standard STO, but DC reactors are mostly optional and must be purchased separately for replacement to avoid excessive harmonic distortion.
  4. Domestic MD880/CH2000 series feature built-in braking units, while DC reactors are optional for partial specifications.
  5. Core Overload Capacity Comparison (Mandatory for Heavy-Duty Applications)

ABB Reference: CT heavy-duty baseline current 206 あ, 150% 過負荷 (309 あ) sustainable for 60 s

All high-end counterpart models (G120C / ATV630 / GA800 / MD880) deliver equivalent overload performance with heavy-duty current ranging from 202 へ 208 あ

Economical ATV340 / G120XA lack the 150% heavy-duty profile and only support 110% light overload, leading to frequent tripping under impact loads.

  1. 取付寸法参考図

ACS880-01-246A-4 is R8 frame (963 × 681 × 386 mm, 58.6 kg).

Siemens G120C and Schneider ATV630 models of identical power have smaller footprints with no cabinet expansion required for retrofits; domestic MD880 dimensions are close to ABB, allowing shared mounting cutouts.

  1. Quick Selection Conclusion
  2. Heavy Industry / Mixing / 運ぶ / Hoisting (Constant Torque Heavy Duty): Prioritize Siemens G120C, Schneider ATV630 and Inovance MD880 for fully equivalent replacement in current rating, overload capacity and functions.
  3. Export Equipment / Overseas 480 V Power Supply: Must select wide-voltage models with suffix -4; narrow-range 380 V units are prohibited.
  4. ファン & パンプス (Light Duty Without Impact): Economical ATV340 and G120XA are available at lower cost.
  5. Demand for Original Same Platform, DTC Control and Factory Integrated Solution: Directly adopt the same series ACS880-01-246A-4.

前へ:

返信を残す

伝言を残す