Series: Harmony RSB Plug-in Interface Relay (Zelio) | Status: Obsolete
✅ Model Explanation
RSB: RSB series plug-in interface relay
2A: 2 changeover contacts (2CO / DPDT, 2NO+2NC)
080: Rated contact current 8A
U7: 240V AC coil, no LED, no test button
📌 Key Specifications
Coil voltage: 240V AC (50/60Hz)
Contacts: 2 C/O (DPDT), AgNi silver-nickel contacts
Contact rating: 8A @250VAC / 8A @28VDC
Max switching voltage: 250VAC / 300VDC
Coil resistance: 33kΩ; Coil current approx. 7.3mA
Operate / release time: 20ms
Operating temperature: -40℃ ~ +70℃
Indicator light: None; Test button: None
Mounting: Plug-in type, used with base
Standards: IEC61810-1, UL508, CSA, EAC certification
🧩 Matching Bases (8-pin, 2CO)
RSZE08P: Spring-cage terminal base
RSZE1S48M: Screw terminal base (old version)
🔄 Replacement Recommendations
No direct one-to-one OEM equivalent. Prefer same-spec models within the same series:
- RSB2A080M7: 230VAC, 8A, 2CO (most common in domestic market, no LED, no test button)
- If LED indicator required: RSB2A080M7S (relay + base assembly)
- Alternative Schneider RXG series: RXG22M7 (230VAC, 8A, 2CO, incompatible base)
Note: 240VAC and 230VAC are generally compatible under normal grid conditions. Confirm coil specification for voltage-sensitive circuits.
📎 Applications
PLC/controller DO isolation, small contactor coil driving, signal transfer, cabinet interface isolation. Widely used in industrial control, HVAC and packaging machinery.
📌 Additional Info
Packing: 10 pcs per box. It is an obsolete spare part, only stock available. Not recommended for new projects.
Application Fields of Schneider RSB2A080U7 (240VAC coil, 2CO, 8A Interface Relay)
Core function: Signal isolation, level conversion and small-load driving inside control cabinets. The 240VAC coil is designed for AC control circuits. Plug-in design facilitates spare parts replacement, mainly for retrofit and maintenance of existing equipment (obsolete model).
- Industrial Automation (Primary Application)
PLC digital output isolation: PLC DO drives contactor coils, solenoid valves and indicator lamps to suppress electrical interference and protect PLC modules
Local cabinet control loops, hard-wired logic, signal transfer and passive dry contact expansion
Control panels for machine tools, automatic production lines, conveyor systems and assembly equipment
- HVAC
Auxiliary control for air handling units, fresh air units, damper actuators, water valves and fan start/stop
DDC output isolation for building automation, signal switching for heating and cooling units
- Packaging, Textile & Printing Machinery
Auxiliary circuits for packaging machines, bag-making machines, textile machines and printing machines; driving small electromagnetic devices, alarm lamps and counters
Signal switching for local machine control panels
- Building Electrical Systems
Group lighting control, fans, exhaust fans, electric roller shutters and auxiliary access control outputs
Auxiliary signal and alarm loop switching in low-voltage distribution cabinets and control boxes
- Water Supply & Wastewater Treatment
Auxiliary pump control, liquid level signal transfer, dosing equipment and valve bank control loops
Instrument signal isolation to protect transmitters, water quality analyzers and other low-voltage devices
- Other Supporting Equipment
Small test equipment, power cabinets, medical auxiliary equipment and warehouse logistics equipment
Export control cabinets for 240VAC grid markets and spare part replacement for overseas legacy machines
✅ Suitable Operating Conditions
Control side: 240VAC AC control circuit; Max load: 8A, 250VAC low-power loads
Advantages: 2 changeover contacts providing NO and NC signals simultaneously; plug-in base for fast maintenance
Limitations: Not suitable for direct driving of high-power motors, high-frequency switching or heavy inductive impulse loads (RC snubber recommended)
❗ Selection Reminder
This model has a 240V AC coil. For new domestic projects with 230VAC supply, RSB2A080M7 is preferred. RSB2A080U7 is mostly used for overseas equipment and legacy unit maintenance replacement.
Replacement List for Schneider RSB2A080U7 (No Exact OEM Equivalent)
Original model: RSB2A080U7|240VAC coil, 2CO, 8A, no LED, no test button, plug-in RSB series, obsolete
Compatible bases: RSZE08P (spring cage) / RSZE1S48M (screw terminal)
- Same RSB Series (Direct Base Reuse, Pinout Compatible)
- RSB2A080M7 (Top Choice for Maintenance)
Specs: 230VAC coil, 2CO, 8A, no LED, no test button
Description: 230VAC and 240VAC are generally compatible in most grid environments. Direct plug-in to original base without rewiring, mainstream replacement for domestic maintenance
Difference: Nominal coil voltage 230V vs original 240V; contacts, current rating and pinout are identical
- RSB2A080M7S (Assembly: Relay + Base)
Supplied with base, suitable for new projects where separate base procurement is not desired
- RSB2A080M7PV (LED indicator version)
230VAC, 2CO, 8A with LED indicator; ideal for retrofit requiring visual status check
⚠️ Warning: If equipment strictly requires 240VAC (overseas grid with tight voltage tolerance), M7 (230V) is not suitable. Cross-brand 240VAC models should be selected instead.
- Other Schneider Series (Base Not Interchangeable, Base Must Be Replaced)
- RXG22M7
RXG series, 230VAC, 2CO, 8A; plug-in interface relay with similar size and performance
Disadvantage: Different base model, original base cannot be reused; RXG base required
- RXM2AB2P7 (RXM Miniature Relay)
230VAC, 2CO, 8A; widely stocked; different outline and base, suitable for new cabinet layout
- Cross-brand Compatible Replacements (For Export/Maintenance, Strict 240VAC Requirement)
Requirements: 2CO, 8A, 240VAC coil, 8-pin plug-in
Omron: MY2N-CR 240VAC (8A, DPDT)
Weidmüller: DRM2700240L
Phoenix Contact: REL-IR2 / 240AC
Chint: NXJ-2Z/240VAC
Important: Verify pin assignment before replacement. Pin layout varies between brands; do not plug in blindly.
- Replacement Selection Rules
✅ Domestic legacy equipment maintenance, 220/230V grid: Prioritize RSB2A080M7, reuse existing base with minimal modification
✅ Export equipment, stable 240VAC grid: Prioritize cross-brand 240VAC coil models
✅ Status indication required: RSB2A080M7PV
✅ New projects, no base restriction: RXG22M7 / RXM2AB2P7
- Risk Notes
Coil voltage is the critical difference: U7=240VAC; M7=230VAC. Do not mix for voltage-sensitive circuits
Contact specs: All adopt AgNi silver-nickel contacts, 8A@250VAC. RC snubber is recommended for inductive loads
All RSB series share the same mechanical and electrical life ratings, differing only in coil voltage and LED option
Full Model List of Schneider Harmony RSB Plug-in Interface Relay (Zelio)
Series Overview: Plug-in interface relay, three contact configurations:
RSB1A120: 1CO, 12A
RSB1A160: 1CO, 16A
RSB2A080: 2CO, 8A (RSB2A080U7 belongs to this subgroup)
Suffix Definition:
Suffix D = DC coil; Suffix 7 = AC coil (50/60Hz)
PV = with LED indicator + varistor surge protection; S = relay + base assembly
No PV suffix: no LED, no test button; No mechanical test button available for this series
Bases: RSZE08P (spring-cage terminal) / RSZE1S48M (screw terminal)
- DC Coil Models
| Coil Voltage | 1CO 12A | 1CO 16A | 2CO 8A |
| 6V DC | RSB1A120RD | RSB1A160RD | RSB2A080RD |
| 12V DC | RSB1A120JD | RSB1A160JD | RSB2A080JD |
| 24V DC | RSB1A120BD | RSB1A160BD | RSB2A080BD |
| 48V DC | RSB1A120ED | RSB1A160ED | RSB2A080ED |
| 60V DC | RSB1A120ND | RSB1A160ND | RSB2A080ND |
| 110V DC | RSB1A120FD | RSB1A160FD | RSB2A080FD |
- AC Coil Models (Basic Version, No LED)
| Coil Voltage | 1CO 12A | 1CO 16A | 2CO 8A |
| 24V AC | RSB1A120B7 | RSB1A160B7 | RSB2A080B7 |
| 48V AC | RSB1A120E7 | RSB1A160E7 | RSB2A080E7 |
| 120V AC | RSB1A120F7 | RSB1A160F7 | RSB2A080F7 |
| 230V AC | RSB1A120P7 | RSB1A160P7 | RSB2A080P7 |
| 230V AC (M7 domestic marking) | RSB1A120M7 | RSB1A160M7 | RSB2A080M7 |
| 240V AC (Obsolete) | RSB1A120U7 | RSB1A160U7 | RSB2A080U7 |
III. PV Suffix Models (LED + Surge Protection, AC)
| Coil Voltage | 1CO 12A | 1CO 16A | 2CO 8A |
| 24V AC | RSB1A120B7PV | RSB1A160B7PV | RSB2A080B7PV |
| 120V AC | RSB1A120F7PV | RSB1A160F7PV | RSB2A080F7PV |
| 230V AC | RSB1A120P7PV | RSB1A160P7PV | RSB2A080P7PV |
| 230V AC M7 | RSB1A120M7PV | RSB1A160M7PV | RSB2A080M7PV |
- S Suffix Assembly Models (Relay + Base, DIN Rail Mount Directly)
Rule: Add S to the end of base model, e.g. RSB2A080M7S, RSB2A080P7S, RSB1A120B7S
Supplied complete with base, no separate RSZE base purchase required, ideal for fast new project selection
- Model Coding Breakdown (RSB)
RSB + Contact Quantity + A + Rated Current + Voltage Code + Optional PV/S
RSB: Harmony plug-in interface relay
1A = 1CO; 2A = 2CO
120=12A; 160=16A; 080=8A
Last two characters: voltage code
JD=12VDC, BD=24VDC, ED=48VDC, FD=110VDC
B7=24VAC, F7=120VAC, M7=230VAC, P7=230VAC, U7=240VAC (obsolete)
PV: LED indicator + surge protection; S: assembly (relay + base)
- Important Notes
- RSB2A080U7 / RSB1A120U7 / RSB1A160U7 (240VAC) are all obsolete, only stock spares available. M7/P7 are preferred for new projects
- Uniform AgNi silver-nickel contacts, suitable for PLC isolation, HVAC, packaging, water treatment and other industrial control circuits
- Identical pinout within the same series. Same contact configuration can be swapped on the same base
- Mechanical life: 10,000,000 operations; Electrical life: 100,000 operations under resistive load
Contactor,circuit breaker,sensor,Encoder,PLC,Converter













NH42-63-318x560.png)