SIMATIC ET200SP RQ 4×120VDC…230VAC/5A NO ST Relay 出力モジュール
Distributed IO ET200SP, 4-channel normally-open digital リレー output module, contact isolated type
✅ Model Code Interpretation
6ES7: SIMATIC S7 オートメーション システム
132: ET200SP Digital Output Module
6HD01: 4-チャンネルリレー出力, 120VDC~230VAC, 5A normally open
0BB1: Single pack (1 unit per box); `2BB1` = 10-piece bulk pack
📋 Key Technical Specifications
| アイテム | パラメータ |
| チャンネル数 | 4 normally-open relay outputs (いいえ), channel-to-channel isolation |
| 接点の定格 | 120V DC ~ 230V AC, 最大. 5チャンネルごとに |
| Base Unit Type | Compatible with BU B0 / BU B1 base units; color code CC40 |
| Backplane Bus Supply | 55ミリアンペア, typical power consumption 1.5W |
| 診断機能 | Module supply diagnostics, substitute value output |
| 動作温度 | 0 ~ +60 ℃ (standard module) |
| コミュニケーション | プロフィネット / プロフィバスDP (with ET200SP interface module) |
| HSコード | 85389091 |
🧩 Features
- Relay dry contact isolation: Galvanic isolation between PLC low-voltage side and load high-voltage side. Suitable for solenoid valves, 接触器, indicator lamps and other AC loads.
- Substitute value: When communication fails or CPU stops, output state can be preset in TIA Portal: hold / reset to 0 / に設定 1.
- Channel status LEDs + module diagnostic LED for fault alarm.
- Separate base & electronic module design: Hot-swappable electronics while wiring remains on base for easy maintenance.
⚙️ Typical Application Scenarios
Control of 220VAC solenoid valves, small contactors, alarm lamps, fan start/stop in control cabinets
Not suitable for high-frequency switching applications (limited relay mechanical service life; cannot handle high-speed pulses)
Distributed remote IO station deployed with IM155-6 interface module
⚠️ Selection & 配線上の注意
- Base unit must be BU B0 / BU B1 type, A-type bases are incompatible; recommended BU20-P16+A0+2B.
- Relay contacts are passive dry contacts. Load power is not supplied by module backplane, external power supply required.
- 誘導負荷 (接触器コイル) are recommended to connect varistor / freewheeling diode in parallel to extend relay service life.
- 5A per channel is rated current; pay attention to heat dissipation when all 4 channels run at full load simultaneously.
📌 Alternative & 派生モデル
6AG1132-6HD01-7BB1: SIPLUS wide-temperature conformal coated version, -40~+70℃, for harsh environments (化学工業, 屋外)
国内代替品: ET200SP compatible 4-channel normally-open 5A relay modules. Verify base compatibility and diagnostic telegram.
Application Scenarios for 6ES7132-6HD01-0BB1 (ET200SP 4-Channel Relay Output Module)
コア機能: Passive dry contacts, チャンネルアイソレーション; 最大. 5A for resistive loads, 最大. 2A for inductive loads; supports 24V~230V AC/DC loads; PROFINET distributed remote IO. Ideal for low-frequency switching control requiring galvanic isolation between strong and weak circuits.
- Industry-specific Applications
- Machinery Manufacturing (最も一般的な)
220VAC pneumatic & hydraulic solenoid valve control (シリンダー, hydraulic valve on/off)
Drive coils of small AC contactors to indirectly control fans, パンプス, コンベア
Equipment alarm lights, audible & visual alarms, panel indicator lamps
Door interlock, guard door signal output, equipment enable signal
該当する: 包装機, 工作機械, 生産ライン, 射出成形機, textile machinery remote IO stations
- Process Automation / 水処理
Remote field cabinet: 220V solenoid valves, dosing pumps, drain valves, agitator start/stop control
Field instrument power switching, warning lights, on-site audible & visual alarms
Water tank level interlock output; remote stations deployed at different plant locations
アドバンテージ: Relay isolation prevents field high-voltage interference from coupling into PROFINET bus
- 空調設備 & ビルディングオートメーション
AC220V air damper actuators, electric butterfly valve on/off control
Contactor coil control for fans, 排気ファン, ウォーターポンプ
Fire linkage signal output, on-site alarm indication
- エネルギー, PV & Power Auxiliary Control
Switchgear auxiliary circuit, relay loop switching, alarm contact output
Small heater, dehumidifier on/off control
Signal isolation transfer: Convert PLC low-voltage signals to dry contacts for 3rd-party systems (DCS, relay protection)
- Supported Load Types
- AC220V solenoid valves, インジケーターランプ, ブザー
- AC220V contactor / intermediate relay coils
- 抵抗負荷: heating tapes, 白熱灯 (≤5A)
- DC24V~DC120V DC loads (dry contacts work for both AC and DC)
- Passive contact output for hard-wired interlock with other control systems
Ⅲ. 不適切な用途
- ❌ High-frequency switching: Mechanical relay has limited service life, not for multiple operations per second. Use transistor DQ modules for high frequency.
- ❌ Direct drive of high-power motors (only drives contactor coils, not main motor circuit)
- ❌ Inductive load current exceeding 2A (solenoid & contactor are inductive loads; varistor / freewheeling diode required to absorb back EMF)
- ❌ Safety circuits (this module is non-failsafe. F-RQ failsafe modules are required for emergency stop and safety gate circuits)
- ❌ High inrush current loads (contact erosion risk; each channel needs external 6A max. fast fuse protection)
- Architecture Characteristics
ET200SP distributed IO: This module is mounted in remote field enclosures away from the main PLC and connected via IM155-6 PROFINET interface module.
Load wiring for 220VAC is routed locally, reducing long-distance high-voltage cables
Relay isolation protects PLC low-voltage system and improves EMC immunity
Substitute value configurable in TIA Portal: Output state can be defined for bus interruption or CPU stop to ensure safe equipment status
ET200SP Digital Output Module Selection Comparison Sheet
Compare 6ES7132-6HD01-0BB1 (RQ 4-channel relay output) vs common transistor DQ modules
- コアパラメータ比較表
| アイテム | 6ES7132-6HD01-0BB1 | 6ES7132-6BH01-0BA0 | 6ES7132-6BD20-0BA0 |
| Relay Output RQ | Transistor DQ 16×24VDC | Transistor DQ 4×24VDC/2A | |
| 出力タイプ | Passive dry contact, normally-open relay NO | PNPトランジスタ, active 24VDC | PNPトランジスタ, active 24VDC |
| チャンネル数 | 4 チャンネル | 16 チャンネル | 4 チャンネル |
| Load Voltage Range | 120VDC ~ 230VAC, 交流 & DC compatible | DC24V only | DC24V only |
| Rated Current per Channel | 5A resistive; 2A inductive | 0.5チャンネルごとに | 2チャンネルごとに |
| Galvanic Isolation | ✅ Channel isolation, strong/weak voltage isolation | ❌ No channel isolation, common 24V ground | ❌ No channel isolation |
| 応答速度 | 遅い: millisecond level (mechanical contact) | 速い: microsecond level | 速い: microsecond level |
| 耐用年数 | Mechanical life ~10⁷ operations (low frequency) | Nearly unlimited electronic life, high frequency capable | Nearly unlimited electronic life |
| 一般的な負荷 | AC220V solenoid valves, 接触器コイル, audible/visual alarms, dry-contact interlock | DC24V solenoid valves, インジケーターランプ, sensor power supply | High-current DC24V loads, DCソレノイドバルブ |
| Base Color Code | CC40 | CC01 | CC01 |
- When to select 【6ES7132-6HD01-0BB1 Relay Module】
✅ Recommended
- Load voltage is AC220V, no extra intermediate relay required on site
- Galvanic isolation required, heavy field interference, prevent high voltage from damaging PLC IO bus
- Need passive dry contact output for hard-wired interlock to 3rd-party DCS / protection relays
- Low switching frequency (triggered every few minutes/hours, not frequent on/off)
- 混合荷重: both AC220V and DC loads up to 120V
❌ Not Recommended
- 頻繁な切り替え: multiple start-stop per second (rapid contact wear and shortened lifetime)
- Pure DC24V loads with large point count requirement (transistor modules cheaper, higher channel density)
- High-speed pulse & motion control output (relay cannot generate pulses)
- SIL safety circuits (Failsafe F-series modules required)
Ⅲ. When to select 【Transistor DQ Module】
✅ Recommended
- All loads are DC24V, frequent switching (continuous actuation of cylinder solenoids)
- Requirement for high-speed switching signals or pulse outputs
- Large I/O point count, high channel density to save cabinet space
- Field loads are low-current DC components without isolation requirement
❌ Not Recommended
- AC220V loads: must add external intermediate relays
- Severe field high-voltage interference without isolation; risk of IO module burnout
- Quick Selection Rule
負荷: AC220V, low frequency, isolation required → 6ES7132-6HD01-0BB1
負荷: DC24V, frequent operation → Transistor DQ (6BH01 for many points / 6BD20 for high per-channel current)
- Additional Selection Notes
- 誘導負荷 (電磁弁, 接触器) need absorption components: varistor in parallel for AC loads, freewheeling diode for DC loads to suppress back EMF and extend contact life.
- Relay module base color code CC40, not interchangeable with transistor DQ base CC01.
- Cost reference: Relay modules usually cost more for same channel quantity. しかし, overall system cost may be lower when eliminating external intermediate relays.
- Failure characteristics: Relay contacts risk sticking; transistor modules mostly fail by breakdown with no mechanical sticking risk.
- Special Alternatives
Failsafe output: 6ES7136-6DB00-0CA0 (F-DQ for safety circuits)
Solid-state relay output (no moving contacts, suitable for high-frequency AC switching): ET200SP RQ solid-state relay models
コンタクタ,サーキットブレーカー,センサー,エンコーダ,PLC,コンバータ


















NH42-63-318x560.png)