Schneider RSB2A080U7 Plug-in Interface Relay

Series: Harmony RSB Plug-in Interface Relay (Zelio) | Status: Obsolete ✅ Model Explanation RSB: RSB series plug-in interface relay 2A: 2 changeover contacts (2CO / DPDT, 2NO+2NC) 080: Rated contact current 8A U7: 240V AC coil, no LED, no test button 📌 Key Specifications Coil voltage: 240V AC (50/60Hz) Contacts: 2 C/O (DPDT), AgNi silver-nickel ...

  • Product Details

Series: Harmony RSB Plug-in Interface Relay (Zelio) | Status: Obsolete

✅ Model Explanation

RSB: RSB series plug-in interface relay

2A: 2 changeover contacts (2CO / DPDT, 2NO+2NC)

080: Rated contact current 8A

U7: 240V AC coil, no LED, no test button

📌 Key Specifications

Coil voltage: 240V AC (50/60Hz)

Contacts: 2 C/O (DPDT), AgNi silver-nickel contacts

Contact rating: 8A @250VAC / 8A @28VDC

Max switching voltage: 250VAC / 300VDC

Coil resistance: 33kΩ; Coil current approx. 7.3mA

Operate / release time: 20ms

Operating temperature: -40℃ ~ +70℃

Indicator light: None; Test button: None

Mounting: Plug-in type, used with base

Standards: IEC61810-1, UL508, CSA, EAC certification

🧩 Matching Bases (8-pin, 2CO)

RSZE08P: Spring-cage terminal base

RSZE1S48M: Screw terminal base (old version)

🔄 Replacement Recommendations

No direct one-to-one OEM equivalent. Prefer same-spec models within the same series:

  1. RSB2A080M7: 230VAC, 8A, 2CO (most common in domestic market, no LED, no test button)
  2. If LED indicator required: RSB2A080M7S (relay + base assembly)
  3. Alternative Schneider RXG series: RXG22M7 (230VAC, 8A, 2CO, incompatible base)

Note: 240VAC and 230VAC are generally compatible under normal grid conditions. Confirm coil specification for voltage-sensitive circuits.

📎 Applications

PLC/controller DO isolation, small contactor coil driving, signal transfer, cabinet interface isolation. Widely used in industrial control, HVAC and packaging machinery.

📌 Additional Info

Packing: 10 pcs per box. It is an obsolete spare part, only stock available. Not recommended for new projects.

Application Fields of Schneider RSB2A080U7 (240VAC coil, 2CO, 8A Interface Relay)

Core function: Signal isolation, level conversion and small-load driving inside control cabinets. The 240VAC coil is designed for AC control circuits. Plug-in design facilitates spare parts replacement, mainly for retrofit and maintenance of existing equipment (obsolete model).

  1. Industrial Automation (Primary Application)

PLC digital output isolation: PLC DO drives contactor coils, solenoid valves and indicator lamps to suppress electrical interference and protect PLC modules

Local cabinet control loops, hard-wired logic, signal transfer and passive dry contact expansion

Control panels for machine tools, automatic production lines, conveyor systems and assembly equipment

  1. HVAC

Auxiliary control for air handling units, fresh air units, damper actuators, water valves and fan start/stop

DDC output isolation for building automation, signal switching for heating and cooling units

  1. Packaging, Textile & Printing Machinery

Auxiliary circuits for packaging machines, bag-making machines, textile machines and printing machines; driving small electromagnetic devices, alarm lamps and counters

Signal switching for local machine control panels

  1. Building Electrical Systems

Group lighting control, fans, exhaust fans, electric roller shutters and auxiliary access control outputs

Auxiliary signal and alarm loop switching in low-voltage distribution cabinets and control boxes

  1. Water Supply & Wastewater Treatment

Auxiliary pump control, liquid level signal transfer, dosing equipment and valve bank control loops

Instrument signal isolation to protect transmitters, water quality analyzers and other low-voltage devices

  1. Other Supporting Equipment

Small test equipment, power cabinets, medical auxiliary equipment and warehouse logistics equipment

Export control cabinets for 240VAC grid markets and spare part replacement for overseas legacy machines

✅ Suitable Operating Conditions

Control side: 240VAC AC control circuit; Max load: 8A, 250VAC low-power loads

Advantages: 2 changeover contacts providing NO and NC signals simultaneously; plug-in base for fast maintenance

Limitations: Not suitable for direct driving of high-power motors, high-frequency switching or heavy inductive impulse loads (RC snubber recommended)

❗ Selection Reminder

This model has a 240V AC coil. For new domestic projects with 230VAC supply, RSB2A080M7 is preferred. RSB2A080U7 is mostly used for overseas equipment and legacy unit maintenance replacement.

Replacement List for Schneider RSB2A080U7 (No Exact OEM Equivalent)

Original model: RSB2A080U7|240VAC coil, 2CO, 8A, no LED, no test button, plug-in RSB series, obsolete

Compatible bases: RSZE08P (spring cage) / RSZE1S48M (screw terminal)

  1. Same RSB Series (Direct Base Reuse, Pinout Compatible)
  2. RSB2A080M7 (Top Choice for Maintenance)

Specs: 230VAC coil, 2CO, 8A, no LED, no test button

Description: 230VAC and 240VAC are generally compatible in most grid environments. Direct plug-in to original base without rewiring, mainstream replacement for domestic maintenance

Difference: Nominal coil voltage 230V vs original 240V; contacts, current rating and pinout are identical

  1. RSB2A080M7S (Assembly: Relay + Base)

Supplied with base, suitable for new projects where separate base procurement is not desired

  1. RSB2A080M7PV (LED indicator version)

230VAC, 2CO, 8A with LED indicator; ideal for retrofit requiring visual status check

⚠️ Warning: If equipment strictly requires 240VAC (overseas grid with tight voltage tolerance), M7 (230V) is not suitable. Cross-brand 240VAC models should be selected instead.

  1. Other Schneider Series (Base Not Interchangeable, Base Must Be Replaced)
  2. RXG22M7

RXG series, 230VAC, 2CO, 8A; plug-in interface relay with similar size and performance

Disadvantage: Different base model, original base cannot be reused; RXG base required

  1. RXM2AB2P7 (RXM Miniature Relay)

230VAC, 2CO, 8A; widely stocked; different outline and base, suitable for new cabinet layout

  1. Cross-brand Compatible Replacements (For Export/Maintenance, Strict 240VAC Requirement)

Requirements: 2CO, 8A, 240VAC coil, 8-pin plug-in

Omron: MY2N-CR 240VAC (8A, DPDT)

Weidmüller: DRM2700240L

Phoenix Contact: REL-IR2 / 240AC

Chint: NXJ-2Z/240VAC

Important: Verify pin assignment before replacement. Pin layout varies between brands; do not plug in blindly.

  1. Replacement Selection Rules

✅ Domestic legacy equipment maintenance, 220/230V grid: Prioritize RSB2A080M7, reuse existing base with minimal modification

✅ Export equipment, stable 240VAC grid: Prioritize cross-brand 240VAC coil models

✅ Status indication required: RSB2A080M7PV

✅ New projects, no base restriction: RXG22M7 / RXM2AB2P7

  1. Risk Notes

Coil voltage is the critical difference: U7=240VAC; M7=230VAC. Do not mix for voltage-sensitive circuits

Contact specs: All adopt AgNi silver-nickel contacts, 8A@250VAC. RC snubber is recommended for inductive loads

All RSB series share the same mechanical and electrical life ratings, differing only in coil voltage and LED option

Full Model List of Schneider Harmony RSB Plug-in Interface Relay (Zelio)

Series Overview: Plug-in interface relay, three contact configurations:

RSB1A120: 1CO, 12A

RSB1A160: 1CO, 16A

RSB2A080: 2CO, 8A (RSB2A080U7 belongs to this subgroup)

Suffix Definition:

Suffix D = DC coil; Suffix 7 = AC coil (50/60Hz)

PV = with LED indicator + varistor surge protection; S = relay + base assembly

No PV suffix: no LED, no test button; No mechanical test button available for this series

Bases: RSZE08P (spring-cage terminal) / RSZE1S48M (screw terminal)

  1. DC Coil Models
Coil Voltage1CO 12A1CO 16A2CO 8A
6V DCRSB1A120RDRSB1A160RDRSB2A080RD
12V DCRSB1A120JDRSB1A160JDRSB2A080JD
24V DCRSB1A120BDRSB1A160BDRSB2A080BD
48V DCRSB1A120EDRSB1A160EDRSB2A080ED
60V DCRSB1A120NDRSB1A160NDRSB2A080ND
110V DCRSB1A120FDRSB1A160FDRSB2A080FD
  1. AC Coil Models (Basic Version, No LED)
Coil Voltage1CO 12A1CO 16A2CO 8A
24V ACRSB1A120B7RSB1A160B7RSB2A080B7
48V ACRSB1A120E7RSB1A160E7RSB2A080E7
120V ACRSB1A120F7RSB1A160F7RSB2A080F7
230V ACRSB1A120P7RSB1A160P7RSB2A080P7
230V AC (M7 domestic marking)RSB1A120M7RSB1A160M7RSB2A080M7
240V AC (Obsolete)RSB1A120U7RSB1A160U7RSB2A080U7

III. PV Suffix Models (LED + Surge Protection, AC)

Coil Voltage1CO 12A1CO 16A2CO 8A
24V ACRSB1A120B7PVRSB1A160B7PVRSB2A080B7PV
120V ACRSB1A120F7PVRSB1A160F7PVRSB2A080F7PV
230V ACRSB1A120P7PVRSB1A160P7PVRSB2A080P7PV
230V AC M7RSB1A120M7PVRSB1A160M7PVRSB2A080M7PV
  1. S Suffix Assembly Models (Relay + Base, DIN Rail Mount Directly)

Rule: Add S to the end of base model, e.g. RSB2A080M7S, RSB2A080P7S, RSB1A120B7S

Supplied complete with base, no separate RSZE base purchase required, ideal for fast new project selection

  1. Model Coding Breakdown (RSB)

RSB + Contact Quantity + A + Rated Current + Voltage Code + Optional PV/S

RSB: Harmony plug-in interface relay

1A = 1CO; 2A = 2CO

120=12A; 160=16A; 080=8A

Last two characters: voltage code

JD=12VDC, BD=24VDC, ED=48VDC, FD=110VDC

B7=24VAC, F7=120VAC, M7=230VAC, P7=230VAC, U7=240VAC (obsolete)

PV: LED indicator + surge protection; S: assembly (relay + base)

  1. Important Notes
  2. RSB2A080U7 / RSB1A120U7 / RSB1A160U7 (240VAC) are all obsolete, only stock spares available. M7/P7 are preferred for new projects
  3. Uniform AgNi silver-nickel contacts, suitable for PLC isolation, HVAC, packaging, water treatment and other industrial control circuits
  4. Identical pinout within the same series. Same contact configuration can be swapped on the same base