ALPHA6000M-S2R75GBRSM Mini Vector Inverter - Contactor,circuit breaker,sensor,Encoder,PLC,Converter

Wechat: +86-13184948252  WhatsaApp: 0086-13811255435  E-mail:  kent@bestcontactor.com

About    Contact    |    

 ALPHA6000M-S2R75GBRSM Mini Vector Inverter - Contactor,circuit breaker,sensor,Encoder,PLC,Converter

solar inverter/PLC/

 ALPHA6000M-S2R75GBRSM Mini Vector Inverter

ALPHA6000M-S2R75GB; RSM is a custom suffix (not defined in standard factory manuals. It usually stands for built-in braking resistor, fitted keypad, special firmware version or RoHS custom version. Confirm the definition of RSM with your supplier before ordering.) ✅ Model Code Breakdown ALPHA6000M: ALPHA6000M series, mini open-loop current vector inverter S2: Single-phase 220V input (200~240V ...

  • Product Details

ALPHA6000M-S2R75GB; RSM is a custom suffix (not defined in standard factory manuals. It usually stands for built-in braking resistor, fitted keypad, special firmware version or RoHS custom version. Confirm the definition of RSM with your supplier before ordering.)

✅ Model Code Breakdown

ALPHA6000M: ALPHA6000M series, mini open-loop current vector inverter

S2: Single-phase 220V input (200~240V AC)

R75: Matched motor power 0.75kW

G: General-purpose load (constant torque)

B: Built-in braking unit (supports external braking resistor)

RSM: Custom suffix (non-standard factory code)

✅ Key Electrical Specifications

Rated input: Single-phase AC 220V, 50/60Hz

Rated output: 3-phase 0~220V

Rated output current: 4.0A

Control modes: V/F control, Sensorless Open-loop Vector, V/F separation

Starting torque: 180% rated torque at 0.5Hz

Speed regulation range: 1:200 in vector mode; 1:100 in V/F mode

Communication: Built-in RS485, Modbus-RTU

Max output frequency: 0~650Hz

Overload capacity: 150% for 60s, 200% for 3s

Protection: Overcurrent, overvoltage, undervoltage, overheating, overload, phase loss, ground fault, etc.

✅ Product Features

Compact body, small footprint, suitable for cabinets with limited installation space

AVR automatic voltage regulation, stable operation with ±20% grid voltage fluctuation

Supports motor parameter auto-tuning, strong low-frequency torque

Multiple programmable DI/DO, analog AI/AO, multi-speed, PID, counting and other functions

Independent air channel for reliable heat dissipation. Widely used for assembly lines, fans, water pumps, conveyors, small machine tools and other constant-torque applications

✅ Typical Applications

Small conveyors, packaging machinery, fans & water pumps, production lines, small extruders, woodworking machinery, food processing machinery

✅ Replacement & Compatibility

Same-series alternative: ALPHA6000E-S2R75GB (6000E is standard version; 6000M is mini version. Pinout and dimensions differ, not direct plug-and-play)

Domestic equivalent models: Inovance MD200, Invt GD10, Delta VFD-M single-phase 220V 0.75kW models

Full Technical Package for ALPHA6000M-S2R75GBRSM

  1. Main Circuit Terminals (S2R75GB, single-phase 220V)
TerminalFunctionDescription
L, NSingle-phase 220V inputAC200~240V power supply
+, PBBraking resistor terminalsBuilt-in braking unit. Connect resistor between + and PB. Do NOT connect to DC negative (-)
U, V, W3-phase outputConnect to 3-phase 220V asynchronous motor. Never connect mains power
PEProtective earthInverter and motor frame must be grounded together

Critical warning: Never connect L/N to U/V/W, this will destroy the inverter immediately; PB and + can only be connected with braking resistor, short-circuit is forbidden.

  1. Control Circuit Terminals (S2R4GB ~ S2R75GB)
TerminalFunctionSpecification
X1~X6Multi-function DI inputsDry contact, common terminal COM. Factory default: X1 forward run, X2 reverse run
COMDI common terminal24V reference ground
24VExternal 24V DC supplyMax 100mA. Do not short to COM directly
10V+10V analog referenceMax 20mA, for potentiometer
GNDAnalog groundReference for AI/AO
AI1Analog input 10~10V / 4~20mA (selected by DIP switch), 0~20mA, 250
AI2Analog input 2-10V~+10V voltage input
AO1, AO2Analog outputConfigurable 0~10V or 4~20mA, selected by SW2 DIP switch
DOOpen-collector outputOpto-isolated, max 50mA, 0~50kHz pulse output
TA, TB, TCRelay outputTA-TB NC; TA-TC NO; 250VAC/2A
485+, 485-RS485 communicationModbus-RTU, for PLC / HMI connection
PLCDI source selection terminalFactory default: PLC shorted with 24V for NPN mode; disconnect to use PNP

Common Wiring Schemes

  1. Potentiometer speed + terminal control: Potentiometer to 10V, AI1, GND; short X1-COM = forward run
  2. 485 communication: 485+ to A, 485to B; add termination resistor on remote side if needed
  3. Relay fault signal: TA-TC to PLC fault input
  4. Factory Reset Procedure (ALPHA6000M / 6000E compatible)
  5. Power on, press PRG to enter parameter menu
  6. Locate P0.02 (parameter initialization)
  7. Setting options:

0: No action

1: Clear fault records

2: Restore factory defaults (recommended)

  1. Confirm, wait for auto-reset. Power cycle to take effect

Frequently used basic parameters:

P0.01: Control mode 0=V/F, 2=open-loop vector (vector recommended)

P0.07: Run command source 0=keypad, 1=terminals, 2=communication

P0.03: Frequency reference source 0=keypad, 2=AI1, 8=multi-speed, 10=PID

P0.10: Max output frequency, default 50Hz, up to 650Hz

⚠️ Resistance below 100Ω will damage the built-in braking transistor. Mount resistor away from other components with sufficient clearance; resistor housing must be grounded.

Wiring: Connect resistor two wires directly between + and PB, not the “-” terminal.

  1. Equivalent Replacement List (single-phase 220V 0.75kW mini vector, built-in braking unit preferred)

Note: ALPHA6000M is mini type. Pinout and mounting holes differ from 6000E standard version, cannot be swapped directly

Domestic Alternatives

  1. Inovance MD200S0.75B (single-phase 220V, mini, built-in braking)
  2. Invt GD10-0R75-S2-B (GD10 mini series)
  3. Delta VFD007M21A (VFD-M classic small model)
  4. Sifang E310-2S0007
  5. Win-V63 0.75kW 220V single-phase

Replacement Notes

Priority check items: built-in braking unit, DI/DO quantity, AO 4-20mA support, Modbus RTU

Original unit: single-phase input, 3-phase 220V output. Replacement motor must be rated 220V 3-phase, cannot drive 380V motor directly

For easy parameter migration: ALPHA6000E-S2R75GB from same brand, but larger size and different mounting holes

  1. Fault Code Quick Reference (6000M)
Fault CodeDescriptionTroubleshooting
OCOvercurrentMotor short circuit, earth fault, locked rotor, too short acceleration time
OVOvervoltageFast deceleration, missing braking resistor, high grid voltage
LVUndervoltageInput phase loss, low supply voltage, poor contact of contactor
OHOverheatBlocked air channel, failed fan, high ambient temperature
OLMotor overloadOverloaded machine, incorrect motor auto-tuning
CECommunication errorReversed 485 wiring, termination resistor, mismatched address / baud rate
  1. Motor Auto-Tuning (Mandatory for Vector Mode)
  2. Set P0.01=2 (open-loop vector)
  3. Enter motor nameplate data: P2.00 rated power, P2.01 rated current, P2.02 rated frequency, P2.03 rated speed
  4. P2.04=1 (static auto-tuning, motor stationary); P2.04=2 rotating auto-tuning (motor runs no-load, higher torque accuracy)
  5. Confirm and start; auto-tuning finishes automatically

ALPHA6000M Multi-speed + PID Constant Pressure Water Supply Parameter Set

For ALPHA6000M‑S2R75GB (0.75kW single-phase 220V)

Note: Do not activate both functions at once. PID is for constant pressure water / air supply; multi-speed is for assembly lines, packaging machines and multi-position fixed speed switching.

Scheme A: Multi-speed Control (DI speed selection, terminal start/stop)

Control Logic

Command source: Terminal run

Frequency source: Multi-speed

DI assignment: X1 forward run, X2 reverse run, X3/X4/X5 as speed selectors (3-bit binary, up to 8 speeds)

COM is DI common terminal, NPN mode (factory PLC shorted with 24V)

Parameter List

Param No.NameSettingRemarks
P0.01Control mode2Open-loop vector (recommended); 0=V/F
P0.07Run command source1Terminal control (X1 forward / X2 reverse)
P0.03Frequency reference source8Multi-speed reference
P0.10Max frequency50Follow motor nameplate, max 650Hz
P0.11Min frequency0Adjust as required
P1.00Acc time 15Unit: s
P1.01Dec time 15Extend for frequent stopping
P3.00X1 function0Forward run
P3.01X2 function1Reverse run
P3.02X3 function12Speed selector S1
P3.03X4 function13Speed selector S2
P3.04X5 function14Speed selector S3
P4.00Multi-speed 010Speed 0 (all S1S2S3 OFF)
P4.01Multi-speed 115S1 ON
P4.02Multi-speed 220S2 ON
P4.03Multi-speed 325S1+S2 ON
P4.04Multi-speed 430S3 ON
P4.05Multi-speed 535S1+S3 ON
P4.06Multi-speed 640S2+S3 ON
P4.07Multi-speed 750S1+S2+S3 ON

Wiring Tips

No pressure / speed sensor required; only DI switch signals

If only 4 speeds are needed, use X3 and X4 only; X5 can be assigned to fault reset or other functions

Scheme B: PID Constant Pressure Water Supply (Closed-loop, 4-20mA pressure transmitter)

For small pump pressure stabilization. 4~20mA transmitter to AI1; 4mA = lower pressure, 20mA = full scale pressure

Output of this inverter is 3-phase 220V. Pump motor must be 3-phase 220V type, not 380V pump motor

Control Logic

Command source: Terminal start (X1 forward run)

Frequency source: PID output

AI1: 4~20mA pressure feedback

PID setpoint: Keypad setting (or AI2 potentiometer setpoint)

Parameter List

Param No.NameSettingRemarks
P0.01Control mode0V/F preferred for pumps
P0.07Run command source1Terminal start X1 forward
P0.03Frequency reference source10PID reference
P0.10Max frequency50Pump rated frequency
P0.11Min frequency20Prevent dry running at low speed
P1.00Acc time10Avoid water hammer
P1.01Dec time15Pumps must not stop rapidly
P5.00PID enable1Enable PID
P5.01PID setpoint source0Keypad setpoint; 1=AI2 external setpoint
P5.02PID feedback source0AI1 feedback
P5.03PID proportional gain Kp30Initial value; reduce if oscillating
P5.04PID integral time Ti2Unit: s; increase if pressure fluctuates
P5.05PID derivative time Td0Derivative unused for water supply
P5.06PID deviation limit5Fast adjustment over this deviation
P5.07PID output upper limit100Corresponds to max frequency
P5.08PID output lower limit0
P5.09PID sleep function00=disable; 1=enable sleep at low flow
P6.00AI1 type selection11=4~20mA; 0=0~10V
P6.01AI1 min value0Pressure at 4mA (MPa)
P6.02AI1 max value1Pressure at 20mA (MPa), adjust as per transmitter

Wiring

Pressure transmitter: Powered by inverter 24V, signal+ → AI1, signal→ GND

Set AI1 DIP switch to current mode (4-20mA)

Short X1-COM to start; open to stop

PID Tuning Sequence (Important)

  1. Disable PID first (P5.00=0), run pump manually to confirm rotation direction
  2. Confirm transmitter range: e.g. 0~1MPa, P6.01=0, P6.02=1.0
  3. P5.00=1 to enable PID, set target pressure on keypad e.g. 0.4MPa
  4. Troubleshooting:

Pressure oscillates: Reduce Kp (e.g. to 15), increase Ti

Pressure rises slowly: Increase Kp, reduce Ti

Severe overshoot: Reduce Kp, increase Ti

  1. Sleep function (P5.09=1): At low flow, when pressure exceeds setpoint for a period, inverter drops to min frequency then stops; restarts when pressure drops below wake-up threshold. Suitable for small water systems.

Switching Tip

Multi-speed: P0.03=8

PID constant pressure: P0.03=10

Change P0.03 and power cycle inverter for best stability.

Full ALPHA6000M Series Model List (ALPHA Mini Vector Inverters)

  1. Model Coding Rule

ALPHA6000M S2 R75 G B RSM

  1. S2: Single-phase 220V input; 3: 3-phase 380V input
  2. R75=0.75kW; 1R5=1.5kW; 2R2=2.2kW
  3. G: General constant torque load; P: Fan & pump variable torque load
  4. B: Built-in braking unit (this model has B)
  5. RSM: RS485 Modbus communication option suffix

Important note: S2R4GB and S2R75GB only support V/F, no SVC vector; higher power models support vector control

  1. Single-phase 220V (S2 series, mini type, same family as your unit)

Standard models (built-in braking unit GB)

  1. ALPHA6000M-S2R4GB | 0.4kW
  2. ALPHA6000M-S2R75GB | 0.75kW (base model of your unit)
  3. ALPHA6000M-S21R5GB | 1.5kW
  4. ALPHA6000M-S22R2GB | 2.2kW

With communication suffix RSM

S2R4GBRSM

S2R75GBRSM (your model)

S21R5GBRSM

S22R2GBRSM

  1. 3-phase 380V (3 series, dual rating G/P)

Small power integrated type (built-in braking unit)

  1. ALPHA6000M-3R75GB/31R5PB | 0.75kW(G)/1.5kW(P)
  2. ALPHA6000M-31R5GB/32R2PB | 1.5kW(G)/2.2kW(P)
  3. ALPHA6000M-32R2GB/3004PB | 2.2kW(G)/4kW(P)
  4. ALPHA6000M-3004GB/35R5PB | 4kW(G)/5.5kW(P)
  5. ALPHA6000M-35R5GB/37R5PB-N | 5.5kW(G)/7.5kW(P)
  6. ALPHA6000M-37R5GB/3011PB | 7.5kW(G)/11kW(P)

Medium power (SJ suffix, external braking unit required)

  1. 3011GB/3015PB-SJ | 11/15kW
  2. 3015GB/3018PB-SJ | 15/18.5kW
  3. 3018GB/3022PB-SJ | 18.5/22kW
  4. 3022GB-SJ | 22kW

Fan & pump only P type (no G rating)

3030P-N, 3037P-N, 3045P-N … up to 3630P-N

  1. ALPHA6000M vs 6000E (Replacement Reference)
  2. 6000M: Mini compact version

Max power 22kW; small S2 single-phase units, compact terminals; S2R4/S2R75 no vector support; smaller mounting cutout, not interchangeable with 6000E.

  1. 6000E: Standard universal version

Power range 0.75~630kW; vector supported on all ratings; larger enclosure and mounting holes, incompatible with M series housing.

  1. Same Power Alternatives for S2R75GBRSM

Same series original: ALPHA6000M-S2R75GBRSM

Same power without communication: ALPHA6000M-S2R75GB

3-phase equivalent: 3R75GB (3-phase 380V input)

  1. Rated Current Table (Single-phase S2)
ModelPowerInput CurrentOutput Current
S2R4GB0.4kW5.1A2.4A
S2R75GB0.75kW9.2A4.5A
S21R5GB1.5kW13.1A7A
S22R2GB2.2kW23A10A

Prev:

Next:

Leave a Reply