Ordering No.: 1SFA898216R7000
PSTX: ABB PSTX advanced soft starter series, three-phase thyristor control with built-in bypass contactor
470: Rated operational current (In-line connection): 470 A
690: Main circuit voltage: 208~690 VAC
70: Control supply: 100–250 V AC, 50/60 Hz
- Key Technical Ratings
| Item | Specification |
| In-line rated current | 470 A |
| Inside-delta equivalent current | 814 A |
| Main circuit voltage | 208~690 VAC, 50/60 Hz |
| Control supply | 100–250 VAC |
| Power (In-line, 400V) | 250 kW |
| Power (In-line, 690V) | 450 kW |
| Power (Inside-delta, 690V) | 800 kW |
| Starting capacity | 4×Ie for 10 secondseero |
| Maximum starts per hour | 6 timeseero |
| Cooling | Thermostat-controlled fan cooling, built-in bypass contactoreero |
| Protection class (main circuit) | IP20; detachable keypad IP66eero |
| Communication | Built-in Modbus RTUeero |
| Analog output | Current / Voltage / Power factor selectable |
| Overload class | Class 10eero |
| Ambient temperature | -25~+60 ℃; Max altitude 4000 m (derating required)eero |
- Built-in Functions
Soft start & soft stop: Voltage ramp, torque control ramp, current limit start, dual current limit mode
Pump cleaning & anti-surge functions (ideal for pump applications)
Jog / slow speed, pre-start, kick start
Dynamic braking & standstill braking
Limp mode: Two-phase reduced-capacity operation if one thyristor fails
Fire emergency mode: Bypass all protections to force run
Real-time clock, event log, energy metering, thyristor running hour counter
Auto phase sequence detection & auto restart
Full protection: Electronic overload, locked rotor, phase loss, current unbalance, underload, earth fault, over/under voltage, PTC/PT100 motor temperature monitoring, bypass fault, communication fault
HMI: Color graphical display, 17 languages, detachable with password lock
- Typical Applications
Water pumps, fans, compressors, belt conveyors, crushers and other heavy-duty equipment. The built-in bypass cuts off thyristor current after full speed, eliminating continuous heat loss and saving energy.
- Cross-Series & Replacement Notes
- PSTX470-600-70 (Order No. 1SFA898116R7000): Max voltage 600V, cannot directly replace the 690V version
- PSTB470: Basic model without torque control, limp mode and pump cleaning; not an equivalent replacement
- Domestic alternatives: Renle, Xichi, Heping 470A/690V built-in bypass soft starters; communication and protection logic differ, PLC programs need modification
- Installation & Maintenance Tips
- Two wiring options: In-line (most common) / Inside-delta (boost motor power rating; soft starter only carries branch winding current)
- Sufficient cabinet ventilation; derate power for +60℃ ambient or high altitude
- Regularly inspect built-in bypass contacts; thyristors and cooling fans are wearing parts
- Set Modbus RTU address and baud rate via the keypad; refer to PSTX official communication manual for register mapping
Working Principle of Thyristor Soft Starters (ABB PSTX Type)
A soft starter is essentially a thyristor (SCR) AC voltage regulator wired in series with the three-phase motor main circuit. It adjusts the thyristor firing angle to gradually raise motor terminal voltage for smooth ramp-up start, and gradually lower voltage for smooth ramp-down stop — no sudden full voltage jump as in direct-on-line or star-delta starting.
- Core Component: Anti-parallel Thyristors per Phase
Each phase has a pair of reverse-connected thyristors:
Small firing angle → short conduction time → low output voltage
Gradually increasing firing angle → voltage rises smoothly
Full firing angle → output voltage nearly equals grid rated voltage
Thyristors only trigger at voltage zero-crossing in each AC half-cycle, enabling precise voltage regulation.
- Start-Stop Sequence (Built-in Bypass Model like PSTX)
- Standby: Bypass contactor open; all current flows through thyristor modules
- Soft Ramp-up: Controller increases thyristor conduction angle step by step; motor voltage climbs slowly, limiting inrush current (no 5~7× rated current surge of DOL start). Two main modes: voltage ramp or torque-controlled ramp (PSTX exclusive)
- Bypass Closure: When motor reaches full speed, the built-in bypass contactor closes. Current transfers to mechanical contacts; thyristors exit the main circuit with no continuous heat generation
- Normal Operation: Motor runs directly on mains; soft starter only monitors protection
- Soft Stop: Bypass opens again, switching back to thyristor voltage control; voltage ramps down slowly to stop the motor gently, eliminating water hammer in piping and mechanical shock on transmission parts
- Difference vs Star-Delta / Autotransformer Starters
Star-delta: Step voltage switching, still creates secondary current surges; only fixed voltage reduction ratio
Autotransformer: Step-down voltage only, bulky size, no continuous adjustable curve
Thyristor soft starter: stepless continuous voltage regulation, programmable start curves, plus braking, pump cleaning, full motor protection and fieldbus communication
- Two Common Starting Modes
Current limit start: Lock maximum starting current first; voltage adjusts automatically to match load — preferred for heavy loads
Torque-controlled start (PSTX only): Regulates motor torque directly instead of pure voltage, delivering smoother acceleration with less mechanical impact
- Key Limitation
Thyristor voltage regulation only changes voltage amplitude, NOT frequency.
👉 Soft starter ≠ Variable Frequency Drive (VFD): Soft starters only control starting & stopping; they cannot run the motor continuously at variable speed. VFD adjusts both voltage and frequency for continuous speed regulation.
Common Faults for PSTX Built-in Bypass Soft Starters
- Heatsink / Thyristor Overheating (Fault F04xx)
Symptom: Trips after several starts; housing hot; cooling fan fails to run
Root Causes:
Fan damaged or air duct blocked with dust
Cabinet sealed tightly; high ambient temperature or high altitude without derating
Bypass contactor fails to close; thyristors stay energized and overheat
Excessively long ramp time or frequent starts exceeding the 6 starts/hour limit
Solutions: Clean dust, replace fan, verify start frequency, troubleshoot bypass circuit
- Phase Loss / 3-Phase Current Imbalance (F03xx)
Symptom: Trips immediately on power-up; motor hums with heavy vibration
Root Causes:
Blown fuses, open circuit breakers, loose terminal lugs or oxidized copper busbars
One-phase thyristor open-circuit or trigger failure
Broken motor winding or poor cable connection
Distinction: Input phase loss = supply side; Output phase loss = wiring between soft starter and motor or damaged SCR
- Overcurrent / Short Circuit
Symptom: Instant trip on start; current far exceeds the set current limit
Root Causes:
Motor locked rotor (blocked impeller, seized bearing)
Cable or motor insulation breakdown (phase-phase or phase-earth short)
Starting voltage set too high or current limit value set too large
Thyristor short-circuited (do not retry starting repeatedly)
- Start Timeout (Failed to Reach Full Speed)
Symptom: Ramp finishes but motor never reaches rated speed; start timeout fault triggers
Root Causes:
Current limit set too low or initial voltage too low (insufficient torque)
Excessive load inertia, closed valve or heavy mechanical resistance
Wrong motor rated current parameter or undersized motor
Severe grid voltage drop during start
- Bypass-Related Faults (Most Frequent on PSTX: F0613, bypass failure, stuck contacts)
- Bypass fails to pull in: Thyristors remain energized and overheat rapidly
Causes: Damaged coil, insufficient control voltage, bypass function disabled in parameters, internal detection circuit failure
- Bypass contactor welded shut: Input and output permanently shorted; soft stop function fails completely; safety hazard
Causes: Frequent heavy-current cycling, arc erosion on contacts, repeated short-circuit surges
- Motor Overload Trip
Symptom: Trips after long running time, not during startup
Root Causes:
Continuous overloaded operation, pump clogging, worn bearings
Incorrect motor rated current or Class 10 overload setting
Long low-speed operation leading to poor motor cooling; PTC/PT100 overtemperature alarm
- Underload Protection Trip
Symptom: Motor runs but current drops below threshold (dry-run protection for pumps/fans)
Root Causes: Pump running dry, fully open valve with no load, broken belt or disconnected coupling
Note: Disable underload protection temporarily during no-load commissioning; re-enable after field commissioning.
- Thyristor SCR Damage (Short / Open Circuit)
Symptom: No clear fault code, but 3-phase current unbalanced, loss of voltage control, residual voltage on output after shutdown
Root Causes: Grid surge / lightning strikes, repeated heavy starts, poor cooling, output short-circuit impact
Testing: Disconnect power and measure resistance across each thyristor; shorted SCR shows near-zero resistance between input and output. Damaged power modules cannot be repaired and must be replaced.
- Control Supply & Communication Faults
No power on HMI: Black screen, random faults → low 100–250V control supply or blown internal fuse
Modbus RTU communication loss: PLC cannot read data → mismatched address/baud rate, poor shielding or ground interference
- Phase Sequence Fault
Symptom: Phase reversal alarm on power-up; start inhibited
Root Cause: Incoming three-phase wiring reversed. You can disable phase sequence check temporarily (not recommended for permanent operation).
- Failed Soft Stop (Water Hammer)
Symptom: Motor stops abruptly, causing severe pipeline water hammer
Root Causes: Soft stop ramp time set too short; welded bypass contactor prevents switching back to thyristor control, resulting in direct hard stop.
Fast On-Site Troubleshooting Sequence (PSTX Recommended)
- Check fault code and event log on the graphical display (PSTX stores full historical records)
- Cut off power and inspect all main terminals & busbars for overheating and loose connections
- Disconnect the motor and run no-load test to isolate faults: soft starter failure vs motor/mechanical load failure
- Verify bypass contactor operation and cooling fan rotation
- Double-check that all motor nameplate parameters match the soft starter settings
Full PSTX Series Model List (Built-in Bypass)
PSTX xxx-600-70 (208~600V AC)
| Model | Order No. | Rated Current | 400V Power |
| PSTX30-600-70 | 1SFA898103R7000 | 30 A | 15 kW |
| PSTX37-600-70 | 1SFA898104R7000 | 37 A | 18.5 kW |
| PSTX45-600-70 | 1SFA898105R7000 | 45 A | 22 kW |
| PSTX60-600-70 | 1SFA898106R7000 | 60 A | 30 kW |
| PSTX72-600-70 | 1SFA898107R7000 | 72 A | 37 kW |
| PSTX85-600-70 | 1SFA898108R7000 | 85 A | 45 kW |
| PSTX105-600-70 | 1SFA898109R7000 | 105 A | 55 kW |
| PSTX142-600-70 | 1SFA898110R7000 | 142 A | 75 kW |
| PSTX170-600-70 | 1SFA898111R7000 | 170 A | 90 kW |
| PSTX210-600-70 | 1SFA898112R7000 | 210 A | 110 kW |
| PSTX250-600-70 | 1SFA898113R7000 | 250 A | 132 kW |
| PSTX300-600-70 | 1SFA898114R7000 | 300 A | 160 kW |
| PSTX370-600-70 | 1SFA898115R7000 | 370 A | 200 kW |
| PSTX470-600-70 | 1SFA898116R7000 | 470 A | 250 kW |
| PSTX570-600-70 | 1SFA898117R7000 | 570 A | 315 kW |
| PSTX720-600-70 | 1SFA898118R7000 | 720 A | 400 kW |
| PSTX840-600-70 | 1SFA898119R7000 | 840 A | 450 kW |
| PSTX1050-600-70 | 1SFA898120R7000 | 1050 A | 560 kW |
| PSTX1250-600-70 | 1SFA898121R7000 | 1250 A | 710 kW |
PSTX xxx-690-70 (208~690V AC, including PSTX470-690-70)
| Model | Order No. | Current | 400V kW | 690V kW |
| PSTX30-690-70 | 1SFA898203R7000 | 30 A | 15 | 25 |
| PSTX37-690-70 | 1SFA898204R7000 | 37 A | 18.5 | 30 |
| PSTX45-690-70 | 1SFA898205R7000 | 45 A | 22 | 37 |
| PSTX60-690-70 | 1SFA898206R7000 | 60 A | 30 | 45 |
| PSTX72-690-70 | 1SFA898207R7000 | 72 A | 37 | 55 |
| PSTX85-690-70 | 1SFA898208R7000 | 85 A | 45 | 59 |
| PSTX105-690-70 | 1SFA898209R7000 | 105 A | 55 | 75 |
| PSTX142-690-70 | 1SFA898210R7000 | 142 A | 75 | 90 |
| PSTX170-690-70 | 1SFA898211R7000 | 170 A | 90 | 132 |
| PSTX210-690-70 | 1SFA898212R7000 | 210 A | 110 | 160 |
| PSTX250-690-70 | 1SFA898213R7000 | 250 A | 132 | 184 |
| PSTX300-690-70 | 1SFA898214R7000 | 300 A | 160 | 220 |
| PSTX370-690-70 | 1SFA898215R7000 | 370 A | 200 | 257 |
| PSTX470-690-70 | 1SFA898216R7000 | 470 A | 250 | 355 |
| PSTX570-690-70 | 1SFA898217R7000 | 570 A | 315 | 450 |
| PSTX720-690-70 | 1SFA898218R7000 | 720 A | 400 | 560 |
| PSTX840-690-70 | 1SFA898219R7000 | 840 A | 450 | 710 |
| PSTX1050-690-70 | 1SFA898220R7000 | 1050 A | 560 | 800 |
| PSTX1250-690-70 | 1SFA898221R7000 | 1250 A | 710 | 1000 |
PSTB Basic Series (Reduced Functions, Built-in Bypass)
| Model | Order No. | Current | 400V Power |
| PSTB370-600-70 | 1SFA894015R7000 | 370 A | 200 kW |
| PSTB470-600-70 | 1SFA894016R7000 | 470 A | 250 kW |
| PSTB570-600-70 | 1SFA894017R7000 | 570 A | 315 kW |
| PSTB720-600-70 | 1SFA894018R7000 | 720 A | 400 kW |
| PSTB840-600-70 | 1SFA894019R7000 | 840 A | 450 kW |
| PSTB1050-600-70 | 1SFA894020R7000 | 1050 A | 560 kW |
PSTB does not support torque control, limp mode or pump cleaning. Only for simple fan & pump start-stop; not a direct replacement for PSTX.
PSR Compact Soft Starters (Economical, NO Built-in Bypass)
| Model | Order No. | Current | 400V Power |
| PSR3-600-70 | 1SFA896103R7000 | 3 A | 0.75 kW |
| PSR6-600-70 | 1SFA896104R7000 | 6 A | 1.5 kW |
| PSR9-600-70 | 1SFA896105R7000 | 9 A | 2.2 kW |
| PSR12-600-70 | 1SFA896106R7000 | 12 A | 3 kW |
| PSR16-600-70 | 1SFA896107R7000 | 16 A | 4 kW |
| PSR25-600-70 | 1SFA896108R7000 | 25 A | 5.5 kW |
| PSR30-600-70 | 1SFA896109R7000 | 30 A | 7.5 kW |
| PSR37-600-70 | 1SFA896110R7000 | 37 A | 11 kW |
| PSR45-600-70 | 1SFA896111R7000 | 45 A | 15 kW |
| PSR60-600-70 | 1SFA896112R7000 | 60 A | 18.5 kW |
| PSR72-600-70 | 1SFA896113R7000 | 72 A | 22 kW |
| PSR85-600-70 | 1SFA896114R7000 | 85 A | 30 kW |
| PSR105-600-70 | 1SFA896115R7000 | 105 A | 37 kW |
Series Quick Comparison
- PSTX: High-end flagship, color HMI, torque control, braking, pump cleaning, Modbus, full protection, built-in bypass; preferred for export industrial projects
- PSTB: Mid-range basic model, monochrome screen, limited functions, built-in bypass
- PSR: Compact low-cost version, no built-in bypass, requires external bypass contactor; only for small-power motors
- PSS / PST: Older legacy models, phased out; only available as spare parts for existing installations, not recommended for new projects
Optional Communication Accessories (PSTX)
PS-FBPA: 1SFA896312R1002, basic fieldbus adapter
PSTX ANYBUS Modbus RTU: 1SFA899300R1003