エレスタ SIR222P 強制ガイドセーフティリレー

ELESTA (ピルツ傘下のスイスのセーフティリレーブランド) SIR4 Power high-current PCB-mount safety relay SIR: SIR4 series safety relay with forcibly guided contacts 222: 接点構成: 2 通常開 (いいえ) + 2 通常閉 (ノースカロライナ州) (dual-pole double-throw safety structure) P: High-current version rated for 12A load (standard SIR222 is 10A) Standard stock coil specifications: SIR222P 24VDC ...

  • 製品詳細

ELESTA (Swiss safety relay brand under キノコ) SIR4 Power high-current PCB-mount safety relay

  1. SIR: SIR4 series safety relay with forcibly guided contacts
  2. 222: 接点構成: 2 通常開 (いいえ) + 2 通常閉 (ノースカロライナ州) (dual-pole double-throw safety structure)
  3. P: High-current version rated for 12A load (standard SIR222 is 10A)

Standard stock coil specifications:

SIR222P 24VDC (主流, part number H301164, coil resistance 760Ω)

SIR222P 12VDC (part number H301192)

Custom coil voltages available: 5/6/18/48/110VDC

Core Safety Certifications

IEC準拠 61810-3 Type A Forcibly Guided Contacts and EN50205 machinery safety standards. Applicable to machine tool and automated safety circuits to meet safety contact fault monitoring requirements.

  1. 機械的寸法 & 取り付け

Overall size: 46.4(L) × 16(W) × 30.7(H) mm

取り付け: Through-hole PCB soldering (14-pin footprint)

重さ: 約. 32g

ハウジング: Transparent green dustproof flame-retardant PC, allows visual inspection of coil and contact status

Standard through-hole pin pitch for PCB mounting; compatible with dedicated PCB sockets

  1. Coil Electrical Parameters (直流)
アイテムパラメータ値
Nominal pull-in coil power0.75W
Holding power consumption0.23W (low-power latching, low heat generation)
24VDC coil resistance760Ω ±10%
Pull-in voltage range70%定格電圧の ~110% (DC 16.8~26.4V)
ドロップアウト電圧≤10% Un
耐電圧 (coil to contacts)2500V AC for 1 分
Coil protectionBuilt-in freewheeling diode (prevents reverse breakdown of DC coils)
  1. Core Contact Electrical Ratings (2NO+2NC Safety Forced Linkage)

4.1 耐荷重 (High-Current Advantage of SIR222P)

Continuous rated current: 12あ / 250VAC (AC1 resistive load)

Peak inrush current: マックス. 60あ (20MS, suitable for inductive startup of motors and contactors)

Switching voltage range: AC 5~480V / DC 5~250V

Rated switching capacity: 3000バージニア州

Minimum reliable switching load: 5ミリアンペア / 5V (no sticking for weak signal circuits)

接点材質: AgSnO2 silver tin oxide, 耐アーク性と耐溶接性

4.2 Core Feature of Forcibly Guided Safety Design (Distinction from Standard Relays)

Forced mechanical linkage: NO and NC contacts within the same channel can never conduct simultaneously

Monitoring logic: Safety circuits can detect NC feedback signals to judge contact welding faults

Dielectric withstand voltage between contacts: 4000VAC; open contact withstand voltage: 1500VAC

Contact creepage distance: ≥10mm between coil and output contacts; ≥8mm between two output contact banks for enhanced isolation protection

4.3 Service Life Ratings

機械的寿命: 10 million operations under no-load conditions

電気的寿命 (12A/250VAC resistive): 250,000 オペレーション

Factory contact resistance: ≤100mΩ (tested at 6V/100mA)

  1. 14-Pin Pinout Definition (Standard Top Silkscreen Layout)

Coil Pins (Drive Side)

13(+), 14(-): DC coil positive and negative terminals with built-in diode. Connect 14 to 0V and 13 to DC24V.

Two Independent Safety Contact Banks (1NO+1NC per bank with forced linkage)

チャネル 1 (First Contact Bank)

1: Common COM1 | 2: NC Normally Closed | 3: NO Normally Open

チャネル 2 (Second Contact Bank)

4: Common COM2 | 5: NC Normally Closed | 6: NO Normally Open

Pins 7~12 are unoccupied locating pins with no electrical connections.

  1. Environmental Operating Parameters

動作温度: -40℃~+70℃

保管温度: -40℃~+85℃

湿度: 5%~95% RH、結露なし

振動 / 耐衝撃性: IEC60068 industrial equipment grade, suitable for machine tool and production line control cabinets

  1. 典型的なアプリケーションシナリオ (Dedicated for Safety Circuits)
  2. Dual-channel monitoring for machine safety door and emergency stop circuits (NC contacts detect welding faults)
  3. Safe cut-off circuits for inverter and servo enable signals
  4. Output expansion for safety light curtains and safety mats on automated production lines
  5. Safety control circuits for rail transit, medical equipment and lifts
  6. High-current output expansion for PLCs (direct drive of contactors and solenoid valves up to 12A)
  7. Equipment fault diagnosis feedback (self-inspection of contact adhesion via NC contacts)
  8. Cross-Series Model Selection Comparison Table
モデル接点構成Continuous Currentコイル電力アプリケーションシナリオ
SIR222P2NO+2NC12あ0.75WHigh-current safety circuits, contactor driving (primary recommended model)
SIR2222NO+2NC10あ0.6WMedium/low-current signal safety circuits
SIR312P3NO+1NC12あ0.75WMulti-output single-channel monitoring
SIM2222NO+2NC8あ1WCompact low-load safety relay
  1. トラブルシューティング マトリックス
故障現象根本的な原因解決
Coil energized but NO contacts fail to close1. Reversed coil polarity; 2. Supply voltage below 70% 定格電圧; 3. 焼けたコイルSwap pins 13 そして 14; Measure DC supply voltage; リレーを交換する
NO contacts stick closed after power-off, NC contacts cannot close (critical safety failure)Load current exceeds 12A; repeated heavy arcing welds contactsReduce load or add intermediate relay; Install brand-new SIR222P
Both NC and NO contacts conduct during safety inspectionDamaged forcibly guided mechanical structure; relay cannot be repairedReplace immediately; prohibit further use in safety circuits
Severe contact voltage drop and overheatingPoor PCB soldering; long-term near full 12A loadRe-solder PCB pins; Parallel additional contacts for current sharing
Coil shows no pull-in action at allOpen circuit at pins 13/14; No power supply outputInspect power circuit and PCB solder joints for open connections
  1. Mandatory Installation & Usage Prohibitions
  2. NC contact safety monitoring must not be omitted: Safety devices must read NC feedback signals; otherwise anti-welding protection is lost.
  3. Long-term resistive load shall not exceed 12A; inductive loads are recommended to be derated to 8A.
  4. DC coils must not be energized with reversed polarity for extended periods (built-in diode only provides one-time transient protection; sustained reverse voltage burns the coil).
  5. Prohibit full-load continuous operation above 70℃ in sealed cabinets; sufficient heat dissipation space must be reserved.
  6. Do not parallel contacts of different relays for current expansion; single-channel load cannot exceed rated current of one contact.
  7. Only PCB soldering mounting is allowed; avoid violent bending or repeated plugging/unplugging of pins.
  8. Standard Packing List

1 × SIR222P relay unit

  1. Original manufacturer safety datasheet, TÜV/CE safety certification documents
  2. Standard package quantity: 15 1箱あたりの個数

Application Manual for ELESTA SIR222P Forcibly Guided Safety Relay

Document Version: V1.0|Applicable Models: SIR222P-24VDC (主流), SIR222P-12VDC

ブランド: ELESTA (スイス)|Safety Standards: IEC 61810-3 Type A Forcibly Guided Contacts, EN50205, ISO13849-compliant safety circuit design

Table of Contents

  1. 製品概要 & 型式コードの説明
  2. Complete Electrical Specifications
  3. Pinout Definition & Standard Wiring Specifications
  4. 4 Standard Industrial Wiring Schemes (Including Safety Circuits)
  5. PCB Mounting, Soldering & Mechanical Installation Standards
  6. Load Selection & Derating Guidelines
  7. Core Rules for Safety Circuit Design (Requirements for Forcibly Guided Contacts)
  8. Power-On Commissioning & Functional Test Procedures
  9. トラブルシューティング マトリックス
  10. Mandatory Installation & Usage Prohibitions
  11. Cross-Series Alternative Model Comparison
  12. 包装 & 認証書類
  13. 製品概要 & 型式コードの説明

1.1 Model Code SIR222P

SIR: SIR4 Power series PCB-mounted forcibly guided safety relay

222: Contact structure: 2いいえ + 2ノースカロライナ州, two independent banks of 1NO+1NC forced-linkage contacts

P: High-current version with 12A AC1 continuous rating per contact (standard SIR222 is only 10A)

1.2 Core Safety Features (Distinction from Ordinary Relays)

  1. Forcibly Guided Mechanical Structure: NO and NC contacts within one channel can never conduct simultaneously. If contacts weld shut, the paired opposite contacts remain open to enable fault diagnosis.
  2. Coil-to-contact dielectric withstand voltage: 2500VAC; inter-contact isolation: 4000VAC. Creepage distances meet safety isolation criteria.
  3. AgSnO2 silver tin oxide contacts with thin gold plating, anti-arcing and anti-welding, compatible with both high-current loads and weak signal detection.
  4. Built-in coil freewheeling diode (dedicated for DC coils to prevent reverse voltage breakdown).

1.3 Applicable Safety Performance Levels

Suitable for PLd / カテゴリ3, SIL2 safety cut-off circuits. Dual-channel redundant design achieves Cat.4 / PLe.

  1. Complete Electrical Specifications

2.1 コイルパラメータ (直流)

アイテムSIR222P-24VDCSIR222P-12VDC
Nominal pull-in power0.75W0.75W
Holding power consumption0.23W0.23W
DC coil resistance760Ω±10%190Ω±10%
Pull-in voltage range70%~110% Un (16.8~26.4VDC)8.4~13.2VDC
ドロップアウト電圧≤10% Un≤10% Un
Coil reverse protectionBuilt-in freewheeling diode (Pin13+, Pin14-)Built-in freewheeling diode
Coil dielectric withstand voltage2500V AC for 1min2500V AC for 1min

2.2 Contact Load Ratings (Per 1NO/1NC Channel)

  1. AC1 resistive: 12あ / 250VAC, max switching capacity 3000VA
  2. AC15 inductive (接触器 / 電磁弁): 8あ / 250VAC (derating mandatory)
  3. DC13 inductive: 5あ / 24VDC
  4. Peak surge current: 60あ (short-duration 20ms)
  5. Minimum reliable switching load: 5ミリアンペア / 5V (no poor contact for PLC weak feedback signals)
  6. 接点材質: AgSnO2 with 0.2~0.4μm gold plating
  7. Factory contact resistance: ≤100mΩ (6V/100mA test condition)

2.3 Service Life Ratings

機械的寿命 (無負荷): 10 100万操作

電気的寿命 (12A/250VAC resistive): 250,000 オペレーション

電気的寿命 (8A inductive load): 100,000 オペレーション

2.4 環境 & 機械的パラメータ

全体の寸法: 46.4(L)×16(W)×30.7(H)mm, 14-pin through-hole PCB mount

重さ: 32g

動作温度: -40℃~+70℃ (enhanced heat dissipation required for full load at 70℃)

保管温度: -40℃~+85℃

湿度: 5%~95% RH、結露なし

耐振動性: 10~55Hz, 1.5mm amplitude for 2 hours on each of three axes

ハウジング: Transparent green flame-retardant PC for visual contact inspection

  1. Pinout Definition (Top Silkscreen View, Standard PCB Footprint)

3.1 Coil Drive Pins

13: Coil positive DC+

14: Coil negative DC(cathode of built-in diode; sustained reverse connection prohibited)

3.2 Two Independent Forcibly Guided Contact Banks (COM+NC+NO per bank)

チャネル 1 (First Safety Contact Bank)

1: Common COM1

2: NC1 Normally Closed (forced linkage feedback contact)

3: NO1 Normally Open (main power output)

チャネル 2 (Second Safety Contact Bank)

4: Common COM2

5: NC2 Normally Closed (forced linkage feedback contact)

6: NO2 Normally Open (main power output)

3.3 Unoccupied Pins

ピン 7,8,9,10,11,12: Locating reinforcement only, no electrical connection, wiring forbidden.

3.4 Forced Linkage Logic (Core Safety Principle)

コイルが非通電状態 (open state): Pins 2-NC1 and 5-NC2 conduct; Pins 3-NO1 and 6-NO2 open

コイル通電 (pulled-in state): Pins 2-NC1 and 5-NC2 open; Pins 3-NO1 and 6-NO2 conduct

Fault judgment rule: If NC contacts remain closed after coil energization → NO contacts welded shut; safety circuit triggers fault and equipment shutdown.

  1. Four Standard Industrial Wiring Schemes

スキーム 1: Dual-Channel Safety Cut-Off Circuit (非常停止 / Safety Door, 最も一般的な)

機能の説明

Two independent NO contacts cut servo/inverter enable signals; two NC contacts connect to PLC for contact welding fault monitoring, complying with ISO13849 Cat.3 safety requirements.

配線手順

  1. Coil drive: PLC 24V+ output → Pin13; 0V → Pin14
  2. Power output circuit (two independent cut-off paths, parallel connection prohibited)

チャネル 1: 24VAC/DC supply → COM1(Pin1); NO1(Pin3) → Servo Enable Coil 1

チャネル 2: 24VAC/DC supply → COM2(Pin4); NO2(Pin6) → Servo Enable Coil 2

  1. Fault feedback monitoring (NC contacts wired to PLC digital input)

NC1(Pin2) and NC2(Pin5) shorted together and connected to PLC PNP input; PLC logic: NC contacts must open when relay pulls in. Continuous conduction indicates contact welding and locks out equipment startup.

Mandatory Safety Rule

Two output loads must be independent. Parallel connection of NO1 and NO2 for current expansion destroys dual-channel redundant safety design.

スキーム 2: PLC High-Current Output Expansion (電磁弁 / Contactor Drive)

適用範囲

PLC single-point output current ≤0.5A, insufficient for direct drive of 10A solenoid valves; SIR222P expands contact current capacity.

  1. コイル: PLC output drives Pins13/14 (24VDC)
  2. Main circuit AC220V live wire → COM1(Pin1), COM2(Pin4)
  3. NO1(Pin3) and NO2(Pin6) parallel to solenoid coil (parallel allowed for resistive loads, not recommended for inductive loads)
  4. NC contacts unused or wired to alarm indicator light (light illuminates when relay de-energized)

スキーム 3: Equipment Self-Diagnosis Circuit (Safety Light Curtain Output Expansion)

  1. Dual-channel NC signals from safety light curtain wired in series to drive relay coil Pins13/14
  2. Two NO contacts cut main contactor power supply; two NC contacts feed real-time contact status to PLC
  3. 論理: Curtain blocked → coil de-energized → NO contacts open and machine stops; If NC contacts stay closed with unobstructed curtain, relay contact damage is detected and alarm interlock activates.

スキーム 4: Mixed Weak Signal & High-Current Circuit (Contact Channel Isolation)

  1. Channel1 NO contacts: Drive high-current AC220V contactors
  2. Channel2 NC contacts: Feed 5V weak feedback signal to MCU IO ports (gold-plated contacts guarantee stable low-current contact performance)

Prohibition: Do not share one contact bank for both high-current inductive loads and 5V weak signals; arcing contaminates contact surfaces and causes intermittent weak signal faults.

  1. PCB Mounting & Soldering Standards

5.1 PCB Pad Design Requirements

Pin hole diameter: 1.3mm, pad diameter ≥2.2mm

Standard pin pitch layout compatible with all 14-pin relays

Wider copper traces for COM/NO/NC high-current pins; copper thickness ≥35μm, trace width ≥5mm for 12A loads

5.2 Soldering Process Specifications

  1. Wave soldering peak temperature ≤260℃, contact duration ≤4s; hand iron temperature ≤350℃, single pin soldering time ≤3s
  2. Prolonged high-temperature heating of pins is forbidden, as it melts internal contact plastic supports
  3. Solder joints must be fully filled without cold solder or bridging between adjacent pins
  4. Clean flux residue after soldering to prevent leakage and creepage currents

5.3 放熱要件

Continuous full 12A operation: Increase PCB copper trace heat dissipation area; cabinet ambient temperature ≤60℃

Ambient temperature of 70℃: Load must be derated to ≤8A

  1. Load Selection & Derating Standards
負荷の種類Rated Permitted CurrentMandatory Derating Explanation
AC250V resistive (heating lamps, 抵抗器)12あNo derating required for long-term stable operation
AC250V inductive (接触器, 電磁弁)8あInductive kickback arcs occur at power-off; mandatory 1/3 derating
DC24V inductive (electromagnetic clutches)5あPoor DC arc extinction performance; significant derating required
Weak signal 5~24V (PLC feedback)≤0.5AOnly use gold-plated NC contacts; do not share channel with high-current loads

Recommended Arc Suppression Measures

Fit absorption components across inductive load coils:

AC loads: RC absorption circuit (0.1μF capacitor in series with 100Ω resistor)

DC loads: Freewheeling diode wired in reverse parallel across coil terminals

  1. Mandatory Core Rules for Safety Circuit Design (Violation Invalidates Safety Certifications)
  2. NC contact monitoring cannot be omitted

All safety cut-off circuits (非常停止, safety doors, light curtains) must route both NC contact banks to the upper controller (PLC) for welding diagnosis. Circuits without monitoring fail to meet IEC61810-3 safety requirements.

  1. Dual-channel outputs must not be paralleled

Two NO contacts provide redundant safety cut-off; each must drive an independent load. Parallel connection eliminates fault isolation capability.

  1. Single-channel cut-off is prohibited for safety applications

Using only one NO contact to cut power while leaving the other unused downgrades safety classification directly to Cat.1 and fails machine safety acceptance tests.

  1. Do not series multiple safety relay contacts for current expansion

Multi-stage series connection increases contact failure probability and reduces safety level.

  1. Coil power supply must share the same source as the safety circuit. Separate power supplies cause asynchronous logic operation.
  2. Power-On Commissioning & Functional Test Procedures

8.1 Static Pre-Power Test (Multimeter Required)

  1. Coil de-energized state: Measure continuity between 1-2 そして 4-5; open circuit between 1-3 そして 4-6
  2. Measure coil resistance at Pins13/14 (760Ω for 24VDC model) to rule out short/open circuits
  3. Verify no continuity between unoccupied pins and coil/contact terminals

8.2 Energized Pull-In Test

  1. Apply rated DC24V to Pin13(+) and Pin14(-)
  2. Multimeter verification: Open circuit between 1-2 そして 4-5; continuity between 1-3 そして 4-6
  3. Cut coil supply voltage; contacts reset rapidly to original state

8.3 Safety Fault Simulation Test (Mandatory for Acceptance)

Manually simulate NO contact welding by shorting Pins1 and 3. With coil energized, NC1 (Pin2) remains conductive. PLC detects persistent NC closure and triggers fault alarm to validate the forcibly guided mechanical design.

  1. トラブルシューティング マトリックス
故障現象根本的な原因Standard Resolution
コイル通電, NO contacts fail to close1. Reversed Pin13/14 polarity; 2. Supply below 70% そして; 3. Open coil windingSwap coil terminals, measure supply voltage, リレーを交換する
NO contacts stick closed after power-off, NC cannot closeLoad exceeds 12A; no absorption circuit for inductive loads leading to arc weldingInstall RC/diode absorption, derate load, リレーを交換する
Coil pulls in but NC contacts remain closed (critical safety failure)Damaged forcibly guided mechanical linkage, seized contactsDiscard and replace immediately; ban use in safety circuits
接点過熱, voltage drop >1VPoor PCB soldering, continuous 12A full load at high temperature, insufficient copper trace widthRe-solder joints, enlarge PCB heat dissipation traces, derate operating load
Intermittent PLC weak signal feedbackNC contacts previously carrying high-current loads with carbonized arc deposits on contact surfacesリレーを交換する; separate high-current and weak signal channels
No coil pull-in action, zero voltage detectedOpen circuit at Pins13/14, blown power fuseInspect PCB solder pads and 24V supply circuit
Leakage short between adjacent pinsResidual flux condensation, cabinet internal condensationClean PCB surface, improve cabinet dehumidification and ventilation
  1. Absolute Installation & Usage Prohibitions
  2. Omission of NC contact welding monitoring on safety cut-off circuits voids safety certification validity.
  3. Continuous resistive loads exceeding 12A or inductive loads exceeding 8A burn contact sets.
  4. Long-term reverse energization of DC coils destroys the built-in freewheeling diode.
  5. Do not run continuous full 12A loads above 70℃ in sealed cabinets.
  6. Do not share one contact bank for both high-current inductive loads and 5V weak signal circuits.
  7. Parallel connection of two NO contacts for current expansion is forbidden in safety circuit applications.
  8. Prolonged full-load operation at ambient temperature above 70℃ is prohibited.
  9. Violent pin bending, repeated plugging/unplugging, and extended high-temperature soldering are forbidden.
  10. Do not deploy in circuits above AC480V, exceeding contact voltage withstand ratings.
  11. Cross-Series Alternative Selection Comparison
モデル接点構成Per-Contact Rated Currentコイル電力Application Difference
SIR222P2NO+2NC12A AC10.75WHigh-current safety cut-off, direct contactor drive (primary model)
SIR2222NO+2NC10A AC10.6WMedium/low-current signal safety circuits, low power consumption demand
SIR312P3NO+1NC12A AC10.75WMulti-channel power output with single fault monitoring path
SIM2222NO+2NC8A AC11WCompact low-load PCB control boards
  1. 包装 & 認証書類

12.1 Standard Packing List

1 × SIR222P-24VDC safety relay

  1. Original manufacturer datasheet
  2. Copies of CE and TÜV safety certification
  3. Standard carton quantity: 15 1箱あたりの個数

12.2 コンプライアンス認証

CE Industrial Equipment Certification

TÜV IEC 61810-3 Type A Forcibly Guided Contact Certification

EN50205 Machinery Safety Standard Compliance

RoHS Lead-Free Environmental Compliance Certification