슈나이더 A9L16482

슈나이더 A9L16482: Acti9 iPRD1 12.5r 3P+N Surge Protective Device

A9L16482 is a Type 1+2 결합된 surge protective device (SPD) from Schneider Electric’s Acti9 series, specially designed for 3P+N three‑phase four‑wire systems. It provides comprehensive lightning and surge protection with remote signaling function, suitable for power input points of residential and small commercial buildings.

  1. Core Parameters Summary
사양
모델A9L16482 (액티9 iPRD1 12.5r)
보호 유형유형 1+2 결합된 SPD (protects against direct and indirect lightning strikes)
극 구성3P+N (3 phases + neutral)
정격전압 (UC)350뷔와 (phase‑to‑phase), 255뷔와 (neutral‑to‑earth)
최대 방전 전류 (아이맥스)50그만큼 (8/20μs waveform)
전압 보호 수준 (위로)1.5kV (phase‑to‑phase), 1kV (neutral‑to‑earth)
TechnologyMOV (금속 산화물 배리스터) + GDT (가스 방전관) hybrid technology
치수4 modules wide (72mm), height 89mm, depth 69mm
무게0.649 kg
배선 용량Solid wire 10–35mm², stranded wire 10–25mm²
Earthing SystemCompatible with TN‑S and TT systems
원격 기능With remote signaling contacts, connectable to monitoring systems
  1. 기술적 특징
  2. 일체형 1+2 보호

No need for an extra Type 1 SPD; one unit provides full lightning protection

Suitable for installation in the main distribution board at the building incomer as the first level of surge protection

  1. Hybrid Protection Technology

GDT: Handles high‑energy direct lightning strikes, with high insulation resistance and low leakage current

MOV: Fast response to induced lightning and switching overvoltages for fine protection

Combined to achieve a wide range of surge current absorption capacity

  1. 원격 모니터링 기능

Built‑in status monitoring circuit, outputs operating status via remote signaling contacts

Connectable to PLC or building automation systems for real‑time SPD status monitoring

Automatically sends alarm signals in case of failure for timely maintenance and replacement

  1. 안전설계

Overcurrent protection to prevent overheating in case of SPD failure

Mechanical status indicator window for clear normal/fault indication

Complies with IEC 61643‑11 and EN 61643‑11

  1. 응용 & Installation Recommendations

권장 애플리케이션

Main distribution boards of residential and small commercial buildings (as first‑level protection)

Power distribution systems near the power input

Intelligent building systems requiring remote monitoring of surge protection status

Three‑phase four‑wire distribution networks with TN‑S and TT earthing systems

설치 참고 사항

  1. Install after a 3P+N circuit breaker, close to the power input
  2. Connecting cables should be as short and straight as possible (≤50cm recommended) to reduce inductive effects
  3. Use copper conductor ≥16mm² for earthing; earthing resistance shall comply with local regulations
  4. Remote signaling contacts can be connected to DC 24V or AC 230V monitoring circuits
  5. Cooperate with downstream SPDs (유형 2/3) to form a multi‑level protection system
  6. 선택 & Replacement Information

Selection Criteria

System voltage: 350V AC suitable for 400V systems (phase‑to‑phase voltage)

Expected surge current: 50kA suitable for most building power incomers

Earthing system: confirm TN‑S or TT

Monitoring requirement: whether remote status monitoring is needed

교체 모델

모델Main Difference애플리케이션
A9L16481Without remote signalingBasic protection without monitoring
A9L16483Higher rated currentHigher‑power distribution systems
A9L16484Different protection levelApplications with special accuracy requirements
  1. 유지 & 보증

Warranty period: 18 개월

Regularly check the status indicator (green = normal, red = fault)

Inspection and recording are recommended after the SPD operates (even if not damaged)

Replace immediately in case of failure to avoid loss of protection