Danfoss ICAD600A 027H9065 Stepper Electric Actuator

제품 포지셔닝:Stepper electric actuator (power head) for Danfoss ICM motorized valves in refrigeration systems, old A-series, obsolete ✅ Basic Information Model:ICAD600A, Order code 027H9065 Brand:댄포스 (Refrigeration segment) Compatible valve bodies:ICM20 / ICM25 / ICM32 motorized regulating valves, also capable of driving CVE pilot valves Construction:Stepper motor driven, with valve position feedback, local keypad & 표시하다, ...

  • 제품 세부정보

제품 포지셔닝:스테퍼 electric actuator (power head) ~을 위한 댄포스 ICM motorized 밸브 in refrigeration systems, old A-series, 쓸모없는

✅ 기본정보

모델:ICAD600A, Order code 027H9065

상표:댄포스 (Refrigeration segment)

Compatible valve bodies:ICM20 / ICM25 / ICM32 motorized regulating valves, also capable of driving CVE pilot valves

건설:Stepper motor driven, with valve position feedback, local keypad & 표시하다, manual override function

기원:폴란드

⭐ 핵심 전기 사양

전원공급장치:24DC에서 (+10% / -15%), DC power only

Max current:1.2 에이

Control signals:

아날로그 입력:0/4-20 엄마, 0/2-10 DC에서

아날로그 출력:0/4-20 엄마 (밸브 위치 피드백)

3-channel NPN digital outputs (valve position status, 잘못, 등.)

Passive dry contact digital input

보호 등급:IP67

주변 온도:-30 ℃ ~ +50 ℃

주택:Aluminum body + PBT top cover, 순중량 약. 1.2 kg

커넥터:M12 circular connector (4-pin power + 8-pin signal). Pre-assembled cables available as options: 027H0426 (1.5중), 027H0438 (3중), 027H0427 (10중), 027H0435 (15중)

🧩 Control Modes

  1. Analog modulation:Continuous regulation via EKC347 level controller or PLC with 4-20mA / 0-10V 출력
  2. Digital position control
  3. Local panel manual open, close and calibration
  4. Compatible with ICAD-UPS power-fail hold module for safe position protection upon power loss

🔁 Replacement Options (주요 섹션)

Factory successor:ICAD600B (주문 번호. 027H0485). 기계적으로 상호 교환 가능, upgraded with OLED screen, Bluetooth APP and RS485 communication. 하지만, wiring logic and parameter programming need verification and adaptation; direct blind replacement is not permitted.

Similar obsolete parts within the same series:027H9075 (ICAD600A, identical hardware to 027H9065, only version/config difference, also obsolete)

⚠️ Fault & 유지보수 노트

일반적인 결함:Loss of communication, valve position non-following, 모터 실속, blank display, 물 유입 & oxidation at M12 connectors

구경 측정:Full zero & full stroke auto-calibration must be performed after replacement or disassembly

중요한:24V AC must NOT be applied directly. A dedicated isolated 24V DC power supply is required; voltage drop shall be calculated for long wiring runs

📎 Application Scope

Industrial ammonia refrigeration, CO₂ transcritical systems, large fluorinated refrigerant chiller packages, used for continuous regulation of liquid level, pressure and superheat (pump recirculation, evaporator, condenser, economizer circuits)

📋 Supporting Documentation

Manuals:AI000086409336 (General ICAD600/900 manual), AN000086415021 (배선 & commissioning manual)

ICAD600A (027H9065) → ICAD600B (027H0485) Retrofit Checklist

핵심 결론:기계적으로 호환 가능, fits directly on existing ICM20/25/32 valve bodies. But M12 pin assignment, parameter menu and fault logic differ; the old cable cannot be plugged in and powered up directly.

  1. BOM
범주목비고
본체ICAD600B, 주문 번호. 027H0485Replaces 027H9065, compatible with ICM20/25/32
Optional pre-made cable027H0426 (1.5중) / 027H0438 (3중) / 027H0427 (10중)B-series dedicated M12 power + M12 signal cable. Old A-series cables have different pinouts and reuse is not recommended
UPS power-fail hold027H0388 ICAD UPS moduleCompatible with A & 비; B has revised logic for UPS detection pin
소모품Molycote 55 유지, O-링For valve stem magnetic coupling seal; lubrication mandatory after disassembly to prevent water ingress failure
도구2.5mm hex key, 토크 렌치, 멀티미터, 절연 테이프Installation torque: 3N 방향 m, tighten diagonally and evenly
  1. Mechanical Retrofit (Low Risk)

✅ Compatibility:Valve seat, magnetic coupling and mounting screw positions match completely; no modification to valve body or bracket required

⚠️ Operating Procedure

  1. Manually set valve to mid-position first (to prevent valve stem detachment after actuator removal)
  2. Loosen the 3 fixing hex screws and lift the old ICAD600A vertically
  3. Inspect magnetic coupling and O-rings on valve body for damage, ice buildup or heavy contamination; remove old grease residue
  4. Apply Molycote 55 to O-ring groove and O-ring, align magnetic coupling and lower ICAD600B vertically
  5. Tighten the 3 screws diagonally at a controlled torque of 3N·m; avoid one-sided over-tightening
  6. Verify housing sealing surface is fully seated without warping

위험 포인트:Misaligned magnetic coupling or missing grease → water ingress, magnetic coupling slip and valve position drift later

  1. Electrical Retrofit (비판적인! Pinout Incompatibility, Highest Risk Area)

ICAD600A:M12 power 3-pin; M12 signal 7-pin

ICAD600B:M12 power 4-pin; M12 signal 8-pin; independent 4-pin M12 RS485 port exclusive to B-series

4-pin M12 Power Connector (비)

Pin I Black:Fail-safe 19-24V DC (UPS backup power, 선택 과목)

Pin II White:Main 24V DC+

Pin III Brown:24DC에서(접지)

Pin IV Blue:UPS status feedback signal (Not available on A-series)

8-pin M12 Signal Connector (비)

Pin A Black:Common terminal for fault output (NPN)

Pin B Brown:Fully open limit output

Pin C Red:Fully closed limit output

Pin D Orange:신호 GND

Pin E Yellow:아날로그 입력 (0/4-20mA /0/2-10V)

Pin F Pink:Analog feedback output (valve position 0/4-20mA)

Pin G Grey:Digital input DI (할 수 있게 하다 / Safety close)

Pin H Violet:예약된

Comparison with A: Wire color sequence for digital outputs and analog input differs. Direct plug-in of old cable will burn signal channels or trigger faults.

✅ Two implementation options:

옵션 1: Purchase factory pre-assembled B-series cables, re-terminate wiring at cabinet terminals one-to-one (Recommended for reliable site performance)

옵션 2: Rewire existing cable, re-crimp M12 contacts according to above definition and apply clear marking

Power requirement remains 24VDC SELV isolated power supply, max 1.2A, same as A-series; 24V AC is not supported.

  1. 주인 / Controller Program Modification (EKC347 / PLC)
  2. Analog control loop (4-20mA control)

Control signal range: 0/4-20엄마, 0-10V definition unchanged. B internal input resistance differs; range setting on PLC/EKC side can stay, but valve position feedback reading calibration is recommended.

에이: Valve feedback 4-20mA; B also 4-20mA with improved load capacity up to 500Ω

  1. Digital position signals (Full open, Full close, 잘못)

All three are NPN open-collector outputs with identical function definition. Common terminal pin has changed; PLC input common point wiring must be adjusted accordingly.

  1. Existing EKC347 parameters:

Superheat, liquid level setpoints and PID gains can be retained

Valve body model must be reselected inside B actuator (parameter i26). B will automatically calibrate stroke

  1. RS485 (New for B): Not required if original system has no bus. If bus communication is planned later, Modbus mapping and terminating resistor need to be added.
  2. 시운전 & 교정 절차 (필수적인, Skipping Causes Position Error)
  3. Double-check wiring, power on without load first, check OLED screen (B uses OLED, A uses segment LCD)
  4. Enter parameter menu, set valve body type: ICM20/25/32 (i26) → trigger automatic stroke calibration
  5. Calibration sequence: Auto full close → full open → full close, zero and full stroke recorded
  6. Manual mode test: 열려 있는 / close via local panel, confirm smooth movement without sticking
  7. Auto mode: Apply 4mA / 20mA reference signal, verify linear tracking of valve position feedback
  8. 결함 시뮬레이션: Signal loss, 전력 손실, check fault output and UPS safe position logic
  9. Save parameters and back up configuration (B supports Bluetooth APP commissioning via Danfoss BT tool)

중요한:A-series fault code list cannot be used for B; B alarm system is revised and some alarm definitions are different.

  1. Risk Checklist & 함정 회피
  2. ❌ Plug old A cable directly into B: Pin misalignment → burnt analog channels, power short circuit, A1/A2 alarms
  3. ❌ Skip calibration before commissioning: 제로 드리프트, incomplete closure or incomplete opening
  4. ❌ Omit Molycote 55 애플리케이션: Magnetic coupling water ingress, slip and position loss at low temperature
  5. ❌ Ignore blue UPS pin: Continuous UPS fault alarm on B if blue wire is not connected when UPS module is fitted
  6. ❌ Torque over 3N·m: Housing deformation and seal failure
  7. Acceptance Test Items

공전: Valve position 0%, 50%, 100%, feedback error ≤±2%

동적: Step response test, no oscillation or sticking

Fault conditions: 단선, 전력 손실, 마구간; controller receives fault signal correctly

환경 보호: IP67, proper connector sealing, no condensation ingress in humid conditions

Recurring Faults after ICAD600A (027H9065) → ICAD600B (027H0485) 대사, 원인 & 문제 해결

전제: Most issues originate from incorrect pin wiring, missing calibration, UPS logic difference, 임피던스 / load mismatch. Mechanical seizure of valve body is a pre-existing condition, not a new fault introduced by replacement.

  1. 전원 켜기 오류 (Alarm at power-up, 디스플레이 없음, cyclic reboot)
  2. Blank OLED, no illumination

원인: Wrong M12 power pin assignment, reversed 24VDC polarity, 부족한 전력 용량, 과도한 전압 강하, 물 유입 & oxidation at M12 plug

문제 해결: Measure Pin II(+) & III(-) 멀티미터 포함; confirm DC24V not AC24V; measure voltage at actuator end for long cable runs

  1. Cyclic reboot & flashing screen after power-up

원인: Blue UPS Pin IV left floating without connection; old A-type UPS module mismatched; high ripple power supply

치료: Disable UPS detection in menu if UPS module is not used; do not leave pin floating and tolerate constant alarm

  1. Power fault alarm immediately after energization (B exclusive alarm)

원인: Forced reuse of old cable, cross connection between power and signal lines, internal short in connector

  1. Calibration Related Faults (Most frequent after swap)
  2. Auto-calibration aborted, stops mid-cycle, stroke error alarm

트리거:

Misaligned magnetic coupling, coupling slip, O-ring binding; valve stem offset during assembly

오염, ice plug or spool seizure in valve body (A may tolerate marginal friction while B has tighter detection)

Incorrect mounting torque (over-tightened coupling or insufficient torque leading to slip)

Wrong valve body selection at parameter i26 (selected larger ICM size)

징후: Calibration halts halfway and cannot complete full close → full open travel

  1. Calibration successful, but valve fails to close tight / over-travel / cannot reach full open

원인: Spool was not set to mid-position before calibration; worn seat, foreign debris, abnormal magnetic coupling gap

특징: 4mA command does not correspond to 0% feedback, 20mA cannot reach 100%

  1. Control Signal Loop Faults (4-20엄마 / 0-10다섯)
  2. Control signal applied, valve stationary, position reading fixed

원인: Wrong connection at analog input Pin E; signal GND not common with controller GND; signal type mismatch (menu set for voltage while current signal is applied, 또는 그 반대)

주요 내용: B input impedance differs from A; verify drive capability of EKC347 or PLC analog output

  1. Inaccurate / drifting feedback, feedback inconsistent with actual valve position

원인: Wrong wiring at feedback Pin F; feedback loop overloaded resistance, loose GND connection, incomplete calibration

징후: Controller reading differs from local actuator display

  1. Valve oscillation, small continuous hunting

원인: PID parameters inherited from A; B stepper response speed differs; poor shielding earthing causing interference; signal cable routed together with power cable

메모: PID tuned for A often oscillates directly on B and requires fine adjustment

  1. Digital Output Faults (Full Open / Full Close / Fault NPN)
  2. PLC fails to receive full-open / full-close signal or signal stays permanently ON

원인: 에이 & B have different common terminal definition for digital outputs. Reused old cable leads to wrong common connection; reversed external supply for NPN loop

임계점: B’s three DO channels share Pin A (fault common), which is completely different from A

  1. Persistent fault output with normal valve operation

High incidence: UPS detection enabled without UPS module fitted, B interprets status as UPS fault; UPS function not disabled in menu

  1. UPS Power-Fail Hold Specific Faults (with 027H0388 fitted)
  2. Fails to move to safe position on power loss or constant UPS alarm at startup

원인: B blue Pin IV on power plug is UPS status feedback, which does not exist on A; legacy UPS wiring incompatible; aged UPS battery

함정: A UPS only required power feed; B requires both power and status feedback wire otherwise permanent alarm

  1. 통신 결함 (RS485 모드버스, New for B)
  2. No Modbus data read, 간헐적인 의사소통

원인: Wrong wiring on 4-pin M12 communication port; 종단 저항 없음; 중복된 주소; 일치하지 않는 전송 속도; poor shield earthing

팁: Bus port can be left unconnected if unused for analog control; avoid accidental signal connection to this port

  1. 저온 / Site Environmental Faults (Common for NH₃ & CO₂ transcritical systems)
  2. Random position loss and slip at low temperature without fixed alarm

원인: Molycote 55 grease not applied during assembly; O-링이 없거나 손상됨, moisture entering magnetic coupling and freezing

특징: Calibration passes at ambient temperature, random drift when cooled, temporary recovery after reboot

  1. Condensation inside connector, intermittent sporadic faults

원인: Aged old M12 connector seal; poor crimp sealing after reworking cable, IP67 rating compromised

  1. Misleading Apparent Faults (Logic Difference, Not Actual Failure)
  2. Different valve movement at identical 4mA setpoint compared with A

Not a fault: B stroke algorithm, dead band and stepper speed parameters are independent; loop matching is required

  1. Alarm codes not found in A manual

B alarm table rewritten; many A alarm IDs do not exist on B

  1. Different local keypad operation logic

Menu navigation and manual mode entry sequence changed; commissioning personnel may mistake for actuator malfunction

  1. Fast Troubleshooting Sequence (On-site Priority)
  2. Verify every M12 pin assignment (힘, 신호, UPS) first to rule out miswiring
  3. 전원 공급 확인: Stable 24V DC, ≥22V at actuator terminals under load
  4. Check menu settings: 신호 유형 (현재의 / 전압), valve body model i26, UPS enable / disable
  5. Run a complete auto-calibration again
  6. Check common ground and shield bonding, 간섭을 제거하다
  7. Test in manual mode alone to isolate whether fault lies in actuator hardware or upstream controller signal

Danfoss ICAD Stepper Electric Actuator Full Model & Order Code List (For ICM Refrigeration Valves)

설명: ICAD = Stepper motor actuator for ICM / ICMTS regulating valves and CVE pilot valves. Divided into A-series (오래된, 쓸모없는), B-series (새로운, 활동적인), TS transcritical dedicated variant. All models run on 24V DC.

  1. A 시리즈 (구세대, 027H9xxxx, 더 이상 사용되지 않음)
모델주문 코드Compatible Valve비고
ICAD600A027H9065ICM20/25/32현재 모델, segment LCD, no RS485, no Bluetooth
ICAD600A027H9075ICM20/25/32Same ICAD600A, version variation
ICAD600A027H9120ICM20/25/32동일한 사양
ICAD600A-TS027H9078ICMTS20~ICMTS80CO₂ transcritical dedicated
ICAD900A027H9101Large bore ICMTSCO₂ transcritical dedicated
ICAD1200A027H9077ICM40/50/65/100/125/150High torque A version
ICAD1200A027H9122ICM40/50/65/100/125/150Same ICAD1200A
  1. B-series (현재 활성, 027H04xx, OLED + Bluetooth, 옵션 RS485 / 이더넷)

ICAD600B (For ICM20 / ICM25 / ICM32)

모델주문 코드구성
ICAD600B027H0485표시하다, Bluetooth, RS485 (가장 일반적인, direct replacement for A)
ICAD600B027H0486표시하다, Bluetooth, 이더넷
ICAD600B027H0488디스플레이 없음, Bluetooth, RS485
ICAD600B027H0489디스플레이 없음, Bluetooth, 이더넷

ICAD1200B (For ICM40~ICM150)

모델주문 코드구성
ICAD1200B027H0490표시하다, Bluetooth, RS485
ICAD1200B027H0491표시하다, Bluetooth, 이더넷
ICAD1200B027H0492디스플레이 없음, Bluetooth, 이더넷
ICAD1200B027H0493디스플레이 없음, Bluetooth, RS485

ICAD600B-TS:CO₂ transcritical dedicated, separate order family for ICMTS valve bodies

  1. 부속품 & Cable Order Codes (ICAD compatible)
설명주문 코드메모
ICAD UPS power-fail hold module027H0388Works with A & 비 (B has UPS status detection pin)
Pre-assembled cable 1.5m027H0426M12 power + M12 signal, B-series only
Pre-assembled cable 3m027H0438M12 power + M12 signal
Pre-assembled cable 10m027H0427M12 power + M12 signal
Pre-assembled cable 15m027H0435M12 power + M12 signal
M12 connector spare kit027H0430Signal plug spare part
Protective dust cap027H0431Top cover protection for actuator
  1. 빠른 선택 참조

ICM20 / ICM25 / ICM32 → ICAD600A (더 이상 사용되지 않음) / ICAD600B (대사)

ICM40~ICM150 → ICAD1200A (더 이상 사용되지 않음) / ICAD1200B (대사)

ICMTS (CO₂ transcritical) → ICAD600A-TS / ICAD900A / ICAD600B-TS

  1. 중요 사항
  2. All A-series (027H9xxx) 단종되었습니다. B-series is preferred for replacement. 기계적으로 상호 교환 가능, pin assignment incompatible; old cable must not be plugged directly.
  3. B-series: RS485 variant widely used for site retrofit; Ethernet variant for building automation and remote SCADA
  4. TS variants have special internal seals and firmware tuned for CO₂ transcritical operation; standard ICAD600B cannot substitute directly
  5. All ICAD actuators run on 24V DC. 24V AC supply is strictly prohibited