L4008: Honeywell basic series of water temperature controllers, used for liquid temperature limiting and regulation in boilers, storage tanks and other equipment, equipped with remote temperature bulb.
이자형: Series function code, stands for High Limit type, 수동 재설정, Breaks on Temperature Rise.
1255: 구성 코드, defining key parameters such as temperature range, temperature bulb length and mounting method.
- 핵심 기본 매개변수
| 목 | 사양 |
| 상표 | 하니웰 / Resideo |
| 제품 유형 | High Limit Remote Bulb Aquastat Controller |
| 온도 범위 | 100°F (37.8℃) ~ 240°F (115.6℃) |
| 재설정 모드 | 수동 재설정 (Press red reset button to release safety lockout) |
| Bulb Length | 20 피트 (대략. 6.1 중) |
| Maximum Limit Temperature | 240°F (factory preset) |
| 스위치 유형 | SPST Micro Switch™ |
| 전기 등급 | 120V AC @ 8A; 240V AC @ 5.1A; Locked Rotor Current: 48A @ 120V, 30.6@ 240V |
| 장착 방법 | 수평의 / Vertical mounting available |
| 애플리케이션 | Liquid temperature control for boilers, storage tanks, 온수기; also applicable to duct or ambient air temperature detection |
- 주요 특징
- Remote Sensing Design: The temperature bulb is separated from the controller body, 감지 지점에서 멀리 떨어진 곳에 설치 가능.
- 안전 잠금 기능: 온도가 설정된 한계에 도달하면 자동으로 트립되고 잠깁니다.; 장비 과열 손상을 방지하기 위해 작동을 재개하려면 수동 재설정이 필요합니다..
- 빠른 응답: 설정 온도에서 신속한 트리핑을 위해 완전 밀폐형 Micro Switch™ 스냅액션 스위치 채택.
- 직관적인 조정: 손쉬운 현장 설정을 위해 눈에 보이는 온도 눈금과 외부 조정 나사가 장착되어 있습니다..
- 유연한 장착: 수평 또는 수직 설치 지원; 감지 전구는 액체에 직접 담그거나 Thermowell을 통해 설치할 수 있습니다..
- 튼튼한 & 믿을 수 있는: 열악한 작동 환경에 적합한 산업 등급 구조.
- 호환 가능한 교체 모델
- 동일 브랜드 교체:
L4008E1305: 동일한 온도 범위 (100-240°F), 수동 재설정, 다른 전구 길이
L4008E1040: 온도 범위 130~270°F, 수동 재설정, 66-인치 전구
L4008E1313: 온도 범위 100~200°F, 수동 재설정, 원격 전구 유형
- 브랜드 간 호환 모델:
존슨 컨트롤 A19ABC-1C: 하이 리미트 아쿠아스타트, 100-240°F, 수동 재설정
지멘스 RWD62: 범용 온도 조절기, 상한 모드로 구성 가능, 원격 센서 지원
- 모집요강
- 설치 참고 사항: 온도 전구는 측정된 액체에 완전히 잠겨야 합니다., 정확한 측정을 위해 탱크 벽이나 가열 요소와의 접촉을 피하십시오..
- 재설정 작업: 시스템 종료 후, 먼저 온도가 안전한 범위로 떨어지는지 확인하세요., 그런 다음 빨간색 재설정 버튼을 눌러 다시 시작하세요..
- 배선 표준: 전기 등급에 따라 엄격하게 배선하십시오.; 과부하 작동을 피하십시오.
- 권장사항 설정: 보일러 별, 설비 제조사 사양별 상한 온도 설정; 장비의 최대 견딜 온도를 초과해서는 안 됩니다..
- 유지: 부식 및 느슨한 접촉을 방지하기 위해 전구 절연 및 단자 연결을 정기적으로 검사하십시오..
- 안전 수칙: 상한 컷아웃으로 사용하는 경우, 시스템 안전을 강화하기 위해 다른 안전 보호 장치와 협력하는 것이 좋습니다..
Honeywell L4008E1255 High Limit Aquastat 컨트롤러용 전체 설치 안내서
- 설치 전 준비 & 안전 지침
1.1 필수 도구 & 부속품
| 도구 / 종범 | 목적 |
| 드라이버 세트 (평평한 / 필립스) | 컨트롤러 고정 및 단자 배선 |
| 파이프 렌치 / 조정 가능한 렌치 | 써모웰 및 피팅 설치 |
| 와이어 스트리퍼 | 와이어 스트리핑 (권장 스트리핑 길이: 6-8mm) |
| 멀티미터 | 회로 연속성 및 전압 테스트 |
| PTFE 테이프 / 실란트 | 누수를 방지하기 위해 써모웰 나사산을 밀봉하세요. |
| 장착 나사 (#8 / #10) | 컨트롤러 본체 고정 |
| 써모웰 (1/2″ NPT 스레드) | 온도 전구를 보호하고 정확한 감지를 보장합니다. |
1.2 안전 예방 조치
전원 끄기 작업: 감전 위험을 방지하려면 설치 전에 시스템 전원을 분리하세요..
시스템 드레이닝: 보일러 내부 액체 배출 / 물 유출을 방지하기 위해 전구 설치 전 연결 포트 아래 탱크.
온도체크: 시스템이 안전한 온도까지 냉각되는지 확인하세요. (<50℃) 화상을 입지 않도록.
Professional Qualification: Installation and commissioning recommended by qualified HVAC technicians.
Rating Matching: Verify controller electrical ratings (120V AC @8A; 240V AC @5.1A) match system load.
- Controller Main Unit Mounting Methods
L4008E1255 supports two main mounting options according to site space:
2.1 벽 / 패널 나사 장착 (추천)
- 포지셔닝 & 마킹
Select vertical wall or control cabinet panel with dry, ventilated and vibration-free environment.
Use three mounting holes on controller rear as template to mark screw positions with pencil.
구멍 간격: 대략. 76mm horizontal, 51mm vertical (standard mounting dimension).
- Drilling & 고정
Drill with 3/16 인치 (대략. 4.8mm) bit for drywall / 목재.
Install plastic wall anchors for wall mounting.
Fasten controller to wall / panel with 8 또는 10 self-tapping screws, ensure firm installation without looseness.
2.2 Pipe Surface Mounting (선택 과목)
- Accessory Preparation: Use dedicated Honeywell pipe mounting bracket (included in some models).
- Bracket Fixing: Secure bracket to pipe with diameter ≥2 inch using pipe clamp, ensure tight clamping.
- Controller Installation: Fix controller onto bracket; either vertical or horizontal orientation is acceptable.
2.3 Mounting Orientation Requirements
수직 장착: Most recommended for internal component heat dissipation and mechanical stability.
수평 장착: Allowed; ensure capillary hangs naturally without sharp bending.
Inverted Mounting Prohibited: Do not install upside down, otherwise internal switch operation accuracy may be affected.
- Temperature Bulb Installation (Core Procedure)
L4008E1255 is equipped with 20 피트 (대략. 6.1 중) remote temperature bulb, installation quality directly affects temperature control accuracy.
3.1 장착 방법 선택
| 응용 시나리오 | Recommended Method | Applicable Condition |
| 보일러 / Storage Tank | Thermowell Mounting | Liquid pressure >0.1MPa, long-term stable measurement required |
| Open Tank | Direct Immersion | No liquid pressure, 쉬운 유지 보수 |
| Duct / 공기 | Bracket Fixed Mount | Air temperature detection, avoid direct contact with duct wall |
3.2 Thermowell Mounting (Standard Procedure)
- System Preparation
Cut off system power and drain liquid below connection port.
Clean boiler / tank thread port to remove dirt and impurities.
- Thermowell Installation
Adopt standard 1/2″ NPT threaded thermowell (usually supplied with product).
Wrap 3–5 layers of PTFE tape on thread and apply proper sealant.
Screw thermowell into port with pipe wrench; torque controlled at 20–25N·m, avoid over-tightening thread damage.
- Bulb Installation
Remove bulb protective cover and inspect bulb for damage.
Insert bulb fully to the bottom of thermowell for full liquid contact.
Fix bulb wiring to prevent capillary pulling or sharp bending (minimum bend radius ≥50mm).
3.3 Direct Immersion Mounting (Simplified Procedure)
- Ensure tank opening diameter ≥25mm for easy bulb insertion.
- 전구를 깊이가 ≥100mm인 액체에 완전히 담그십시오.; 탱크 벽이나 가열 요소와의 접촉을 피하십시오.
- 측정 정확도에 영향을 미치는 변위를 방지하기 위해 일치하는 클램프로 전구 케이블을 고정합니다..
3.4 주요 전구 설치 지점
직책 선택: 액체가 잘 흐르는 곳에 설치, 정체 구역 및 발열체에서 멀리 떨어진 곳.
모세관 보호: 과도한 굽힘을 피하십시오, 내부 유체 누출을 방지하기 위해 쥐어 짜거나 늘리기.
방수 씰링: 컨트롤러 내부로 습기가 유입되는 것을 방지하기 위해 케이블 입구에 방수 씰링을 적용합니다..
정기고정: 진동 영향을 줄이기 위해 케이블을 1~1.5m 간격으로 고정하십시오..
- 전기 배선 절차
4.1 터미널 정의
| 터미널 마킹 | 기능 설명 | 배선 요구 사항 |
| L1/L2 | 전원 입력 (120전압/240V AC) | 실시간 연결 / 그에 따라 중성선, 부하 전류 일치 |
| T1/T2 | 제어 출력 (SPST 스위치) | 제어 장비 연결 (연소기, 워터펌프 등), 과부하는 허용되지 않습니다 |
| – | 접지 터미널 | 안전을 위해 안정적인 접지선을 연결해야 합니다. |
4.2 배선 작업 단계
- 터미널 커버 제거: 전면 터미널 커버 나사를 풀고 배선실을 엽니다..
- 와이어 준비: 14~18AWG 사용 (2.5-0.75mm²) 구리선, 스트리핑 길이 6~8mm.
- 전원 배선: L1을 활선에 연결, L2에서 중성선으로, 견고한 연결 보장.
- 부하 배선: 활선을 로드하려면 T1을 연결하세요., 제어선을 로드하는 T2; 다른 쪽 끝을 중립에 연결하십시오..
- 접지 연결: 황록색 접지선을 접지 단자에 고정합니다., 접지 저항 보장 <4오.
- 터미널 검사: 각 와이어를 부드럽게 당겨서 헐거움이 없는지 확인하세요.; 단락을 방지하기 위해 노출된 도체가 없는지 확인하십시오..
- 커버 재설치: 먼지와 습기 유입을 방지하기 위해 단자 커버를 닫고 고정하십시오..
- 시운전 & 테스트 절차
5.1 온도 조정
- 기본 설정: 공장 사전 설정 상한 240°F (115.6℃), 장비 요구 사항에 따라 조정 가능.
- 조정 방법:
일자 드라이버로 전면 조정 나사를 돌립니다.: 더 높은 온도에서는 시계 방향으로, counterclockwise for lower.
Set target temperature referring to scale dial (adjustable range 100°F~240°F).
Recommended setting 10–15°F lower than equipment maximum withstand temperature for safety margin.
5.2 Functional Test Steps
- 재설정 작업: Press red reset button to release safety lockout before first power-on (factory locked state).
- 전원 켜기 테스트: Switch on power and check indicator light (장착된 경우) operates normally.
- Temperature Rise Test: Start system and verify controller automatically trips output when temperature reaches set point.
- Reset Verification: After temperature drops to safe range (set point −10°F below), press reset button and confirm system resumes operation.
- Repeat Test: Repeat 2–3 cycles to ensure reliable tripping and normal reset performance.
- 설치 금지 & 유지 관리 지침
6.1 설치 금지
❌ Do not install controller in humid, dusty or corrosive gas environment.
❌ 전구와 고온 표면의 직접적인 접촉을 방지하세요 (>250°F) 손상을 피하기 위해.
❌ AC24V 또는 DC 전원을 사용하지 마세요.; 120V/240V AC만 허용됩니다..
❌ 출력 접점에 과부하가 걸리지 않도록 하십시오.; 정격 전류를 초과해서는 안 됩니다. (8A@120V, 5.1A@240V).
6.2 유지 관리 권장 사항
| 유지보수 항목 | 주기 | 운영 내용 |
| 온도 전구 청소 | 모든 6 개월 | 전구 표면에 스케일과 부식이 있는지 확인하세요.; 필요한 경우 부드러운 천으로 닦으십시오. |
| 터미널 검사 | 모든 1 년도 | 배선의 느슨함과 산화 여부를 점검하십시오.; 나사를 다시 조이세요 |
| 기능 테스트 | 모든 1 년도 | 정상 작동을 위한 온도 제어 및 재설정 기능 테스트 |
| 컨트롤러 외관 확인 | 계간지 | 하우징에 손상 및 물 유입 흔적이 있는지 검사하세요. |
6.3 일반적인 설치 문제 해결
| 결함 현상 | 가능한 원인 | 해결책 |
| 부정확한 온도 조절 | 전구가 액체에 완전히 담기지 않음 | 완전한 액체 접촉을 보장하기 위해 전구를 다시 설치하십시오. |
| 컨트롤러가 작동하지 않음 | 재설정 버튼을 누르지 않음 | 시스템 냉각 후 빨간색 재설정 버튼을 누르세요. |
| 빈번한 접촉 연소 | 부하 전류가 정격을 초과함 | 더 높은 용량의 컨트롤러를 교체하거나 중간 릴레이를 추가하세요. |
| 모세관 누출 | 설치 중 과도한 굽힘 | 전구를 교체하고 모세관 보호 장치로 다시 설치 |
- 설치 요약
Honeywell L4008E1255의 설치는 안전 우선 원칙을 따라야 합니다. & 표준 작동, 아래와 같은 핵심 단계:
- 시스템 안전을 보장하기 위한 전원 끄기 준비.
- 컨트롤러 본체를 벽이나 파이프에 수직 또는 수평 방향으로 장착합니다..
- 정확한 감지를 위해 Thermowell 또는 직접 담금을 통해 온도 전구를 설치하십시오..
- 전원 공급 장치와 정격 부하가 일치하는 표준 전기 배선.
- 온도 제어 및 재설정 기능을 검증하기 위한 시운전 및 테스트 완료.
설치 후, 설치 날짜 기록, 향후 유지 관리 및 문제 해결 참조를 위해 온도 및 테스트 결과 설정.