이것은 슈나이더 TeSys K series 3-pole miniature AC contactor. 정격 작동 전류는 12A입니다. (AC-3, 440다섯), 코일 전압 110V AC, 그리고 장착되어 있습니다 1 평상시 열림 (1아니요) 보조 접점. It adopts screw-clamp terminals. Designed for motor control, HVAC systems and small industrial equipment. Some legacy variants are discontinued, while this exact model remains in production. For performance upgrade, you may switch to the TeSys D series.
- 모델 코드 설명
| 코드 세그먼트 | 정의 | 자세한 설명 |
| LC1 | 제품 카테고리 | Prefix for Schneider AC contactors; LC stands for contactor, 1 for standard type |
| 케이 | 제품 시리즈 | TeSys K series, miniature compact contactors for low-power control |
| 12 | 정격 작동 전류 | 12에이 (AC-3, 440다섯), suitable for motors up to 5.5kW @ 400V |
| 10 | 보조 접점 구성 | 1아니요 (1 평상시 열림), 0NC (0 평상시 닫힘) |
| 에프 | 코일 전압 코드 | 110V AC 코일 (50/60헤르츠 범용) |
| 7 | 배선 유형 | Screw-clamp terminals, standard mounting |
- 주요 기술 사양
| 범주 | 기술 데이터 | 비고 |
| 기본 특성 | ||
| 제품 유형 | 3-pole AC Contactor | For switching 3-phase circuits |
| 시리즈 | TeSys K | Schneider miniature contactor range |
| 폴란드 | 3피 (L1, L2, L3) | 3-phase control |
| 정격 작동 전류 (~ 안에) | 12에이 (AC-3, 440다섯) | Controls motors up to 5.5kW @ 400V |
| 정격 작동 전압 (우에) | 690뷔와 | Maximum working voltage |
| 제어 코일 전압 (UC) | 110뷔와 (50/60헤르츠) | Universal frequency design |
| 보조 연락처 | 1아니요 (평상시 열림) | For circuit latching or signal feedback |
| 성능 매개변수 | ||
| 정격 작동 주파수 | 1200 주기/시간 (AC-3) | Standard duty for motor control |
| 기계적 내구성 | 10,000,000 운영 | No-load cycles |
| 전기적 내구성 | 1,000,000 운영 (AC-3, 정격 전류) | On-load cycles |
| 코일 전력 소비 | 찾다: 7버지니아, 보유: 2버지니아 | 낮은 전력 소비, 에너지 절약 |
| Pick-up Time | ≤ 60ms | 빠른 응답 |
| Drop-out Time | ≤ 40ms | Fast disconnection |
| 물리적 특성 | ||
| 치수 (폭 × 높이 × 깊이) | 45mm × 85mm × 57mm | 표준 모듈형 디자인, 차지하다 3 module units |
| 설치 | 35mm DIN 레일 / 패널 장착 | EN 준수 50022 |
| 터미널 | 나사 클램프, max wire cross-section: 2.5mm² | Easy installation with reliable connection |
| 무게 | 대략. 180g | Weight per unit |
| 환경 & 인증 | ||
| 작동 온도 | -25°C ~ +55°C | Performance may degrade beyond this range |
| 보관 온도 | -40°C ~ +85°C | |
| 습기 | 5% ~ 95% (비응축) | |
| 유입 방지 | IP20 | 손가락 방지, not for outdoor use |
| 인증 | IEC 60947-4-1, 안에 60947-4-1 | CE marked, complies with international safety standards |
| 수명주기 상태 | ||
| 상태 | Some old models updated; LC1K1210F7 is still in production | Obsolete legacy versions phased out; this model remains available |
- 전체 모델 목록 (TeSys K Series 12A)
| 모델 | 코일 전압 | 보조 연락처 | 배선 유형 | Order Reference | 애플리케이션 |
| LC1K1210F7 | 110뷔와 | 1아니요 | 나사 | LC1K1210F7 | 일반 산업 제어, North American & Asian equipment |
| LC1K1210E7 | 48뷔와 | 1아니요 | 나사 | LC1K1210E7 | 안전 제어 회로, low-voltage systems |
| LC1K1210G7 | 120뷔와 | 1아니요 | 나사 | LC1K1210G7 | North American standard equipment |
| LC1K1210M7 | 220뷔와 | 1아니요 | 나사 | LC1K1210M7 | 유럽 사람 & Asian standard equipment |
| LC1K1210Q7 | 24DC에서 | 1아니요 | 나사 | LC1K1210Q7 | DC 제어 회로, PLC 시스템 |
| LC1K1201F7 | 110뷔와 | 1NC | 나사 | LC1K1201F7 | Circuits requiring Normally Closed feedback |
| LC1K1210U7 | 240뷔와 | 1아니요 | 나사 | LC1K1210U7 | Heavy-duty industrial equipment |
| LC1K1210V7 | 400뷔와 | 1아니요 | 나사 | LC1K1210V7 | 고전압 제어 회로 |
- 대사 & 브랜드 간 등가물
4.1 Original Manufacturer Replacements
| 원래 모델 | 교체 모델 | 이유 | 호환성 |
| LC1K1210F7 | LC1K1210F7 | Same model continuously produced | 완벽하게 호환됨, 직접 교체 |
| LC1D1210F7 | Upgrade to TeSys D series with enhanced performance | Dimensionally compatible, 향상된 기능 | |
| LC1E1210F7 | Economy version for cost optimization | 비슷한 성능, 저렴한 비용 |
4.2 Cross-Brand Compatible Products
| 상표 | 모델 | 매칭레벨 | 비고 |
| 씨줄 | A12-30-10*110V | 95% | Same dimensions and performance |
| 지멘스 | 3RT2015-1BB41 | 90% | Identical auxiliary contact configuration |
| 르그랑 | 8860 | 90% | Different terminal design |
| 친트 (중국) | CJX2-1210*110V | 85% | Cost-effective with complete certifications |
- 애플리케이션 & 일반적인 경우
5.1 권장 애플리케이션
모터 제어: Direct start/stop for 3-phase asynchronous motors below 5.5kW
HVAC 시스템: Control of air conditioning compressors, fans and water pumps, small central air-conditioning units
산업 자동화: PLC control circuits, 컨베이어, packaging machinery and other small equipment
상업용 건물: Elevator door operators, fire safety equipment and lighting control
Agricultural Equipment: Irrigation pumps and greenhouse ventilation systems
5.2 권장되지 않는 애플리케이션
High-frequency cycling: Operating frequency over 1200 주기/시간. TeSys D series is recommended.
고전력 모터: Motors exceeding 5.5kW @ 400V. Select higher-rated contactors.
Outdoor humid environments: IP20 protection is insufficient; additional enclosure protection required.
Explosive hazardous areas: Explosion-proof contactors must be used.
5.3 일반적인 적용 사례
사례 1: Small Injection Molding Machine
장비: 3kW hydraulic pump motor for injection molding machine
문제: Original contactor was bulky and limited cabinet space
해결책: Install LC1K1210F7 together with overload relay
결과: 50% 공간 절약, simpler control circuit and lower failure rate
사례 2: Hospital Central Air-Conditioning System
장비: 4kW fan motors in parallel operation
Requirements: 저소음, low power consumption and high reliability
해결책: Adopt LC1K1210F7 with Schneider EOCR overload protection
결과: 15% 에너지 절약, stable operation and reduced maintenance cost
- 문제 해결 & 유지보수 가이드
6.1 일반적인 결함 & 솔루션
| 결함 현상 | 가능한 원인 | Remedial Actions |
| Coil fails to pull in | 1. No voltage or incorrect coil voltage | 1. Verify power voltage matches coil rating |
| 2. 구운 코일 | 2. 코일 저항 측정; replace if open-circuited | |
| 3. Open control circuit | 3. Check wiring and components in control circuit | |
| 4. 기계적 방해 | 4. Clean iron core, inspect springs and sliding parts | |
| 장착 후 소음이 심함 | 1. 깨진 쉐이딩 코일 | 1. Replace core assembly |
| 2. Dust/rust on core surface | 2. Clean core contact surface | |
| 3. Uneven mounting | 3. Reinstall and level the unit | |
| 4. Undervoltage supply | 4. Ensure supply voltage within 卤10% tolerance | |
| Main contacts burned | 1. 과부하 전류 | 1. Replace with higher-rated contactor |
| 2. Frequent cycling | 2. Optimize control logic to reduce switching frequency | |
| 3. Poor arc suppression | 3. Install surge suppressor | |
| 4. Fatigued contact springs | 4. Replace contact assembly | |
| Auxiliary contact malfunction | 1. Burned contacts | 1. 보조 접점 모듈 교체 |
| 2. 느슨한 배선 | 2. 단자 나사를 다시 조이세요 | |
| 3. Linkage mechanism fault | 3. Inspect linkage; 필요한 경우 교체 |
6.2 Maintenance Procedures
- Monthly Routine Inspection
Check appearance for damage or discoloration
Inspect terminals for looseness and overheating signs
Test pull-in and drop-out action for smooth operation and abnormal noise
- Annual Preventive Maintenance
Power off and clean surface with dry soft cloth
Inspect contact wear; replace if wear depth exceeds 1mm
Measure coil resistance to confirm normal status
Lubricate moving parts with small amount of silicone-based grease
- 교체주기
Standard operating conditions: 5 ~ 8 연령
High-frequency cycling: 2 ~ 3 연령
가혹한 환경 (고온 / 높은 습도): 1 ~ 2 연령
6.3 Quick Troubleshooting Tips
For LC1K miniature contactors rated 12A for motor control
Check voltage first if coil fails to energize; check core for abnormal noise
Replace unit when contacts burn or auxiliary contacts fail
Regular inspection ensures safety; replace after 5 years service life
- 선택 지침
- 현재 등급: Select current ≥ 1.2 times motor rated current. 12A is suitable for motors below 5.5kW.
- 코일 전압: Match coil voltage with control circuit voltage. Common ratings: 24DC에서, 110뷔와, 220뷔와.
- 보조 연락처: 1NO for latching; 1NC for interlock; 1NO+1NC for complex control.
- 배선 유형: Screw terminals for fixed installation; spring terminals for frequent rewiring.
- Replacement Rule: Prioritize same-series products; verify dimensions and mounting when switching to other series.
접촉기,회로 차단기,태양광 인버터,전기 계량기,태양 전지