 ABB PSTX470-690-70 Soft Starter

Ordering No.: 1SFA898216R7000 PSTX: ABB PSTX advanced soft starter series, three-phase thyristor control with built-in bypass contactor 470: Rated operational current (In-line connection): 470 A 690: Main circuit voltage: 208~690 VAC 70: Control supply: 100–250 V AC, 50/60 Hz Key Technical Ratings Item Specification In-line rated current 470 A Inside-delta equivalent current 814 A Main ...

  • Product Details

Ordering No.: 1SFA898216R7000

PSTX: ABB PSTX advanced soft starter series, three-phase thyristor control with built-in bypass contactor

470: Rated operational current (In-line connection): 470 A

690: Main circuit voltage: 208~690 VAC

70: Control supply: 100–250 V AC, 50/60 Hz

  1. Key Technical Ratings
ItemSpecification
In-line rated current470 A
Inside-delta equivalent current814 A
Main circuit voltage208~690 VAC, 50/60 Hz
Control supply100–250 VAC
Power (In-line, 400V)250 kW
Power (In-line, 690V)450 kW
Power (Inside-delta, 690V)800 kW
Starting capacity4×Ie for 10 secondseero
Maximum starts per hour6 timeseero
CoolingThermostat-controlled fan cooling, built-in bypass contactoreero
Protection class (main circuit)IP20; detachable keypad IP66eero
CommunicationBuilt-in Modbus RTUeero
Analog outputCurrent / Voltage / Power factor selectable
Overload classClass 10eero
Ambient temperature-25~+60 ℃; Max altitude 4000 m (derating required)eero
  1. Built-in Functions

Soft start & soft stop: Voltage ramp, torque control ramp, current limit start, dual current limit mode

Pump cleaning & anti-surge functions (ideal for pump applications)

Jog / slow speed, pre-start, kick start

Dynamic braking & standstill braking

Limp mode: Two-phase reduced-capacity operation if one thyristor fails

Fire emergency mode: Bypass all protections to force run

Real-time clock, event log, energy metering, thyristor running hour counter

Auto phase sequence detection & auto restart

Full protection: Electronic overload, locked rotor, phase loss, current unbalance, underload, earth fault, over/under voltage, PTC/PT100 motor temperature monitoring, bypass fault, communication fault

HMI: Color graphical display, 17 languages, detachable with password lock

  1. Typical Applications

Water pumps, fans, compressors, belt conveyors, crushers and other heavy-duty equipment. The built-in bypass cuts off thyristor current after full speed, eliminating continuous heat loss and saving energy.

  1. Cross-Series & Replacement Notes
  2. PSTX470-600-70 (Order No. 1SFA898116R7000): Max voltage 600V, cannot directly replace the 690V version
  3. PSTB470: Basic model without torque control, limp mode and pump cleaning; not an equivalent replacement
  4. Domestic alternatives: Renle, Xichi, Heping 470A/690V built-in bypass soft starters; communication and protection logic differ, PLC programs need modification
  5. Installation & Maintenance Tips
  6. Two wiring options: In-line (most common) / Inside-delta (boost motor power rating; soft starter only carries branch winding current)
  7. Sufficient cabinet ventilation; derate power for +60℃ ambient or high altitude
  8. Regularly inspect built-in bypass contacts; thyristors and cooling fans are wearing parts
  9. Set Modbus RTU address and baud rate via the keypad; refer to PSTX official communication manual for register mapping

Working Principle of Thyristor Soft Starters (ABB PSTX Type)

A soft starter is essentially a thyristor (SCR) AC voltage regulator wired in series with the three-phase motor main circuit. It adjusts the thyristor firing angle to gradually raise motor terminal voltage for smooth ramp-up start, and gradually lower voltage for smooth ramp-down stop — no sudden full voltage jump as in direct-on-line or star-delta starting.

  1. Core Component: Anti-parallel Thyristors per Phase

Each phase has a pair of reverse-connected thyristors:

Small firing angle → short conduction time → low output voltage

Gradually increasing firing angle → voltage rises smoothly

Full firing angle → output voltage nearly equals grid rated voltage

Thyristors only trigger at voltage zero-crossing in each AC half-cycle, enabling precise voltage regulation.

  1. Start-Stop Sequence (Built-in Bypass Model like PSTX)
  2. Standby: Bypass contactor open; all current flows through thyristor modules
  3. Soft Ramp-up: Controller increases thyristor conduction angle step by step; motor voltage climbs slowly, limiting inrush current (no 5~7× rated current surge of DOL start). Two main modes: voltage ramp or torque-controlled ramp (PSTX exclusive)
  4. Bypass Closure: When motor reaches full speed, the built-in bypass contactor closes. Current transfers to mechanical contacts; thyristors exit the main circuit with no continuous heat generation
  5. Normal Operation: Motor runs directly on mains; soft starter only monitors protection
  6. Soft Stop: Bypass opens again, switching back to thyristor voltage control; voltage ramps down slowly to stop the motor gently, eliminating water hammer in piping and mechanical shock on transmission parts
  7. Difference vs Star-Delta / Autotransformer Starters

Star-delta: Step voltage switching, still creates secondary current surges; only fixed voltage reduction ratio

Autotransformer: Step-down voltage only, bulky size, no continuous adjustable curve

Thyristor soft starter: stepless continuous voltage regulation, programmable start curves, plus braking, pump cleaning, full motor protection and fieldbus communication

  1. Two Common Starting Modes

Current limit start: Lock maximum starting current first; voltage adjusts automatically to match load — preferred for heavy loads

Torque-controlled start (PSTX only): Regulates motor torque directly instead of pure voltage, delivering smoother acceleration with less mechanical impact

  1. Key Limitation

Thyristor voltage regulation only changes voltage amplitude, NOT frequency.

👉 Soft starter ≠ Variable Frequency Drive (VFD): Soft starters only control starting & stopping; they cannot run the motor continuously at variable speed. VFD adjusts both voltage and frequency for continuous speed regulation.

Common Faults for PSTX Built-in Bypass Soft Starters

  1. Heatsink / Thyristor Overheating (Fault F04xx)

Symptom: Trips after several starts; housing hot; cooling fan fails to run

Root Causes:

Fan damaged or air duct blocked with dust

Cabinet sealed tightly; high ambient temperature or high altitude without derating

Bypass contactor fails to close; thyristors stay energized and overheat

Excessively long ramp time or frequent starts exceeding the 6 starts/hour limit

Solutions: Clean dust, replace fan, verify start frequency, troubleshoot bypass circuit

  1. Phase Loss / 3-Phase Current Imbalance (F03xx)

Symptom: Trips immediately on power-up; motor hums with heavy vibration

Root Causes:

Blown fuses, open circuit breakers, loose terminal lugs or oxidized copper busbars

One-phase thyristor open-circuit or trigger failure

Broken motor winding or poor cable connection

Distinction: Input phase loss = supply side; Output phase loss = wiring between soft starter and motor or damaged SCR

  1. Overcurrent / Short Circuit

Symptom: Instant trip on start; current far exceeds the set current limit

Root Causes:

Motor locked rotor (blocked impeller, seized bearing)

Cable or motor insulation breakdown (phase-phase or phase-earth short)

Starting voltage set too high or current limit value set too large

Thyristor short-circuited (do not retry starting repeatedly)

  1. Start Timeout (Failed to Reach Full Speed)

Symptom: Ramp finishes but motor never reaches rated speed; start timeout fault triggers

Root Causes:

Current limit set too low or initial voltage too low (insufficient torque)

Excessive load inertia, closed valve or heavy mechanical resistance

Wrong motor rated current parameter or undersized motor

Severe grid voltage drop during start

  1. Bypass-Related Faults (Most Frequent on PSTX: F0613, bypass failure, stuck contacts)
  2. Bypass fails to pull in: Thyristors remain energized and overheat rapidly

Causes: Damaged coil, insufficient control voltage, bypass function disabled in parameters, internal detection circuit failure

  1. Bypass contactor welded shut: Input and output permanently shorted; soft stop function fails completely; safety hazard

Causes: Frequent heavy-current cycling, arc erosion on contacts, repeated short-circuit surges

  1. Motor Overload Trip

Symptom: Trips after long running time, not during startup

Root Causes:

Continuous overloaded operation, pump clogging, worn bearings

Incorrect motor rated current or Class 10 overload setting

Long low-speed operation leading to poor motor cooling; PTC/PT100 overtemperature alarm

  1. Underload Protection Trip

Symptom: Motor runs but current drops below threshold (dry-run protection for pumps/fans)

Root Causes: Pump running dry, fully open valve with no load, broken belt or disconnected coupling

Note: Disable underload protection temporarily during no-load commissioning; re-enable after field commissioning.

  1. Thyristor SCR Damage (Short / Open Circuit)

Symptom: No clear fault code, but 3-phase current unbalanced, loss of voltage control, residual voltage on output after shutdown

Root Causes: Grid surge / lightning strikes, repeated heavy starts, poor cooling, output short-circuit impact

Testing: Disconnect power and measure resistance across each thyristor; shorted SCR shows near-zero resistance between input and output. Damaged power modules cannot be repaired and must be replaced.

  1. Control Supply & Communication Faults

No power on HMI: Black screen, random faults → low 100–250V control supply or blown internal fuse

Modbus RTU communication loss: PLC cannot read data → mismatched address/baud rate, poor shielding or ground interference

  1. Phase Sequence Fault

Symptom: Phase reversal alarm on power-up; start inhibited

Root Cause: Incoming three-phase wiring reversed. You can disable phase sequence check temporarily (not recommended for permanent operation).

  1. Failed Soft Stop (Water Hammer)

Symptom: Motor stops abruptly, causing severe pipeline water hammer

Root Causes: Soft stop ramp time set too short; welded bypass contactor prevents switching back to thyristor control, resulting in direct hard stop.

Fast On-Site Troubleshooting Sequence (PSTX Recommended)

  1. Check fault code and event log on the graphical display (PSTX stores full historical records)
  2. Cut off power and inspect all main terminals & busbars for overheating and loose connections
  3. Disconnect the motor and run no-load test to isolate faults: soft starter failure vs motor/mechanical load failure
  4. Verify bypass contactor operation and cooling fan rotation
  5. Double-check that all motor nameplate parameters match the soft starter settings

Full PSTX Series Model List (Built-in Bypass)

PSTX xxx-600-70 (208~600V AC)

ModelOrder No.Rated Current400V Power
PSTX30-600-701SFA898103R700030 A15 kW
PSTX37-600-701SFA898104R700037 A18.5 kW
PSTX45-600-701SFA898105R700045 A22 kW
PSTX60-600-701SFA898106R700060 A30 kW
PSTX72-600-701SFA898107R700072 A37 kW
PSTX85-600-701SFA898108R700085 A45 kW
PSTX105-600-701SFA898109R7000105 A55 kW
PSTX142-600-701SFA898110R7000142 A75 kW
PSTX170-600-701SFA898111R7000170 A90 kW
PSTX210-600-701SFA898112R7000210 A110 kW
PSTX250-600-701SFA898113R7000250 A132 kW
PSTX300-600-701SFA898114R7000300 A160 kW
PSTX370-600-701SFA898115R7000370 A200 kW
PSTX470-600-701SFA898116R7000470 A250 kW
PSTX570-600-701SFA898117R7000570 A315 kW
PSTX720-600-701SFA898118R7000720 A400 kW
PSTX840-600-701SFA898119R7000840 A450 kW
PSTX1050-600-701SFA898120R70001050 A560 kW
PSTX1250-600-701SFA898121R70001250 A710 kW

PSTX xxx-690-70 (208~690V AC, including PSTX470-690-70)

ModelOrder No.Current400V kW690V kW
PSTX30-690-701SFA898203R700030 A1525
PSTX37-690-701SFA898204R700037 A18.530
PSTX45-690-701SFA898205R700045 A2237
PSTX60-690-701SFA898206R700060 A3045
PSTX72-690-701SFA898207R700072 A3755
PSTX85-690-701SFA898208R700085 A4559
PSTX105-690-701SFA898209R7000105 A5575
PSTX142-690-701SFA898210R7000142 A7590
PSTX170-690-701SFA898211R7000170 A90132
PSTX210-690-701SFA898212R7000210 A110160
PSTX250-690-701SFA898213R7000250 A132184
PSTX300-690-701SFA898214R7000300 A160220
PSTX370-690-701SFA898215R7000370 A200257
PSTX470-690-701SFA898216R7000470 A250355
PSTX570-690-701SFA898217R7000570 A315450
PSTX720-690-701SFA898218R7000720 A400560
PSTX840-690-701SFA898219R7000840 A450710
PSTX1050-690-701SFA898220R70001050 A560800
PSTX1250-690-701SFA898221R70001250 A7101000

PSTB Basic Series (Reduced Functions, Built-in Bypass)

ModelOrder No.Current400V Power
PSTB370-600-701SFA894015R7000370 A200 kW
PSTB470-600-701SFA894016R7000470 A250 kW
PSTB570-600-701SFA894017R7000570 A315 kW
PSTB720-600-701SFA894018R7000720 A400 kW
PSTB840-600-701SFA894019R7000840 A450 kW
PSTB1050-600-701SFA894020R70001050 A560 kW

PSTB does not support torque control, limp mode or pump cleaning. Only for simple fan & pump start-stop; not a direct replacement for PSTX.

PSR Compact Soft Starters (Economical, NO Built-in Bypass)

ModelOrder No.Current400V Power
PSR3-600-701SFA896103R70003 A0.75 kW
PSR6-600-701SFA896104R70006 A1.5 kW
PSR9-600-701SFA896105R70009 A2.2 kW
PSR12-600-701SFA896106R700012 A3 kW
PSR16-600-701SFA896107R700016 A4 kW
PSR25-600-701SFA896108R700025 A5.5 kW
PSR30-600-701SFA896109R700030 A7.5 kW
PSR37-600-701SFA896110R700037 A11 kW
PSR45-600-701SFA896111R700045 A15 kW
PSR60-600-701SFA896112R700060 A18.5 kW
PSR72-600-701SFA896113R700072 A22 kW
PSR85-600-701SFA896114R700085 A30 kW
PSR105-600-701SFA896115R7000105 A37 kW

Series Quick Comparison

  1. PSTX: High-end flagship, color HMI, torque control, braking, pump cleaning, Modbus, full protection, built-in bypass; preferred for export industrial projects
  2. PSTB: Mid-range basic model, monochrome screen, limited functions, built-in bypass
  3. PSR: Compact low-cost version, no built-in bypass, requires external bypass contactor; only for small-power motors
  4. PSS / PST: Older legacy models, phased out; only available as spare parts for existing installations, not recommended for new projects

Optional Communication Accessories (PSTX)

PS-FBPA: 1SFA896312R1002, basic fieldbus adapter

PSTX ANYBUS Modbus RTU: 1SFA899300R1003