MS116: Compact manual motor starter (モーター保護サーキットブレーカー, MMS) シリーズ. Standard version is inherently 3-pole (3P); no 1P/2P variants available for this model.
-16: Thermal trip adjustment range: 10~16 A
Original part number: 1SAM250000R1011
- Main Electrical Specifications
| アイテム | パラメータ |
| 極 | 3P (3-phase main circuit) |
| Thermal trip setting range | 10.0~16.0 A |
| Instantaneous short-circuit trip current IΔ | 80 あ (fixed electromagnetic trip) |
| 旅行クラス | 10あ (for standard motor starting) |
| Rated applicable motor power (400VAC-3) | マックス. 7.5 kW |
| 定格絶縁電圧Ui | 690 Vと |
| 定格使用電圧Ue | 690 Vと / 440 ワシントンDCで |
| 400V service breaking capacity Ics | 16 の |
| 取り付け | DIN35 rail mounting |
| 幅 | 45 mm (2.5 モジュール幅) |
| 端子 | ネジ端子, line-in top / load-out bottom L1/L2/L3 → T1/T2/T3 |
| Integrated functions | 過負荷保護, 短絡保護, phase-loss protection, アイソレーション機能, 温度補償, trip-free mechanism |
- 機能の説明
- ロータリノブの操作: 0 (オフ) — I (の上). Clear isolation position, can be used as an isolator.
- Protection principle
過負荷: Bimetallic thermal trip
短絡: Instantaneous electromagnetic tripping
位相損失: Tripping triggered by 3-phase unbalance
- 代表的な用途: Standalone 3-phase asynchronous motor protection for fans, パンプス, conveyors and packaging machinery.
- オプションのアクセサリ (common for MS116 series)
HKF1-11: 前面に取り付けられた補助接点 (1NO+1NC)
HKF1-02: Fault signal contact
不足電圧解除, シャントリリース, 3-phase busbar, lockable handle kit
- 選定ガイドライン
✅ Select when motor rated current falls within 10~16A
⚠️ Optimally set operating current near the middle of adjustment range; avoid continuous operation at the lower limit of 10A
⚠️ For motors with frequent heavy-duty start-up, calculate starting current; upgrade to MS132 series if necessary
🔁 In-platform upgrade alternative: MS132-16 (より高い遮断容量, expanded accessory compatibility); domestic alternatives: Schneider GV2ME16, CHINT NS2-25 (10~16A)
- 端子マーク
Top terminals: 1L1, 3L2, 5L3 (Power supply incoming)
下部端子: 2T1, 4T2, 6T3 (Motor load outgoing)
Typical Applications of ABB MS116-16 (3P, 10~16A)
Adjustable current range: 10~16A; suitable for 3-phase motors ≤7.5kW @400V. Combines overload, short-circuit and phase-loss protection in one unit, replacing separate circuit breaker + サーマル過負荷リレー. Designed for direct-on-line (DOL) motor circuits.
- General Industrial Applications
- ファン (3~7.5kW)
Workshop exhaust fans, dust extraction fans, centrifugal fans, oven circulating fans, 冷却塔ファン.
Operating feature: Light-load start, 安定した動作. Built-in phase-loss protection prevents motor burnout from single-phasing.
- パンプス (3~7.5kW)
Circulating pumps, cooling water pumps, 浄水ポンプ, small sewage pumps, chilled water circulation pumps for HVAC systems.
注記: Submersible pumps require level control; confirm motor current is within 10~16A before selection.
- Conveying Equipment
Light-duty belt conveyors, roller conveyors, slat conveyors, 小型エレベーター.
Suitable for light loads; NOT recommended for frequent forward/reverse impact loads. Upgrade to MS132 for heavy frequent start-stop duty.
- Drives for Packaging Machinery
Small carton sealers, conveyor drive motors, stretch wrapping machines, small mixing motors.
- 空調設備 & Building Services
- Condenser fans of central air conditioning units, AHU supply/return fans
- Underground car park ventilation fans, auxiliary smoke exhaust fans (excluding primary fire smoke exhaust fans; fire circuits require components complying with local fire codes)
- Small circulation pumps for heat exchange stations
- Plastics, 木工 & Food Light Industry
- Feeder motors & stirring motors for small extruders
- Spindle motors for wood sanders and small cutting machines
- Agitator pumps and conveyor motors for food production lines (乾燥した環境)
- 水処理 & 環境保護
- Small chemical dosing agitator motors
- Small aeration pumps, sludge screw conveyor motors
- Drive motors for small filtration equipment
⚠️ Not Recommended Application Scenarios (Selection Pitfalls)
- Motor rated current <10A or >16A (outside adjustment range)
- Heavy-duty high-inrush equipment (air compressor main motors, large crushers) with extreme starting current
- Motor circuits requiring star-delta starting or soft starters (MS116 only applies to direct-on-line starting)
- High-impact loads and frequent stall conditions
- Explosion hazardous areas (explosion-proof enclosure assembly required; unit itself has no Ex certification)
- Projects where specifications mandate separate circuit breaker + サーマル過負荷リレー (integrated MMS cannot be adopted)
✅ Standard Control Configuration
MS116-16 + ABB Contactor → Direct-On-Line motor starter circuit
オプションのアクセサリ:
HKF1-11 Auxiliary contact (running status feedback)
HKF1-02 Fault signalling contact (transmit overload/short-circuit trip signal to PLC)
Cross-Brand Equivalent Model List
ABB MS116-16 (3P|10~16A, rotary knob type Motor Protection Circuit Breaker)
Baseline specifications:
Adjustable current 10~16A|3P|Class 10A thermal-magnetic trip|built-in phase-loss protection|DIN rail mount|integrated MPCB/MMS
⚠️ Important note: MS116 adopts rotary knob operation. Schneider GV2ME, Delixi CDP6 base versions use push-button operation. Mounting dimensions are compatible and electrical functions are equivalent, but operating style differs. Confirm operation type according to project requirements.
- Imported Brand Direct Equivalents
| メーカー | モデル | Adjustment Range | 操作の種類 | Key Remarks |
| ABB (In-range Upgrade) | MS132-16 | 10~16A | ロータリノブ | Upgraded version of MS116, higher short-circuit breaking capacity, fully interchangeable accessories; preferred OEM replacement |
| シュナイダーエレクトリック | GV3P16 | 10~16A | ロータリノブ | Identical operation style, direct counterpart; TeSys GV3 series |
| シュナイダーエレクトリック | GV2ME20C | 13~18A | Push-button | Partial overlapping range; not recommended if 10A lower limit is required. GV2ME16C covers only 9~14A (mismatched range, cannot be used as direct replacement) |
| シーメンス | 3RV2021-4AA10 | 10~16A | ロータリノブ | 3RV2021 series, widely used imported alternative for industrial projects |
| EATON | PKZM0-16 | 10~16A | ロータリノブ | Moeller technology platform, common replacement for overseas machinery |
| Shihlin Electric | MR-32-16 | 10~16A | ロータリノブ | Taiwanese brand, popular for localisation of imported equipment |
- 国内代替品 (Cost-Effective Solutions)
| メーカー | モデル | Adjustment Range | 操作の種類 | 応用 |
| チント | NS2-25X 16 | 10~16A | ロータリノブ | Standard NS2-25 = push-button; suffix X = rotary version, matches MS operation style |
| デリキシ・エレクトリック | CDV2s-32/16 | 10~16A | ロータリノブ | New CDV2s rotary series; legacy CDP6-32 mainly push-button |
| ピープルエレクトリック | RMM1S-32/3P 16 | 10~16A | ロータリノブ | General domestic motor protection circuit breaker |
| ネーデル | NDM2-32M/3P16 | 10~16A | ロータリノブ | High-end domestic option for control cabinets |
- Critical Risks for Cross-Brand Replacement
- Current Range Hard Limit
MS116-16 = 10~16A
❌ Forbidden substitutions: GV2ME16C (9~14A), 3RV2021-1AA10 (6~10A). Mismatched upper/lower limits lead to ineffective motor protection.
- Operating Mechanism Difference
ロータリノブ: MS116, GV3P, 3RV2021, PKZM0
Push-button: GV2ME, base CDP6, base NS2-25
Standardised cabinet projects & export machinery often require consistent operation form.
- Instantaneous Short-Circuit Trip Threshold
ABB MS116 fixed instantaneous trip at 80A. Instantaneous thresholds vary between brands. Verify motor starting current for heavy-start loads to avoid nuisance tripping.
- Accessory Incompatibility
Auxiliary contacts and fault signalling contacts from different brands cannot be interchanged. When retrofitting equipment, PLC feedback circuits need matching new accessories.
- Shortlist for Direct Procurement
✅ Perfect imported rotary-knob equivalents: Siemens 3RV2021-4AA10 / EATON PKZM0-16 / Schneider GV3P16
✅ ABB factory upgrade option: MS132-16
✅ Cost-effective domestic rotary-knob models: CHINT NS2-25X-16 / Delixi CDV2s-32 (10~16A)