ALPHA6000M-S2R75GB; RSM is a custom suffix (not defined in standard factory manuals. It usually stands for built-in braking resistor, fitted keypad, special firmware version or RoHS custom version. Confirm the definition of RSM with your supplier before ordering.)
✅ Model Code Breakdown
ALPHA6000M: ALPHA6000M series, mini open-loop current vector inverter
S2: Single-phase 220V input (200~240V AC)
R75: Matched motor power 0.75kW
G: General-purpose load (constant torque)
B: Built-in braking unit (supports external braking resistor)
RSM: Custom suffix (non-standard factory code)
✅ Key Electrical Specifications
Rated input: Single-phase AC 220V, 50/60Hz
Rated output: 3-phase 0~220V
Rated output current: 4.0A
Control modes: V/F control, Sensorless Open-loop Vector, V/F separation
Starting torque: 180% rated torque at 0.5Hz
Speed regulation range: 1:200 in vector mode; 1:100 in V/F mode
Communication: Built-in RS485, Modbus-RTU
Max output frequency: 0~650Hz
Overload capacity: 150% for 60s, 200% for 3s
Protection: Overcurrent, overvoltage, undervoltage, overheating, overload, phase loss, ground fault, etc.
✅ Product Features
Compact body, small footprint, suitable for cabinets with limited installation space
AVR automatic voltage regulation, stable operation with ±20% grid voltage fluctuation
Supports motor parameter auto-tuning, strong low-frequency torque
Multiple programmable DI/DO, analog AI/AO, multi-speed, PID, counting and other functions
Independent air channel for reliable heat dissipation. Widely used for assembly lines, fans, water pumps, conveyors, small machine tools and other constant-torque applications
✅ Typical Applications
Small conveyors, packaging machinery, fans & water pumps, production lines, small extruders, woodworking machinery, food processing machinery
✅ Replacement & Compatibility
Same-series alternative: ALPHA6000E-S2R75GB (6000E is standard version; 6000M is mini version. Pinout and dimensions differ, not direct plug-and-play)
Domestic equivalent models: Inovance MD200, Invt GD10, Delta VFD-M single-phase 220V 0.75kW models
Full Technical Package for ALPHA6000M-S2R75GBRSM
- Main Circuit Terminals (S2R75GB, single-phase 220V)
| Terminal | Function | Description |
| L, N | Single-phase 220V input | AC200~240V power supply |
| +, PB | Braking resistor terminals | Built-in braking unit. Connect resistor between + and PB. Do NOT connect to DC negative (-) |
| U, V, W | 3-phase output | Connect to 3-phase 220V asynchronous motor. Never connect mains power |
| PE | Protective earth | Inverter and motor frame must be grounded together |
Critical warning: Never connect L/N to U/V/W, this will destroy the inverter immediately; PB and + can only be connected with braking resistor, short-circuit is forbidden.
- Control Circuit Terminals (S2R4GB ~ S2R75GB)
| Terminal | Function | Specification |
| X1~X6 | Multi-function DI inputs | Dry contact, common terminal COM. Factory default: X1 forward run, X2 reverse run |
| COM | DI common terminal | 24V reference ground |
| 24V | External 24V DC supply | Max 100mA. Do not short to COM directly |
| 10V | +10V analog reference | Max 20mA, for potentiometer |
| GND | Analog ground | Reference for AI/AO |
| AI1 | Analog input 1 | 0~10V / 4~20mA (selected by DIP switch), 0~20mA, 250 |
| AI2 | Analog input 2 | -10V~+10V voltage input |
| AO1, AO2 | Analog output | Configurable 0~10V or 4~20mA, selected by SW2 DIP switch |
| DO | Open-collector output | Opto-isolated, max 50mA, 0~50kHz pulse output |
| TA, TB, TC | Relay output | TA-TB NC; TA-TC NO; 250VAC/2A |
| 485+, 485- | RS485 communication | Modbus-RTU, for PLC / HMI connection |
| PLC | DI source selection terminal | Factory default: PLC shorted with 24V for NPN mode; disconnect to use PNP |
Common Wiring Schemes
- Potentiometer speed + terminal control: Potentiometer to 10V, AI1, GND; short X1-COM = forward run
- 485 communication: 485+ to A, 485to B; add termination resistor on remote side if needed
- Relay fault signal: TA-TC to PLC fault input
- Factory Reset Procedure (ALPHA6000M / 6000E compatible)
- Power on, press PRG to enter parameter menu
- Locate P0.02 (parameter initialization)
- Setting options:
0: No action
1: Clear fault records
2: Restore factory defaults (recommended)
- Confirm, wait for auto-reset. Power cycle to take effect
Frequently used basic parameters:
P0.01: Control mode 0=V/F, 2=open-loop vector (vector recommended)
P0.07: Run command source 0=keypad, 1=terminals, 2=communication
P0.03: Frequency reference source 0=keypad, 2=AI1, 8=multi-speed, 10=PID
P0.10: Max output frequency, default 50Hz, up to 650Hz
⚠️ Resistance below 100Ω will damage the built-in braking transistor. Mount resistor away from other components with sufficient clearance; resistor housing must be grounded.
Wiring: Connect resistor two wires directly between + and PB, not the “-” terminal.
- Equivalent Replacement List (single-phase 220V 0.75kW mini vector, built-in braking unit preferred)
Note: ALPHA6000M is mini type. Pinout and mounting holes differ from 6000E standard version, cannot be swapped directly
Domestic Alternatives
- Inovance MD200S0.75B (single-phase 220V, mini, built-in braking)
- Invt GD10-0R75-S2-B (GD10 mini series)
- Delta VFD007M21A (VFD-M classic small model)
- Sifang E310-2S0007
- Win-V63 0.75kW 220V single-phase
Replacement Notes
Priority check items: built-in braking unit, DI/DO quantity, AO 4-20mA support, Modbus RTU
Original unit: single-phase input, 3-phase 220V output. Replacement motor must be rated 220V 3-phase, cannot drive 380V motor directly
For easy parameter migration: ALPHA6000E-S2R75GB from same brand, but larger size and different mounting holes
- Fault Code Quick Reference (6000M)
| Fault Code | Description | Troubleshooting |
| OC | Overcurrent | Motor short circuit, earth fault, locked rotor, too short acceleration time |
| OV | Overvoltage | Fast deceleration, missing braking resistor, high grid voltage |
| LV | Undervoltage | Input phase loss, low supply voltage, poor contact of contactor |
| OH | Overheat | Blocked air channel, failed fan, high ambient temperature |
| OL | Motor overload | Overloaded machine, incorrect motor auto-tuning |
| CE | Communication error | Reversed 485 wiring, termination resistor, mismatched address / baud rate |
- Motor Auto-Tuning (Mandatory for Vector Mode)
- Set P0.01=2 (open-loop vector)
- Enter motor nameplate data: P2.00 rated power, P2.01 rated current, P2.02 rated frequency, P2.03 rated speed
- P2.04=1 (static auto-tuning, motor stationary); P2.04=2 rotating auto-tuning (motor runs no-load, higher torque accuracy)
- Confirm and start; auto-tuning finishes automatically
ALPHA6000M Multi-speed + PID Constant Pressure Water Supply Parameter Set
For ALPHA6000M‑S2R75GB (0.75kW single-phase 220V)
Note: Do not activate both functions at once. PID is for constant pressure water / air supply; multi-speed is for assembly lines, packaging machines and multi-position fixed speed switching.
Scheme A: Multi-speed Control (DI speed selection, terminal start/stop)
Control Logic
Command source: Terminal run
Frequency source: Multi-speed
DI assignment: X1 forward run, X2 reverse run, X3/X4/X5 as speed selectors (3-bit binary, up to 8 speeds)
COM is DI common terminal, NPN mode (factory PLC shorted with 24V)
Parameter List
| Param No. | Name | Setting | Remarks |
| P0.01 | Control mode | 2 | Open-loop vector (recommended); 0=V/F |
| P0.07 | Run command source | 1 | Terminal control (X1 forward / X2 reverse) |
| P0.03 | Frequency reference source | 8 | Multi-speed reference |
| P0.10 | Max frequency | 50 | Follow motor nameplate, max 650Hz |
| P0.11 | Min frequency | 0 | Adjust as required |
| P1.00 | Acc time 1 | 5 | Unit: s |
| P1.01 | Dec time 1 | 5 | Extend for frequent stopping |
| P3.00 | X1 function | 0 | Forward run |
| P3.01 | X2 function | 1 | Reverse run |
| P3.02 | X3 function | 12 | Speed selector S1 |
| P3.03 | X4 function | 13 | Speed selector S2 |
| P3.04 | X5 function | 14 | Speed selector S3 |
| P4.00 | Multi-speed 0 | 10 | Speed 0 (all S1S2S3 OFF) |
| P4.01 | Multi-speed 1 | 15 | S1 ON |
| P4.02 | Multi-speed 2 | 20 | S2 ON |
| P4.03 | Multi-speed 3 | 25 | S1+S2 ON |
| P4.04 | Multi-speed 4 | 30 | S3 ON |
| P4.05 | Multi-speed 5 | 35 | S1+S3 ON |
| P4.06 | Multi-speed 6 | 40 | S2+S3 ON |
| P4.07 | Multi-speed 7 | 50 | S1+S2+S3 ON |
Wiring Tips
No pressure / speed sensor required; only DI switch signals
If only 4 speeds are needed, use X3 and X4 only; X5 can be assigned to fault reset or other functions
Scheme B: PID Constant Pressure Water Supply (Closed-loop, 4-20mA pressure transmitter)
For small pump pressure stabilization. 4~20mA transmitter to AI1; 4mA = lower pressure, 20mA = full scale pressure
Output of this inverter is 3-phase 220V. Pump motor must be 3-phase 220V type, not 380V pump motor
Control Logic
Command source: Terminal start (X1 forward run)
Frequency source: PID output
AI1: 4~20mA pressure feedback
PID setpoint: Keypad setting (or AI2 potentiometer setpoint)
Parameter List
| Param No. | Name | Setting | Remarks |
| P0.01 | Control mode | 0 | V/F preferred for pumps |
| P0.07 | Run command source | 1 | Terminal start X1 forward |
| P0.03 | Frequency reference source | 10 | PID reference |
| P0.10 | Max frequency | 50 | Pump rated frequency |
| P0.11 | Min frequency | 20 | Prevent dry running at low speed |
| P1.00 | Acc time | 10 | Avoid water hammer |
| P1.01 | Dec time | 15 | Pumps must not stop rapidly |
| P5.00 | PID enable | 1 | Enable PID |
| P5.01 | PID setpoint source | 0 | Keypad setpoint; 1=AI2 external setpoint |
| P5.02 | PID feedback source | 0 | AI1 feedback |
| P5.03 | PID proportional gain Kp | 30 | Initial value; reduce if oscillating |
| P5.04 | PID integral time Ti | 2 | Unit: s; increase if pressure fluctuates |
| P5.05 | PID derivative time Td | 0 | Derivative unused for water supply |
| P5.06 | PID deviation limit | 5 | Fast adjustment over this deviation |
| P5.07 | PID output upper limit | 100 | Corresponds to max frequency |
| P5.08 | PID output lower limit | 0 | |
| P5.09 | PID sleep function | 0 | 0=disable; 1=enable sleep at low flow |
| P6.00 | AI1 type selection | 1 | 1=4~20mA; 0=0~10V |
| P6.01 | AI1 min value | 0 | Pressure at 4mA (MPa) |
| P6.02 | AI1 max value | 1 | Pressure at 20mA (MPa), adjust as per transmitter |
Wiring
Pressure transmitter: Powered by inverter 24V, signal+ → AI1, signal→ GND
Set AI1 DIP switch to current mode (4-20mA)
Short X1-COM to start; open to stop
PID Tuning Sequence (Important)
- Disable PID first (P5.00=0), run pump manually to confirm rotation direction
- Confirm transmitter range: e.g. 0~1MPa, P6.01=0, P6.02=1.0
- P5.00=1 to enable PID, set target pressure on keypad e.g. 0.4MPa
- Troubleshooting:
Pressure oscillates: Reduce Kp (e.g. to 15), increase Ti
Pressure rises slowly: Increase Kp, reduce Ti
Severe overshoot: Reduce Kp, increase Ti
- Sleep function (P5.09=1): At low flow, when pressure exceeds setpoint for a period, inverter drops to min frequency then stops; restarts when pressure drops below wake-up threshold. Suitable for small water systems.
Switching Tip
Multi-speed: P0.03=8
PID constant pressure: P0.03=10
Change P0.03 and power cycle inverter for best stability.
Full ALPHA6000M Series Model List (ALPHA Mini Vector Inverters)
- Model Coding Rule
ALPHA6000M S2 R75 G B RSM
- S2: Single-phase 220V input; 3: 3-phase 380V input
- R75=0.75kW; 1R5=1.5kW; 2R2=2.2kW
- G: General constant torque load; P: Fan & pump variable torque load
- B: Built-in braking unit (this model has B)
- RSM: RS485 Modbus communication option suffix
Important note: S2R4GB and S2R75GB only support V/F, no SVC vector; higher power models support vector control
- Single-phase 220V (S2 series, mini type, same family as your unit)
Standard models (built-in braking unit GB)
- ALPHA6000M-S2R4GB | 0.4kW
- ALPHA6000M-S2R75GB | 0.75kW (base model of your unit)
- ALPHA6000M-S21R5GB | 1.5kW
- ALPHA6000M-S22R2GB | 2.2kW
With communication suffix RSM
S2R4GBRSM
S2R75GBRSM (your model)
S21R5GBRSM
S22R2GBRSM
- 3-phase 380V (3 series, dual rating G/P)
Small power integrated type (built-in braking unit)
- ALPHA6000M-3R75GB/31R5PB | 0.75kW(G)/1.5kW(P)
- ALPHA6000M-31R5GB/32R2PB | 1.5kW(G)/2.2kW(P)
- ALPHA6000M-32R2GB/3004PB | 2.2kW(G)/4kW(P)
- ALPHA6000M-3004GB/35R5PB | 4kW(G)/5.5kW(P)
- ALPHA6000M-35R5GB/37R5PB-N | 5.5kW(G)/7.5kW(P)
- ALPHA6000M-37R5GB/3011PB | 7.5kW(G)/11kW(P)
Medium power (SJ suffix, external braking unit required)
- 3011GB/3015PB-SJ | 11/15kW
- 3015GB/3018PB-SJ | 15/18.5kW
- 3018GB/3022PB-SJ | 18.5/22kW
- 3022GB-SJ | 22kW
Fan & pump only P type (no G rating)
3030P-N, 3037P-N, 3045P-N … up to 3630P-N
- ALPHA6000M vs 6000E (Replacement Reference)
- 6000M: Mini compact version
Max power 22kW; small S2 single-phase units, compact terminals; S2R4/S2R75 no vector support; smaller mounting cutout, not interchangeable with 6000E.
- 6000E: Standard universal version
Power range 0.75~630kW; vector supported on all ratings; larger enclosure and mounting holes, incompatible with M series housing.
- Same Power Alternatives for S2R75GBRSM
Same series original: ALPHA6000M-S2R75GBRSM
Same power without communication: ALPHA6000M-S2R75GB
3-phase equivalent: 3R75GB (3-phase 380V input)
- Rated Current Table (Single-phase S2)
| Model | Power | Input Current | Output Current |
| S2R4GB | 0.4kW | 5.1A | 2.4A |
| S2R75GB | 0.75kW | 9.2A | 4.5A |
| S21R5GB | 1.5kW | 13.1A | 7A |
| S22R2GB | 2.2kW | 23A | 10A |