Schneider TM3AI8 Analog Input Expansion Module

Modicon TM3 series 8-channel analog input expansion module, 나사식 터미널 버전; spring terminal variant: TM3AI8G ✅ Model Definition TM3: Expansion I/O series for M2xx PLCs AI: 아날로그 입력 8: 8 channels TM3AI8: 나사 터미널; TM3AI8G: Spring-cage terminals. 동일한 전기 매개변수, only terminal construction differs. ✅ Compatible PLC CPUs Modicon M221 / M241 / M251 / ...

  • 제품 세부정보

Modicon TM3 series 8-channel analog input expansion module, 나사식 터미널 버전; spring terminal variant: TM3AI8G

✅ Model Definition

TM3: Expansion I/O series for M2xx PLCs

일체 포함: 아날로그 입력

8: 8 채널

TM3AI8: 나사 터미널; TM3AI8G: Spring-cage terminals. 동일한 전기 매개변수, only terminal construction differs.

✅ Compatible PLC CPUs

Modicon M221 / M241 / M251 / M262. Programming software: EcoStruxure Machine Expert (formerly SoMachine)

✅ Key Technical Specifications

목매개변수
Number of channels8 single-ended analog inputs
ADC resolution12-조금 (11 조금 + 서명 비트), Σ-Δ sampling
Signal types (configurable per channel)전압: 0~10V, -10~+10V
현재의: 0~20mA, 4~20mA, extended range modes available
입력 임피던스Voltage ≥1MΩ; Current ≤50Ω
Overload withstand맥스. 13V for voltage; 맥스. 40mA for current
정확성 (25℃)±0.2% full scale, temperature drift ±0.01%FS/℃
Sampling time1ms per enabled channel; Total conversion time = 1ms + 1채널당 ms + PLC scan time
전원공급장치DC24V module supply
설치DIN 레일, cascaded via TM3 backplane bus

⚠️ Critical Warning: Hardware wiring (voltage/current) must match software configuration. Configuring a voltage channel as current mode will burn the module circuit directly.

✅ Typical Applications

Acquire signals from pressure transmitters, 온도 트랜스미터, level sensors, flow meters, load cells, potentiometers and other sensors. Used in packaging machinery, 공조, production lines and small process control systems.

✅ Wiring Guidelines

  1. All inputs are single-ended; differential input is not supported.
  2. 현재 신호: Wire 4-20mA loop of transmitter directly to AI+ and AI-.
  3. 전압 신호: Connect sensor voltage output to AI+ and AI-.
  4. Analog ground shall be bonded with PLC power ground to reduce interference. Use shielded cable for long analog runs with single-end grounding.

✅ Diagnostics & 오류 코드 (IBStatus Status Byte)

Status Code설명
0정상, signal within range
5Over-range high (input too high)
6Under-range / 단선 (alarm at 0mA under 4-20mA mode, 단선 감지)
7Module hardware fault
94~20mA low extended range (1.2~3.99mA)

메모: When 4-20mA channel is open-circuit with no wiring, the module reads the minimum value by default and diagnostic byte = 6. This is normal wire-break detection. Under 0~20mA mode, open circuit reads 0 without this alarm.

✅ Alternative Selection Options

  1. 동일 시리즈 교체: TM3AI8G (spring terminals for fast field wiring)
  2. 국내 호환 대안: Inovance AM600/AM400 analog input modules, Xinje XL series AI modules
  3. Upgrade for more channels: Select other TM3 AI modules as required. Observe the maximum TM3 expansion limit for M2xx PLCs.

✅ Maintenance & Second-hand Inspection Checklist

  1. Visual check: Backplane bus latches intact, terminal block free of burn marks.
  2. Power-up test: PLC recognizes module, module LED status normal.
  3. Channel test: Inject voltage/current reference signal, read raw values and verify linearity.
  4. Firmware: TM3 analog module firmware V29, upgradable in Machine Expert.
  5. 버스: TM3 module cascade order must not be changed. Poor backplane contact triggers I/O bus fault.

✅ HS 코드 참조

PLC analog I/O expansion module, 85371011 (Programmable controller input/output module). Final classification subject to customs broker and local customs ruling.

✅ Program Migration Notes

Upgrade from legacy TM2 AI modules to TM3AI8: Software must be updated to SoMachine V4.3 / EcoStruxure Machine Expert V1.0 or newer.

Memory mapping and channel diagnostic addresses differ from TM2 modules. Hardware configuration and analog acquisition / wire-break logic need reprogramming.

TM3AI8 Channel Configuration in EcoStruxure Machine Expert (formerly SoMachine)

호환 가능한 CPU: M221/M241/M251/M262

  1. Add Module on Hardware Bus
  2. Right-click IO_Bus in Device Tree → Add Device, select `TM3AI8` (나사식 터미널) / `TM3AI8G` (스프링 터미널). Confirm module order, TM3 expansion bus sequence must match physical installation order.
  3. After adding, expand TM3AI8 in device tree. 8 analog channels `CH0~CH7` available.
  4. Channel Parameter Configuration (핵심)
  5. Double-click TM3AI8 in device tree, switch to the I/O Configuration tab. 8 channels can be configured independently.
  6. Channel Type dropdown options (per channel):

사용되지 않음: Channel disabled, no acquisition

0~10V

-10~+10V

0~20mA

4~20mA (기준, wire-break diagnostic supported)

0~20mA extended

4~~20mA extended (detects 1.2~~3.99mA fault range, diagnostic code 9)

⚠️ 중요: Hardware wiring must match software type! Setting voltage channel to current mode will damage module input circuit.

  1. After configuration, raw acquisition word `%IWi.x` (Raw AD value) and diagnostic byte `%IBs.x` are generated automatically:

%IWi: Raw channel value

%IBs: Channel status byte for wire-break / over-range judgment

  1. Switch to I/O Mapping: Bind `%IWi` and `%IBs` to custom variables for program access.
  2. Raw Value Range Mapping (for engineering conversion)
채널 유형Raw MinRaw Max
0~10V04000
-10~+10V-40004000
0~20mA04000
4~20mA400020000

Example for 4-20mA transmitter: 4mA → 4000; 20mA →20000

Engineering formula:

ProcessValue = (RawValue4000) / (200004000) × (UpperRangeLowerRange)

  1. Diagnostic Byte %IBs.x Definition
Diagnostic Code설명
0정상, signal within range
5Over-range high
6Under-range / 단선 (typical alarm when 4-20mA wire disconnected)
7Module hardware fault
94~20mA extended mode: 1.2~3.99mA fault range

메모: Under standard 4~20mA mode, open circuit keeps Raw reading fixed at 4000. Wire break cannot be detected only by raw value; %IBs diagnostic byte must be read.

  1. 다운로드 & 시운전
  2. Compile project, verify no hardware configuration errors.
  3. Go online with PLC, open variable watch table to monitor %IW and %IB.
  4. Apply reference voltage/current signal source and verify readings.
  5. Disconnect signal wire to confirm diagnostic byte becomes 6 for 4~20mA channel, wire-break detection works.
  6. 일반적인 함정
  7. Wrong TM3 module sequence: IO bus fault, PLC fails to identify module.
  8. Mismatch between software type and physical wiring: risk of channel burnout.
  9. Standard 4~20mA mode: relying only on raw value, missing wire-break detection.
  10. Unshielded cable for long analog runs: ground potential difference causes reading fluctuation.

TM3AI8 Analog Input Module Fault Diagnosis Method

General principle: Isolate fault location: 감지기 / 배선 / 기준 치수 / PLC configuration. Do not assume module failure immediately.

Applicable to 슈나이더 TM3AI8 with M221/M241/M251/M262 + EcoStruxure Machine Expert

  1. Step1: Module-level Diagnostic (Whole Module Communication Check)
  2. Connect PLC online, check TM3AI8 icon status in device tree

Red cross: PLC cannot communicate with module

문제 해결: Loose expansion bus latch, wrong module installation order, damaged backplane bus, missing DC24V supply, hardware module failure.

Green OK: Module communication healthy. Fault is limited to channel, wiring or configuration.

  1. Read module global status word (module level fault):

Bus fault: Expansion I/O bus error, all channels invalid.

Internal module hardware fault: Module status alarm, abnormal readings for all channels.

  1. Step2: Per-channel Diagnosis (%IBs.x channel diagnostic byte, 핵심)

Monitor channel diagnostic byte `%IBs.x` in software

Diagnostic Code설명결함 위치
0정상, signal within rangeChannel hardware OK; unstable reading: check sensor/noise/calibration
5Over-range highInput signal exceeds full scale, check transmitter output
6Under-range / 단선 (4~20mA)Signal wire broken, transmitter power loss, open loop; Not necessarily module damage
7Channel hardware faultChannel chip damaged on module
94~20mA extended mode: 1.2~3.99mATransmitter failure, leakage current in loop; not module damage

요점: Only diagnostic code 7 indicates hardware damage; 암호 6 mostly points to external wiring or sensor open circuit.

  1. 3단계: Signal Injection Test (Cross Test to Separate External / Module Fault)

테스트 장비

Adjustable signal source: 0-10V voltage source / 4-20mA current simulator

  1. Channel swap test (가장 일반적인)

예: CH0 abnormal reading, CH1 normal

Connect signal source to CH0, configure CH0 for matching signal type.

Move same signal source to CH1.

✅ CH1 reads correctly while CH0 remains abnormal: CH0 channel damaged, module faulty.

✅ Both CH0 and CH1 abnormal: Likely signal source, 배선, grounding or configuration issue, module healthy.

  1. Open-circuit test

전압 모드: Floating channel shows low drifting reading normally.

4~20mA mode: Floating channel triggers diagnostic byte=6 (wire-break alarm), normal module function, not fault.

⚠️ Forbidden: Feed current signal into channel configured as voltage mode; channel will burn out!

  1. Step4: 육안검사 & Power Supply Check
  2. 모듈 전원 공급 장치: Measure DC24V at module terminals, valid range 20.4V~28.8V. Low voltage causes reading jitter and unstable communication.
  3. 육안검사

터미널: Burn marks, melted copper, 부식, 물 유입. Short circuit at terminals burns channels.

백플레인 버스: Broken plastic latch, oxidized or deformed metal contact → communication failure.

  1. 환경: 고온, humidity or strong electrical interference leads to analog reading jump, easy to misjudge as module failure.
  2. Quick Fault Phenomenon Table
현상Likely Root CauseModule Fault?
All channels no reading, PLC reports module communication loss24V 공급 / expansion bus / module sequencePossible module damage
Single channel diagnostic code=7, still alarm after signal source swapChannel circuit burnout✅ Module faulty
Single channel diagnostic code=6, other channels normalTransmitter power off / 단선❌ External fault
All channels reading fluctuating continuously, diagnostic byte=0접지 불량 / no shield / power cable interference❌ Noise issue
Fixed raw %IW value regardless of applied signalChannel latch-up, hardware damage✅ Module faulty
Software channel type mismatch with physical wiring구성 오류, may burn channel❌ Configuration error (unless channel already burnt)
  1. Final Fault Confirmation Criteria

✅ Confirmed module failure:

  1. Module communication OK, one channel consistently reports diagnostic code=7.
  2. Raw value does not follow reference signal input, while other channels on same module work normally.
  3. Terminal burn marks and no response to signal injection.

❌ Not module failure:

  1. Diagnostic code 6,5,9. Reading normal after moving signal to another channel.
  2. Reading fluctuates with diagnostic byte=0, recovered after grounding and shielding improvement.
  3. PLC fails to detect module, recovered after re-seating bus and correcting power supply.
  4. 보충: Second-hand Module Receiving Inspection Checklist
  5. 전원 켜기, PLC recognizes module without module-level fault.
  6. Inject reference signal to each channel, read %IW and diagnostic byte.
  7. Verify 4~20mA wire-break alarm function.
  8. All channels have good linearity with no fixed offset.

Schneider Modicon TM3 Full Range Expansion Module List (Compatible with M221/M241/M251/M262)

Suffix explanation: No suffix = screw terminal; G = spring-cage terminal; K = HE10 flat cable connector

  1. 아날로그 모듈 (AI/AQ/Mixed AM, TM3AI8 family)
모델Channel Description비고
TM3AI44-채널 아날로그 입력나사식 터미널; TM3AI4G spring terminal
TM3AI88-채널 아날로그 입력Model covered above; TM3AI8G spring terminal
TM3AI2H2-channel high precision analog input,16조금Voltage/current support, 고해상도
TM3AQ22-channel analog outputTM3AQ2G spring terminal
TM3AQ44-channel analog outputTM3AQ4G spring terminal
TM3AM64AI+2AO mixed analog moduleTM3AM6G spring terminal
  1. Digital Input Modules DI
모델Channel Description비고
TM3DI88-포인트 DC24V 디지털 입력나사; TM3DI8G spring
TM3DI8A8-point AC120V digital input교류형
TM3DI1616-포인트 DC24V 디지털 입력나사; TM3DI16G spring
TM3DI32K32-포인트 DC24V 디지털 입력HE10 socket, flat cable
  1. Digital Output Modules DQ
모델Channel Description비고
TM3DQ8R8-포인트 릴레이 출력나사; TM3DQ8RG spring
TM3DQ8T8-point PNP transistor DC24V output나사; TM3DQ8TG spring
TM3DQ16R16-포인트 릴레이 출력나사; TM3DQ16RG spring
TM3DQ16T16-point PNP transistor DC24V output나사; TM3DQ16TG spring
TM3DQ32TK32-point PNP transistor DC24V outputHE10 socket
  1. Mixed Digital I/O Modules DM (DI+DO)
모델Channel Description비고
TM3DM8R4DI+4 relay DO나사; TM3DM8RG spring
TM3DM24R16DI+8 relay DO나사; TM3DM24RG spring
  1. High Speed Counter / 특수 기능 모듈
모델설명
TM3XHSC202High speed counter module, 나사식 터미널Encoder acquisition
TM3XHSC202GHigh speed counter module, 스프링 터미널Encoder acquisition
TM3XFHSC202High speed counter with event capture, 나사식 터미널Event capture support
TM3XFHSC202GHigh speed counter with event capture, 스프링 터미널Event capture support
TM3XTYS4TeSys motor management moduleRJ45 interface, motor protection linkage
  1. Bus Extension Modules (원격 I/O, expand module quantity)
모델설명
TM3XTRA1TM3 bus transmitterCPU side
TM3XREC1TM3 bus receiverRemote cabinet side, max.5m
  1. Bus Coupler (TM3 I/O island, fieldbus slave)
모델설명
TM3BC8CANopen bus coupler, 최대 8 TM3 modules
TM3BC24EtherNet/IP bus coupler, 최대 24 TM3 modules
  1. Safety Module
모델설명
TM3SAC5Safety relay output moduleSafety related applications

Important System Rules

  1. Direct backplane expansion for M221/M241/M251: max.7 TM3 modules. 최대 14 modules when using TM3XTRA1+TM3XREC1 remote extension.
  2. G 버전 (스프링 터미널) shares identical electrical performance with screw terminal variant, only terminal construction differs.
  3. 소프트웨어: EcoStruxure Machine Expert (formerly SoMachine) for configuration of all TM3 modules.
  4. 설치: DIN 레일 설치, modules cascaded via backplane latches.