EOCRPFZ-H2DZ7W와 EOCRPFZ-WRDUH의 차이점 - 접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지

위챗: +86-13184948252 왓츠앱: 0086-13811255435 이메일: kent@bestcontactor.com

에 대한 연락하다 |

EOCRPFZ-H2DZ7W와 EOCRPFZ-WRDUH의 차이점 - 접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지

소식무역 뉴스

EOCRPFZ-H2DZ7W와 EOCRPFZ-WRDUH의 차이점

Samwha EOCR-PFZ Motor Protection Relay

모델 비교: EOCRPFZ-WRDUH VS EOCRPFZ-H2DZ7W

Coding Rule for PFZ Series

`EOCRPFZ [CT 등급][연락처 구성][표시하다][제어 전원][기능][의사소통][트립 곡선][Terminal/Housing Type]`

  1. Model Suffix Breakdown

1) EOCRPZ-WRDUH

여: Built-in CT range 0.5~100A (W-type CT)

아르 자형: Relay contact layout: Trip contact OL (1아니요+1NC) + Alarm contact AL (1아니요)

디: 디지털 디스플레이

유: Control supply AC/DC 85~264V universal wide voltage

시간: Integrated zero-sequence ZCT, earth fault protection supported

👉 No suffix Z = standard version; without special trip curve code, no Curve 7

2) EOCRPZ-H2DZ7W

시간: Built-in CT range 0.5~60A (H-type CT) ✅【Key Difference 1】

2: 연락처 구성: Two independent changeover contact sets ✅【Key Difference 2】

디: 디지털 디스플레이

지: Built-in Modbus-RTU RS485 communication port ✅【Key Difference 3】

7: Special thermal protection curve (customized I²t overload & motor starting characteristic parameters, Curve No.7) ✅【Key Difference 4】

여: 주택 / feed-through terminal type

⚠️ 중요 참고 사항:

EOCRPFZ-WRDUH has no Z code → no RS485 communication;

EOCRPFZ-H2DZ7W with Z suffix = factory-fitted Modbus communication.

  1. Main Comparison Table
비교항목EOCRPZ-WRDUHEOCRPZ-H2DZ7W
Built-in CT Measuring Range0.5~100A0.5~60A
제어 전원 공급 장치AC/DC 85~264V wide universal rangeTypically AC100~240V (confirm upon order, wide voltage not guaranteed)
Output Relay ContactsOL: 1아니요+1NC; 알: 1아니요Two sets of changeover contacts (2×NO/NC), more contact terminals
총 3 contact points
Modbus RS485 Communication❌ Not supported✅ Standard onboard communication; allows PLC remote reading of current & 오류 코드
Overload Protection CurveStandard universal curveSpecial No.7 trip curve (optimized for heavy-start loads: 파쇄기, air compressors etc.)
지락 보호Built-in ZCT, earth fault availableBuilt-in ZCT, earth fault available (동일한 기능)
4~20mA Analog OutputDual-channel 4–20mA outputDual-channel 4–20mA output
Direct Interchangeability❌ Not plug-and-play❌ Not plug-and-play
Differences in measuring range, contact definition, communication and terminal layout
  1. 선택 & On-site Replacement Guidelines
  2. Measuring Range Priority

EOCRPFZ-WRDUH max range 100A; EOCRPFZ-H2DZ7W max 60A.

Never use H2DZ7W if motor rated current exceeds 60A.

  1. Communication Requirement as Key Criterion

If remote current monitoring, fault signal acquisition or remote parameter setting via PLC is required → choose H2DZ7W (with Z communication).

Only local protection without upper system communication → EOCRPFZ-WRDUH is acceptable.

  1. Rewiring Required for Contact Circuits

Terminal assignments and contact numbers differ between the two models. Direct replacement will cause control circuit malfunction. Drawings and wiring must be rechecked and modified.

  1. Match Trip Curve with Load Type

No.7 curve version (접미사 7) is preferred for crushers and heavy-duty long-start motors; standard curve WRDUH is sufficient for ordinary fans and water pumps.

  1. Brief Summary
  2. 측정 범위: WRDUH = 0.5–100A; H2DZ7W = 0.5–60A
  3. 의사소통: H2DZ7W supports Modbus; WRDUH has no communication
  4. 콘택트 렌즈: H2DZ7W equipped with two changeover contact sets; WRDUH adopts standard 1OL+1AL contacts
  5. Protection curve: H2DZ7W uses special No.7 curve for heavy startup loads
  6. 전원공급장치: WRDUH supports wide AC/DC 85~264V input for better compatibility