Fuji EA3AAC3P-32A Molded Case Circuit Breaker

EA33M-3P 32A / EA33AC (The EA33AC variant has no factory 32A rating). EA3AAC3P-32A is a handwritten abbreviation used on drawings & equipment lists. フルネーム: Fuji FUJI AUTO BREAKER EA33M 3P 32A Molded Case Circuit Breaker (MCCB) Model Code Explanation EA33: 30AF frame size (maximum rated current 32A for this frame) M: 標準タイプ, thermal-magnetic ...

  • 製品詳細

EA33M-3P 32A / EA33AC (The EA33AC variant has no factory 32A rating). EA3AAC3P-32A is a handwritten abbreviation used on drawings & equipment lists. フルネーム: 富士山 FUJI AUTO BREAKER EA33M 3P 32A 配線用遮断器 (MCCB)

  1. 型式コードの説明

EA33: 30AF frame size (maximum rated current 32A for this frame)

M: 標準タイプ, thermal-magnetic trip for power distribution protection

3P: 3-ポール, 三相

32あ: Rated operating current In = 32A

注記: EA33AC series maximum rating is only 30A; no genuine 32A version. The 32A variant official designation is EA33M 3P 32A.

  1. コアの電気仕様
アイテムパラメータ
モデルEA33M 3P 32A (corresponds to drawing abbreviation EA3AAC3P-32A)
3P, 三相3線式
Rated Current In32あ
定格絶縁電圧 UiAC415V
定格動作電圧UeAC220V / AC380/415V
Ultimate Breaking Capacity Icu2.5kA @ AC220V; 1.5kA @ AC415V (JIS Standard)
トリップユニット熱磁気トリップ (過負荷による長時間の遅延 + instantaneous trip for short circuit)
規格JIS C8201, IEC60947-2
起源Fuji Electric, 日本 (Older imported model)
  1. Important Information
  2. 製品の状態: 製造中止

The EA33 series is an older generation compact MCCB, production permanently terminated by Fuji.

Direct Replacement Model: BW32AAG-3P 32A, identical mounting dimensions and terminal layout, plug-and-play interchangeable.

  1. 物理的寸法 (幅×高さ×奥行き)

約. 75mm × 130mm × 60mm, front wired fixed type.

  1. 典型的なアプリケーションシナリオ

Three-phase power branch circuits inside small control cabinets, machine tool power circuits, ファン & water pump load feeders.

Not suitable for circuits with high prospective short-circuit current (maximum breaking capacity limited to 2.5kA).

  1. 調達 & 交換の推奨事項

Second-hand / surplus stock: EA33M-3P 32A (limited availability)

For new projects & equipment retrofitting: BW32AAG-3P 32A (Current production G-TWIN series by Fuji Electric)

Complete Installation Guide for Fuji EA33M 3P 32A (EA3AAC3P-32A)

Physical unit model: EA33M 3P 32A, drawing shorthand EA3AAC3P-32A. Legacy Fuji 30AF MCCB, standard front-wired fixed mounting; cannot directly clip onto 35mm DIN rail.

⚠️ Pre-Work Safety Requirements

  1. Isolate upstream power supply completely and verify zero voltage before any wiring & installation work;
  2. Work must be performed by qualified electricians;
  3. 設置環境: Avoid heavy dust, 水分, corrosive gas and direct sunlight. Ambient operating temperature range: -5℃~+40℃;
  4. Circuit breaker must be installed vertically (handle moves up and down). Horizontal or inverted mounting is prohibited, which will cause trip mechanism failure.

一部 1: Mechanical Mounting Procedure

  1. 切り取る & Mounting Dimensions EA33M 3P

全体の寸法: W75mm × H130mm × D60mm

Two bottom mounting holes: φ4.5mm, horizontal hole spacing 54mm; Fastened onto mounting plate with M4 screws.

❗ Critical Note: This model has no built-in DIN rail latch. Direct mounting on standard 35mm DIN rail is impossible. Special adapter bracket required for DIN rail mounting (rarely available on market).

  1. Mounting Operation
  2. Place MCCB flat against mounting plate and maintain vertical alignment;
  3. Tighten upper and lower M4 screws evenly. Do not over-tighten one side to prevent housing deformation;
  4. After fastening, toggle ON/OFF handle repeatedly to confirm smooth operation without jamming.

一部 2. Electrical Wiring Specification (Front Connection)

  1. 端子の定義 (Refer to unit marking)

Top Terminals: Line Side (電源入力) → Connect three-phase L1/L2/L3 supply

Bottom Terminals: Load Side (Power Output) → Connect motors & end equipment

✅ Standard Wiring: Supply from top, load at bottom

警告: Reverse wiring (power fed from bottom) is not recommended for this legacy model. Reverse power supply reduces short-circuit breaking capacity and introduces safety risks during faults.

  1. ケーブル仕様 & 締付トルク

Recommended cable size for 32A: 6mm² copper conductor. Use OT/UT cable lugs; bare stranded wires shall not be directly inserted into terminals.

Terminal screw size: M5

Recommended tightening torque: 2.0~2.5 N·m

Insufficient torque → overheating & burnt terminals; Excessive torque → thread stripping, cracked plastic base.

  1. 配線手順
  2. Control wire stripping length; exposed copper strands shall not extend beyond lugs or contact adjacent phases;
  3. Cable lugs must fully fit flat against terminal surface. Avoid cable lateral tension applying continuous mechanical load to terminals;
  4. Wire three phases sequentially and match phase sequence;
  5. Recheck torque on all terminal screws after wiring completion.

一部 3. Pre-Energizing Inspection Checklist

  1. Confirm handle positioned at OFF (開ける);
  2. Use multimeter to confirm no inter-phase short circuit and no phase-to-earth short circuit;
  3. Maintain sufficient clearances between phases; phase barriers shall be installed inside metal cabinets if necessary;
  4. Clear all metal shavings and loose wire scraps inside cabinet to prevent short circuit.

一部 4. 試運転 & Energizing

  1. Confirm no personnel working on load side before energizing upstream supply;
  2. Switch handle to ON position. Watch for abnormal noise, smoke or overheating;
  3. Run under load for 30 分. Check terminal temperature; no abnormal excessive temperature rise indicates acceptable installation.
  4. 過負荷 & short-circuit tests are only permitted in laboratory environment. Deliberate short-circuit testing on site is forbidden.

一部 5. Critical Prohibited Operations (Common Pitfalls)

  1. ❌ Forbid horizontal or inverted installation
  2. ❌ Forbid direct wiring with loose stranded wires without cable lugs
  3. ❌ Forbid long-term operation with reverse power feed (bottom input)
  4. ❌ Do not pull cables forcibly to apply mechanical stress to breaker terminals
  5. ❌ Do not install directly in environments with high humidity & condensation without protective enclosure
  6. ❗ This model is discontinued with limited spare parts. Replace with BW32AAG-3P32A for new installations (direct size-compatible exchange).

一部 6. Basic Troubleshooting During Commissioning

Instant tripping upon closing: Short-circuit fault on downstream circuit

Tripping after sustained loaded operation: Loose terminals causing heat or load overload

Handle cannot be closed: Internal mechanism seized; breaker damaged, do not strike or force operation

一般的な障害, 原因 & Solutions for Fuji EA33M 3P 32A MCCB

Equipment Note: EA33M is legacy Fuji 30AF thermal-magnetic MCCB. Long service life commonly leads to aging of mechanical latch and internal bimetallic strip; many faults originate from component deterioration.

故障 1: Difficult to close / Unable to latch, handle stuck at mid-position

Symptoms

Handle cannot be pushed fully to ON position and fails to stay latched; rebounds immediately after release.

Root Causes

  1. Trip-free mechanism triggered and not reset

つまずいた後, the breaker enters trip-free state. The handle must be firmly pushed fully down to the OFF limit position for reset before re-closing.

  1. Sustained short circuit or severe overload on downstream circuit triggering instantaneous magnetic trip immediately upon closing.
  2. Long-term aging: internal spring fatigue, latch wear, 機械的な妨害.
  3. Mounting tilt or excessive cabinet vibration causing mechanism misalignment (vertical mounting mandatory).

Troubleshooting Procedure

  1. Cut upstream power supply, push handle firmly all the way down to OFF limit for reset and attempt closing again;
  2. Disconnect all load cables on lower terminals, perform no-load closing test:

✅ Successfully closes without load → Fault exists in downstream wiring or equipment

❌ Still fails to close without load → MCCB internal damage, replace unit directly

  1. Verify vertical mounting; add vibration damping measures if cabinet suffers severe vibration.

故障 2: Spontaneous tripping after running for a period (Time-delayed tripping)

Symptoms

Starts normally, trips after tens of minutes to several hours of operation, no loud short-circuit bang.

Classification of Causes

  1. Overload tripping (thermal trip activation)

Continuous operating current near or exceeding 32A; undersized cables, aging motor stall, combined overload of multiple equipment.

  1. Loose terminals generate heat, heat transfers to internal bimetallic strip and triggers false thermal trip (Most frequent field failure!)

Loose M5 terminal screws due to insufficient torque & vibration → terminal overheating → internal heat conduction causes undesired tripping.

  1. MCCB aging: Fatigued bimetallic strip, shifted trip characteristic, trips falsely under mild temperature rise.
  2. キャビネットの換気が悪く、周囲温度が高すぎる.

是正措置

  1. Measure three-phase operating current with clamp meter to confirm if current exceeds 32A; reduce load or upgrade protection device if overloaded.
  2. Power off and retighten all terminals to specified torque (2.0~2.5 N·m); replace cable lugs if required.
  3. Improve cabinet cooling layout; avoid mounting multiple heat-generating components adjacent to each other.
  4. If frequent delayed tripping occurs under normal load current → breaker aging, replacement recommended.

故障 3: Instant tripping immediately after closing

Symptoms

Breaker trips instantly upon closing, cannot sustain load connection.

原因

  1. Phase-to-phase short circuit or phase-to-earth short circuit on load side (damaged cable insulation, モーター巻線の短絡)
  2. Earth fault on load equipment
  3. Internal inter-phase breakdown inside MCCB (permanent unit damage)

Troubleshooting Flow

  1. Disconnect all outgoing load cables, perform no-load closing test

Closes normally without load → Fault in downstream cable or motor; test insulation with megger

Still trips instantly without load → Internal breakdown of MCCB, discontinue use and replace immediately

故障 4: 過熱 & discolored connection terminals

Symptoms

Terminal temperature rises significantly during operation, cable insulation softens, terminal surface blackens.

原因

  1. Insufficient tightening torque leading to high contact resistance
  2. No cable lugs fitted, loose stranded wires create poor contact
  3. Continuous full-load operation with undersized conductors (Minimum 6mm² copper recommended for 32A)
  4. Oxidation and dust accumulation on terminals.

是正措置

  1. Isolate power supply, clean oxidation layer, install new OT cable lugs;
  2. Retighten terminals to specified torque;
  3. If terminals are severely burnt and plastic base deformed by heat: MCCB must be replaced, continued operation prohibited.

故障 5: 位相損失 / No output on one phase while handle remains closed

Symptoms

Handle shows closed position, voltage present on upper input terminal but no output on lower terminal for one phase.

原因

Each pole of EA33M has independent contacts. Long-term heating and arc erosion lead to contact separation or partial welding on single pole.

⚠️ Severe Hazard! Visibly closed breaker with open internal phase will easily burn out three-phase motors.

救済策

Power off and test continuity between upper and lower terminals for each phase. Replace breaker immediately if any phase fails continuity test; on-site repair is not feasible.

故障 6: Breaker fails to function after short-circuit event

Symptoms

Cannot be closed or runs continuously hot after tripping due to short circuit.

原因

High short-circuit current creates electric arc, permanently scorching main contacts and damaging internal trip mechanism.

重要な注意事項

EA33M has low breaking capacity (1.5kA @ AC415V). One high-magnitude short-circuit can permanently damage the unit.

✅ Solution: After clearing short-circuit fault, replace the breaker rather than continuing operation with damaged components.

Standard Field Troubleshooting Sequence

  1. Isolate power supply → Push handle fully down to OFF position for complete reset
  2. Disconnect all load cables, test breaker performance under no-load
  3. Locate fault source: Distinguish between downstream wiring/equipment fault and internal MCCB failure
  4. Damaged breakers cannot be repaired; direct replacement model: BW32AAG-3P 32A (Direct dimensional interchange)

Critical Operational Warnings

  1. EA33M series has been discontinued. Risk of component aging rises with service time; not recommended as primary protection for critical equipment.
  2. Reverse wiring (power fed from lower terminals) 推奨されません. It reduces short-circuit breaking capacity and increases failure risk.
  3. Do not strike or pry operating handle forcibly to attempt closing, which may permanently jam internal mechanism.