Schneider VW3A3627 PROFINET Communication Module

This dedicated PROFINET IO industrial Ethernet communication option card for Altivar variable speed drives integrates a dual-RJ45 switch with plug-and-play expansion. It connects Schneider drives to Siemens PROFINET bus systems and complies with the standard PROFIdrive drive profile. Complete Model Breakdown VW3A3627 VW3A: Prefix for Altivar drive communication accessories 36: Ethernet bus module series 27: ...

  • 製品詳細

This dedicated PROFINET IO industrial Ethernet communication option card for アルティバール variable speed drives integrates a dual-RJ45 switch with plug-and-play expansion. It connects Schneider drives to Siemens PROFINET bus systems and complies with the standard PROFIdrive drive profile.

  1. 完全なモデルの内訳

VW3A3627

VW3A: Prefix for Altivar drive communication accessories

36: Ethernet bus module series

27: Dual-RJ45 port PROFINET variant

Ⅲ. 主要な技術仕様

アイテム仕様
通信プロトコルプロフィネットIO (RT Real-Time / IRT Isochronous Real-Time), LLDP, PROFIdrive V4, embedded HTTP web server
Physical Interfaces2 ×RJ45 (integrated Layer 2 スイッチ; daisy-chain wiring eliminates extra switches)
伝送速度100 Mbps full-duplex
電源Powered by drive backplane; 外部電源は不要です
Status LEDsMS Module Status, NS Network Status, Port1 TX/RX, Port2 TX/RX
準拠基準IEC 61800-7-201 CiA402, PROFINET Class B/C
保護クラスIP20 (キャビネット取り付け専用)
寸法100 × 80 × 20 mm
正味重量0.3 kg
機能Web-based monitoring, パラメータの読み取り/書き込み, 障害記録, configuration upload/download, Ethernet statistics & 診断
  1. Compatible Drive Models (完全なリスト)
  2. ATV32 / ATV320 (Compact low-power Altivar series)
  3. ATV340 (Machinery-specific; Sercos variants excluded)
  4. ATV630 / ATV650 (ATV600 Process series)
  5. ATV930 / ATV950 (High-power heavy-duty ATV900 series)
  6. Altivar Process Modular modular variable speed drives

> Incompatible Units: ATV12 / ATV21 / ATV212, legacy VW3A34xx bus card series

  1. 主な利点
  2. Dual-port daisy-chaining: Direct cable interconnection between drives reduces switch ports and simplifies cabinet wiring.
  3. Embedded Web Server: Drives can be commissioned via browser by plugging a PC directly into the RJ45 port; no dedicated software needed.
  4. Standard PROFIdrive compliance: Seamless compatibility with Siemens PROFINET PLCs including S7-1200/1500/300/400 and ET200SP.
  5. Hot-swap capable: The module can be removed and replaced while the drive is stopped without damaging the unit.
  6. Comprehensive diagnostics: Four LED indicators enable fast troubleshooting of module faults, cable breaks, and missing master station issues.
  7. Communication Card Series Comparison (選定基準)
モデルBus TypePorts代表的な用途
VW3A3607プロフィバス-DP端子台Retrofit legacy DP bus systems
VW3A3616Modbus TCP / イーサネット/IPデュアル RJ45ロックウェル & domestic brand PLC Ethernet networking
VW3A3601EtherCATデュアル RJ45高速モーションコントロール
VW3A3627プロフィネットデュアル RJ45Projects with full range of Siemens PLCs
VW3A3608CANopenデュアル RJ45CAN bus for small machinery

Ⅶ. 典型的なアプリケーションシナリオ

Automotive production lines, コンベアシステム, 包装機械 (paired with Siemens PLCs)

High-power variable frequency control cabinets for chemical processing, water treatment and HVAC (ATV630 / ATV930)

Machine tools and compact automated equipment (ATV320 / ATV340)

Multi-drive daisy-chain networking to cut industrial switch costs

VIII. Troubleshooting Key Points

  1. Steady red MS LED: ハードウェア障害, loose module insertion, mismatched drive firmware version
  2. Steady red NS LED: No PROFINET device name assigned, IP address conflict, broken bus cable
  3. Unlit port LNK indicator: Damaged Ethernet cable, poor crimp on RJ45 connector, powered-off remote device
  4. Frequent communication packet loss: Non-shielded Ethernet cable, poor cabinet grounding, routing alongside power cables
  5. 交換ノート

No upgraded alternative within the same platform; VW3A3627 is the only original factory card for PROFINET applications.

No single-port PROFINET original card available; this dual-port model must be used if PROFINET connectivity is required.

Supported Drive Brands for Schneider VW3A3627

  1. Sole Supported Brand: シュナイダーエレクトリック

The VW3A3627 is an original factory plug-in communication card exclusively designed for Schneider Altivar drives. Its hardware slot, underlying driver and power supply protocol are custom-made for Schneider drives. It is completely incompatible with all other brands including Siemens, ABB, ダンフォス, Inovance and Delta, with no physical fit or matching communication firmware support.

  1. Full Compatible Schneider Altivar Drive Series
  2. Compact Machinery Range: ATV32 / ATV320

ATV32 (legacy low-power): Direct plug-in installation

ATV320-B variants: Equipped with native communication slot for direct insertion

ATV320-C variants: Require additional VW3A3600 adapter to mount this card

  1. High-End Machinery-Specific ATV340

Compatible models: ATV340U07N4 ~ D22N4, ATV340D30N4E ~ D75N4E

Incompatible models: ATV340U07N4E ~ D22N4E (no expansion slot)

Exclusion: ATV340 Sercos dedicated versions do not support this card

  1. General High-Power Process ATV600 Series

ATV630, ATV650, Altivar Process Modular modular drives

  1. Heavy-Duty High-Power ATV900 Series

ATV930, ATV950

Ⅲ. Clearly Incompatible Legacy Schneider Drives

ATV12, ATV21, ATV212, ATV31, ATV312 (no VW3A36xx expansion slots; only legacy VW3A34xx DP cards are supported)

  1. Critical Supplementary Notes
  2. No cross-brand compatibility

Even if drives from other brands support the PROFINET protocol, differing hardware slots and backplane communication buses prevent installation of the VW3A3627, with no matching firmware drivers. Each brand supplies proprietary PROFINET cards: Siemens SINAMICS uses CBE20, ABB ACS uses FPNO-01, Danfoss VLT uses MCA120.

  1. No brand restriction on PLC side

From a communication perspective, this card interfaces with all PROFINET IO-capable PLCs including Siemens, 革新, Xinje and Rockwell. The only mounting host must be the aforementioned Schneider drives.

  1. Installation prerequisite: Matching drive firmware version. Versions below the minimum requirement trigger a red MS hardware fault LED.

Complete Installation Guide for Schneider VW3A3627 PROFINET Communication Module

  1. Mandatory Safety Pre-Installation Rules (Risk of Electric Shock / ESD Damage)
  2. Full power cut-off & capacitor discharge

Disconnect main drive power and 24V control power, apply lockout-tagout procedure. Wait 15 minutes to discharge DC bus capacitors; verify bus voltage is below 42 V with a multimeter before proceeding.

  1. ESD anti-static protection

Wear an anti-static wrist strap or touch grounded cabinet metalwork to release static charge. Do not touch circuit board gold finger contacts with bare hands—static electricity can permanently damage the module.

  1. 環境要件

Cabinet free of dust and condensation; 周囲温度 0 ~ 50 ℃. Keep clear of high-interference sources such as power cables and contactors.

  1. Parts Checklist

モジュール: VW3A3627

Mandatory accessory for compact ATV320-C units: VW3A3600 communication adapter

Cabling: Industrial shielded CAT5e / CAT6 Ethernet cable (PROFINET standard)

  1. Hardware Installation Steps by Drive Model

モデル 1: ATV320-B (Book-style, no adapter required)

  1. Remove the dust cover from the front communication slot of the drive.
  2. Align the module gold fingers with the slot and insert horizontally. Do not push fully home; the alignment mark confirms correct positioning.
  3. Listen for the click of the locking clip to confirm the module is secured without play.
  4. 除去: Press the PUSH clip below the module and pull steadily outwards.

モデル 2: ATV320-C / ATV320-W (コンパクト / High-protection, アダプターが必要です)

  1. Mount and lock the VW3A3600 adapter onto the side expansion port of the drive first.
  2. Insert the VW3A3627 horizontally into the adapter slot; the clip locks automatically.
  3. 除去: Press down the adapter PUSH clip and extract the communication card.

モデル 3: ATV340 / ATV630/650 / ATV930/950 (プロセス / Heavy-Duty High-Power)

  1. Open the cover of the front expansion slot on the drive.
  2. Align the module gold fingers with the backplane bus slot and push fully home.
  3. Press the top module clip to lock securely with no wobble.
  4. 除去: Pinch both side clips to release and pull the module straight out vertically.

Ⅲ. Ethernet Cable Wiring Specifications (Dual-RJ45 Daisy-Chain Topology)

  1. Port definition: Port1 (uplink to PLC / スイッチ), Port2 (downlink to next drive); integrated Layer 2 switch onboard.
  2. Cabling: Fully shielded industrial Ethernet cable. 360° crimp the cable shield to the metal shell of both RJ45 connectors, with single-point cabinet grounding.
  3. Wiring routing: Separate Ethernet cables from power cables with a minimum clearance of 30 cm; cross cables perpendicularly where crossing is unavoidable.
  4. Prohibited practices: Unshielded civilian Ethernet cables, ungrounded long cables, routing cables adjacent to contactors or drive output power cables.
  5. Pre-Power-On Inspection Checklist
  6. Module clips fully engaged with no loose or partially inserted state.
  7. Gold finger contacts free of bending, oxidation or foreign debris.
  8. RJ45 cable connectors fully crimped, aligned with LNK indicator lights.
  9. All drive covers reinstalled for complete protection.
  10. Reliable PE cabinet grounding with ground resistance ≤ 4 おお.
  11. Power-On Module Detection & 基本構成
  12. Observe module LEDs after power-up:

MS LED: Module status (Green = Normal; Red = Hardware fault / Undetected)

NS LED: Network status (Green = Online; Red = No master station / IP conflict)

Port1/Port2 LNK: Steady on when cable connected; flashing ACT indicates data exchange

  1. Activate communication card via drive parameters:

Navigate to parameter `COM.` → Select communication type as `PROFINET`

Import the corresponding GSD file into the PROFINET master PLC

Assign device name and IP address, complete hardware configuration

  1. Installation Prohibitions (Strictly Forbidden Operations)
  2. Hot plugging/unplugging the module (risks burning the backplane bus, module and drive main control board)
  3. Touching circuit boards without anti-static protection
  4. Forcing card insertion into ATV320-C units without installing the VW3A3600 adapter
  5. Rough force or angled insertion bending gold finger contacts
  6. Using unshielded Ethernet cables or leaving cable shields ungrounded
  7. Leaving drive covers removed after module installation (dust ingress may cause short circuits)

Ⅶ. Quick Troubleshooting for Common Installation Faults

故障の症状根本的な原因解決
Steady red MS LEDモジュールの挿入が緩んでいる / Outdated drive firmware / Dirty gold fingers電源を切る, reinsert module; upgrade drive firmware; clean gold finger contacts
Steady red NS LEDUnassigned PROFINET device name / IP conflict / 断線したケーブルDownload device name via PLC configuration; inspect cables; unify IP subnet range
Unlit port LNK indicatorPoor RJ45 crimp / ケーブルの損傷 / Powered-off remote deviceReplace industrial Ethernet cable; re-crimp RJ45 connectors
Frequent communication packet lossUnshielded cable / 接地不良 / Routing near power cablesFit shielded Ethernet cable; implement solid cabinet grounding; separate wiring routes