제품 포지셔닝:스테퍼 electric actuator (power head) ~을 위한 댄포스 ICM motorized 밸브 in refrigeration systems, old A-series, 쓸모없는
✅ 기본정보
모델:ICAD600A, Order code 027H9065
상표:댄포스 (Refrigeration segment)
Compatible valve bodies:ICM20 / ICM25 / ICM32 motorized regulating valves, also capable of driving CVE pilot valves
건설:Stepper motor driven, with valve position feedback, local keypad & 표시하다, manual override function
기원:폴란드
⭐ 핵심 전기 사양
전원공급장치:24DC에서 (+10% / -15%), DC power only
Max current:1.2 에이
Control signals:
아날로그 입력:0/4-20 엄마, 0/2-10 DC에서
아날로그 출력:0/4-20 엄마 (밸브 위치 피드백)
3-channel NPN digital outputs (valve position status, 잘못, 등.)
Passive dry contact digital input
보호 등급:IP67
주변 온도:-30 ℃ ~ +50 ℃
주택:Aluminum body + PBT top cover, 순중량 약. 1.2 kg
커넥터:M12 circular connector (4-pin power + 8-pin signal). Pre-assembled cables available as options: 027H0426 (1.5중), 027H0438 (3중), 027H0427 (10중), 027H0435 (15중)
🧩 Control Modes
- Analog modulation:Continuous regulation via EKC347 level controller or PLC with 4-20mA / 0-10V 출력
- Digital position control
- Local panel manual open, close and calibration
- Compatible with ICAD-UPS power-fail hold module for safe position protection upon power loss
🔁 Replacement Options (주요 섹션)
Factory successor:ICAD600B (주문 번호. 027H0485). 기계적으로 상호 교환 가능, upgraded with OLED screen, Bluetooth APP and RS485 communication. 하지만, wiring logic and parameter programming need verification and adaptation; direct blind replacement is not permitted.
Similar obsolete parts within the same series:027H9075 (ICAD600A, identical hardware to 027H9065, only version/config difference, also obsolete)
⚠️ Fault & 유지보수 노트
일반적인 결함:Loss of communication, valve position non-following, 모터 실속, blank display, 물 유입 & oxidation at M12 connectors
구경 측정:Full zero & full stroke auto-calibration must be performed after replacement or disassembly
중요한:24V AC must NOT be applied directly. A dedicated isolated 24V DC power supply is required; voltage drop shall be calculated for long wiring runs
📎 Application Scope
Industrial ammonia refrigeration, CO₂ transcritical systems, large fluorinated refrigerant chiller packages, used for continuous regulation of liquid level, pressure and superheat (pump recirculation, evaporator, condenser, economizer circuits)
📋 Supporting Documentation
Manuals:AI000086409336 (General ICAD600/900 manual), AN000086415021 (배선 & commissioning manual)
ICAD600A (027H9065) → ICAD600B (027H0485) Retrofit Checklist
핵심 결론:기계적으로 호환 가능, fits directly on existing ICM20/25/32 valve bodies. But M12 pin assignment, parameter menu and fault logic differ; the old cable cannot be plugged in and powered up directly.
- BOM
| 범주 | 목 | 비고 |
| 본체 | ICAD600B, 주문 번호. 027H0485 | Replaces 027H9065, compatible with ICM20/25/32 |
| Optional pre-made cable | 027H0426 (1.5중) / 027H0438 (3중) / 027H0427 (10중) | B-series dedicated M12 power + M12 signal cable. Old A-series cables have different pinouts and reuse is not recommended |
| UPS power-fail hold | 027H0388 ICAD UPS module | Compatible with A & 비; B has revised logic for UPS detection pin |
| 소모품 | Molycote 55 유지, O-링 | For valve stem magnetic coupling seal; lubrication mandatory after disassembly to prevent water ingress failure |
| 도구 | 2.5mm hex key, 토크 렌치, 멀티미터, 절연 테이프 | Installation torque: 3N 방향 m, tighten diagonally and evenly |
- Mechanical Retrofit (Low Risk)
✅ Compatibility:Valve seat, magnetic coupling and mounting screw positions match completely; no modification to valve body or bracket required
⚠️ Operating Procedure
- Manually set valve to mid-position first (to prevent valve stem detachment after actuator removal)
- Loosen the 3 fixing hex screws and lift the old ICAD600A vertically
- Inspect magnetic coupling and O-rings on valve body for damage, ice buildup or heavy contamination; remove old grease residue
- Apply Molycote 55 to O-ring groove and O-ring, align magnetic coupling and lower ICAD600B vertically
- Tighten the 3 screws diagonally at a controlled torque of 3N·m; avoid one-sided over-tightening
- Verify housing sealing surface is fully seated without warping
위험 포인트:Misaligned magnetic coupling or missing grease → water ingress, magnetic coupling slip and valve position drift later
- Electrical Retrofit (비판적인! Pinout Incompatibility, Highest Risk Area)
ICAD600A:M12 power 3-pin; M12 signal 7-pin
ICAD600B:M12 power 4-pin; M12 signal 8-pin; independent 4-pin M12 RS485 port exclusive to B-series
4-pin M12 Power Connector (비)
Pin I Black:Fail-safe 19-24V DC (UPS backup power, 선택 과목)
Pin II White:Main 24V DC+
Pin III Brown:24DC에서(접지)
Pin IV Blue:UPS status feedback signal (Not available on A-series)
8-pin M12 Signal Connector (비)
Pin A Black:Common terminal for fault output (NPN)
Pin B Brown:Fully open limit output
Pin C Red:Fully closed limit output
Pin D Orange:신호 GND
Pin E Yellow:아날로그 입력 (0/4-20mA /0/2-10V)
Pin F Pink:Analog feedback output (valve position 0/4-20mA)
Pin G Grey:Digital input DI (할 수 있게 하다 / Safety close)
Pin H Violet:예약된
Comparison with A: Wire color sequence for digital outputs and analog input differs. Direct plug-in of old cable will burn signal channels or trigger faults.
✅ Two implementation options:
옵션 1: Purchase factory pre-assembled B-series cables, re-terminate wiring at cabinet terminals one-to-one (Recommended for reliable site performance)
옵션 2: Rewire existing cable, re-crimp M12 contacts according to above definition and apply clear marking
Power requirement remains 24VDC SELV isolated power supply, max 1.2A, same as A-series; 24V AC is not supported.
- 주인 / Controller Program Modification (EKC347 / PLC)
- Analog control loop (4-20mA control)
Control signal range: 0/4-20엄마, 0-10V definition unchanged. B internal input resistance differs; range setting on PLC/EKC side can stay, but valve position feedback reading calibration is recommended.
에이: Valve feedback 4-20mA; B also 4-20mA with improved load capacity up to 500Ω
- Digital position signals (Full open, Full close, 잘못)
All three are NPN open-collector outputs with identical function definition. Common terminal pin has changed; PLC input common point wiring must be adjusted accordingly.
- Existing EKC347 parameters:
Superheat, liquid level setpoints and PID gains can be retained
Valve body model must be reselected inside B actuator (parameter i26). B will automatically calibrate stroke
- RS485 (New for B): Not required if original system has no bus. If bus communication is planned later, Modbus mapping and terminating resistor need to be added.
- 시운전 & 교정 절차 (필수적인, Skipping Causes Position Error)
- Double-check wiring, power on without load first, check OLED screen (B uses OLED, A uses segment LCD)
- Enter parameter menu, set valve body type: ICM20/25/32 (i26) → trigger automatic stroke calibration
- Calibration sequence: Auto full close → full open → full close, zero and full stroke recorded
- Manual mode test: 열려 있는 / close via local panel, confirm smooth movement without sticking
- Auto mode: Apply 4mA / 20mA reference signal, verify linear tracking of valve position feedback
- 결함 시뮬레이션: Signal loss, 전력 손실, check fault output and UPS safe position logic
- Save parameters and back up configuration (B supports Bluetooth APP commissioning via Danfoss BT tool)
중요한:A-series fault code list cannot be used for B; B alarm system is revised and some alarm definitions are different.
- Risk Checklist & 함정 회피
- ❌ Plug old A cable directly into B: Pin misalignment → burnt analog channels, power short circuit, A1/A2 alarms
- ❌ Skip calibration before commissioning: 제로 드리프트, incomplete closure or incomplete opening
- ❌ Omit Molycote 55 애플리케이션: Magnetic coupling water ingress, slip and position loss at low temperature
- ❌ Ignore blue UPS pin: Continuous UPS fault alarm on B if blue wire is not connected when UPS module is fitted
- ❌ Torque over 3N·m: Housing deformation and seal failure
- Acceptance Test Items
공전: Valve position 0%, 50%, 100%, feedback error ≤±2%
동적: Step response test, no oscillation or sticking
Fault conditions: 단선, 전력 손실, 마구간; controller receives fault signal correctly
환경 보호: IP67, proper connector sealing, no condensation ingress in humid conditions
Recurring Faults after ICAD600A (027H9065) → ICAD600B (027H0485) 대사, 원인 & 문제 해결
전제: Most issues originate from incorrect pin wiring, missing calibration, UPS logic difference, 임피던스 / load mismatch. Mechanical seizure of valve body is a pre-existing condition, not a new fault introduced by replacement.
- 전원 켜기 오류 (Alarm at power-up, 디스플레이 없음, cyclic reboot)
- Blank OLED, no illumination
원인: Wrong M12 power pin assignment, reversed 24VDC polarity, 부족한 전력 용량, 과도한 전압 강하, 물 유입 & oxidation at M12 plug
문제 해결: Measure Pin II(+) & III(-) 멀티미터 포함; confirm DC24V not AC24V; measure voltage at actuator end for long cable runs
- Cyclic reboot & flashing screen after power-up
원인: Blue UPS Pin IV left floating without connection; old A-type UPS module mismatched; high ripple power supply
치료: Disable UPS detection in menu if UPS module is not used; do not leave pin floating and tolerate constant alarm
- Power fault alarm immediately after energization (B exclusive alarm)
원인: Forced reuse of old cable, cross connection between power and signal lines, internal short in connector
- Calibration Related Faults (Most frequent after swap)
- Auto-calibration aborted, stops mid-cycle, stroke error alarm
트리거:
Misaligned magnetic coupling, coupling slip, O-ring binding; valve stem offset during assembly
오염, ice plug or spool seizure in valve body (A may tolerate marginal friction while B has tighter detection)
Incorrect mounting torque (over-tightened coupling or insufficient torque leading to slip)
Wrong valve body selection at parameter i26 (selected larger ICM size)
징후: Calibration halts halfway and cannot complete full close → full open travel
- Calibration successful, but valve fails to close tight / over-travel / cannot reach full open
원인: Spool was not set to mid-position before calibration; worn seat, foreign debris, abnormal magnetic coupling gap
특징: 4mA command does not correspond to 0% feedback, 20mA cannot reach 100%
- Control Signal Loop Faults (4-20엄마 / 0-10다섯)
- Control signal applied, valve stationary, position reading fixed
원인: Wrong connection at analog input Pin E; signal GND not common with controller GND; signal type mismatch (menu set for voltage while current signal is applied, 또는 그 반대)
주요 내용: B input impedance differs from A; verify drive capability of EKC347 or PLC analog output
- Inaccurate / drifting feedback, feedback inconsistent with actual valve position
원인: Wrong wiring at feedback Pin F; feedback loop overloaded resistance, loose GND connection, incomplete calibration
징후: Controller reading differs from local actuator display
- Valve oscillation, small continuous hunting
원인: PID parameters inherited from A; B stepper response speed differs; poor shielding earthing causing interference; signal cable routed together with power cable
메모: PID tuned for A often oscillates directly on B and requires fine adjustment
- Digital Output Faults (Full Open / Full Close / Fault NPN)
- PLC fails to receive full-open / full-close signal or signal stays permanently ON
원인: 에이 & B have different common terminal definition for digital outputs. Reused old cable leads to wrong common connection; reversed external supply for NPN loop
임계점: B’s three DO channels share Pin A (fault common), which is completely different from A
- Persistent fault output with normal valve operation
High incidence: UPS detection enabled without UPS module fitted, B interprets status as UPS fault; UPS function not disabled in menu
- UPS Power-Fail Hold Specific Faults (with 027H0388 fitted)
- Fails to move to safe position on power loss or constant UPS alarm at startup
원인: B blue Pin IV on power plug is UPS status feedback, which does not exist on A; legacy UPS wiring incompatible; aged UPS battery
함정: A UPS only required power feed; B requires both power and status feedback wire otherwise permanent alarm
- 통신 결함 (RS485 모드버스, New for B)
- No Modbus data read, 간헐적인 의사소통
원인: Wrong wiring on 4-pin M12 communication port; 종단 저항 없음; 중복된 주소; 일치하지 않는 전송 속도; poor shield earthing
팁: Bus port can be left unconnected if unused for analog control; avoid accidental signal connection to this port
- 저온 / Site Environmental Faults (Common for NH₃ & CO₂ transcritical systems)
- Random position loss and slip at low temperature without fixed alarm
원인: Molycote 55 grease not applied during assembly; O-링이 없거나 손상됨, moisture entering magnetic coupling and freezing
특징: Calibration passes at ambient temperature, random drift when cooled, temporary recovery after reboot
- Condensation inside connector, intermittent sporadic faults
원인: Aged old M12 connector seal; poor crimp sealing after reworking cable, IP67 rating compromised
- Misleading Apparent Faults (Logic Difference, Not Actual Failure)
- Different valve movement at identical 4mA setpoint compared with A
Not a fault: B stroke algorithm, dead band and stepper speed parameters are independent; loop matching is required
- Alarm codes not found in A manual
B alarm table rewritten; many A alarm IDs do not exist on B
- Different local keypad operation logic
Menu navigation and manual mode entry sequence changed; commissioning personnel may mistake for actuator malfunction
- Fast Troubleshooting Sequence (On-site Priority)
- Verify every M12 pin assignment (힘, 신호, UPS) first to rule out miswiring
- 전원 공급 확인: Stable 24V DC, ≥22V at actuator terminals under load
- Check menu settings: 신호 유형 (현재의 / 전압), valve body model i26, UPS enable / disable
- Run a complete auto-calibration again
- Check common ground and shield bonding, 간섭을 제거하다
- Test in manual mode alone to isolate whether fault lies in actuator hardware or upstream controller signal
Danfoss ICAD Stepper Electric Actuator Full Model & Order Code List (For ICM Refrigeration Valves)
설명: ICAD = Stepper motor actuator for ICM / ICMTS regulating valves and CVE pilot valves. Divided into A-series (오래된, 쓸모없는), B-series (새로운, 활동적인), TS transcritical dedicated variant. All models run on 24V DC.
- A 시리즈 (구세대, 027H9xxxx, 더 이상 사용되지 않음)
| 모델 | 주문 코드 | Compatible Valve | 비고 |
| ICAD600A | 027H9065 | ICM20/25/32 | 현재 모델, segment LCD, no RS485, no Bluetooth |
| ICAD600A | 027H9075 | ICM20/25/32 | Same ICAD600A, version variation |
| ICAD600A | 027H9120 | ICM20/25/32 | 동일한 사양 |
| ICAD600A-TS | 027H9078 | ICMTS20~ICMTS80 | CO₂ transcritical dedicated |
| ICAD900A | 027H9101 | Large bore ICMTS | CO₂ transcritical dedicated |
| ICAD1200A | 027H9077 | ICM40/50/65/100/125/150 | High torque A version |
| ICAD1200A | 027H9122 | ICM40/50/65/100/125/150 | Same ICAD1200A |
- B-series (현재 활성, 027H04xx, OLED + Bluetooth, 옵션 RS485 / 이더넷)
ICAD600B (For ICM20 / ICM25 / ICM32)
| 모델 | 주문 코드 | 구성 |
| ICAD600B | 027H0485 | 표시하다, Bluetooth, RS485 (가장 일반적인, direct replacement for A) |
| ICAD600B | 027H0486 | 표시하다, Bluetooth, 이더넷 |
| ICAD600B | 027H0488 | 디스플레이 없음, Bluetooth, RS485 |
| ICAD600B | 027H0489 | 디스플레이 없음, Bluetooth, 이더넷 |
ICAD1200B (For ICM40~ICM150)
| 모델 | 주문 코드 | 구성 |
| ICAD1200B | 027H0490 | 표시하다, Bluetooth, RS485 |
| ICAD1200B | 027H0491 | 표시하다, Bluetooth, 이더넷 |
| ICAD1200B | 027H0492 | 디스플레이 없음, Bluetooth, 이더넷 |
| ICAD1200B | 027H0493 | 디스플레이 없음, Bluetooth, RS485 |
ICAD600B-TS:CO₂ transcritical dedicated, separate order family for ICMTS valve bodies
- 부속품 & Cable Order Codes (ICAD compatible)
| 설명 | 주문 코드 | 메모 |
| ICAD UPS power-fail hold module | 027H0388 | Works with A & 비 (B has UPS status detection pin) |
| Pre-assembled cable 1.5m | 027H0426 | M12 power + M12 signal, B-series only |
| Pre-assembled cable 3m | 027H0438 | M12 power + M12 signal |
| Pre-assembled cable 10m | 027H0427 | M12 power + M12 signal |
| Pre-assembled cable 15m | 027H0435 | M12 power + M12 signal |
| M12 connector spare kit | 027H0430 | Signal plug spare part |
| Protective dust cap | 027H0431 | Top cover protection for actuator |
- 빠른 선택 참조
ICM20 / ICM25 / ICM32 → ICAD600A (더 이상 사용되지 않음) / ICAD600B (대사)
ICM40~ICM150 → ICAD1200A (더 이상 사용되지 않음) / ICAD1200B (대사)
ICMTS (CO₂ transcritical) → ICAD600A-TS / ICAD900A / ICAD600B-TS
- 중요 사항
- All A-series (027H9xxx) 단종되었습니다. B-series is preferred for replacement. 기계적으로 상호 교환 가능, pin assignment incompatible; old cable must not be plugged directly.
- B-series: RS485 variant widely used for site retrofit; Ethernet variant for building automation and remote SCADA
- TS variants have special internal seals and firmware tuned for CO₂ transcritical operation; standard ICAD600B cannot substitute directly
- All ICAD actuators run on 24V DC. 24V AC supply is strictly prohibited
접촉기,회로 차단기,감지기,인코더,PLC,변환기
















NH42-63-318x560.png)



