Model code explanation: LC1E = TeSys E series contactor; 18 = rated 18A at 400V under AC-3 duty; 01 = built-in 1 normally closed contact (1NC)
⚠️ The LC1E series has been discontinued (production stopped in July 2020). The standard replacement model is LC1N1801, fully compatible in mounting, terminal layout and performance.
Key Specifications
Main contacts: 3P, 3NO
AC-3 (motor duty): 18A @ 400V; AC-1 (resistive load): 25A
Motor rating: 7.5kW @ 380/400V; 4kW @ 220V; 9kW @ 440V
Insulation voltage Ui: 690V; Impulse withstand voltage Uimp: 6kV
Auxiliary contact: 1NC (Normally Closed)
Mounting: DIN rail / base plate screw mounting
Overall dimensions: W45mm × H74mm × D80mm, net weight ≈0.3kg
Protection class: IP20; Operating temperature: -5~+55℃; No derating up to 3000m altitude
Mechanical life: 10 million operations; AC-3 electrical life: 1.2 million operations; Max operating frequency: 1800 cycles/hour
Coil suffix definitions (complete model number)
LC1E1801B5: AC24V, 50Hz
LC1E1801F5: AC110V, 50Hz
LC1E1801M5: AC220V, 50Hz (most common in China)
LC1E1801Q5: AC380V, 50Hz
Suffix 7 = 50/60Hz universal; suffix 6 = 60Hz only
Coil power consumption (M5 220V example)
Inrush VA: 95VA; Sealed holding VA: 8.5VA; Coil heat dissipation: 2~3W
Pick-up voltage: 0.85~1.1Uc; Drop-out voltage: 0.3~0.6Uc
Tightening torque & wire gauge
Torque for main circuit and control circuit terminals: 1.2 N·m
Solid wire: 1.5~6mm²; Stranded wire (with ferrule): 1~4mm²
Matching selection reference
Matching thermal overload relay: LRD07 / LRN07 (current range suitable for 18A)
Accessories: LA1EN auxiliary contact block, LA9D coil surge suppressor, mechanical interlock block
Domestic alternative: CJX2-1801 (similar outline, pay attention to mounting hole and marking differences)
Troubleshooting Guide
- Coil energized but no pull-in: Check if coil voltage is within 0.85~1.1Uc; inspect broken coil wire and loose terminals
- Pulled in but main circuit no continuity: Main contact erosion, contact welding, loose wiring
- Buzzing / chattering: Undervoltage, large harmonic distortion, dust accumulated on core faces
- Failed to drop out after power-off: Welded main contacts, core stuck by oil and dirt
Detailed Installation Procedure for Schneider LC1E1801 Contactor
⚠️ Safety precondition: Operated by qualified electricians; cut off all power supply and verify zero voltage before installation. LC1E1801: 3P main contacts with built-in 1NC auxiliary contact. Terminal marking: Main circuit L1/L2/L3 (line side, incoming), T1/T2/T3 (load side, outgoing); Coil A1, A2; Auxiliary contact: 95, 96 (1NC)
- Pre-installation Preparation
- Verify coil voltage: LC1E1801M5=AC220V, Q5=AC380V, F5=AC110V. Coil rated voltage must match control circuit voltage to avoid coil burnout.
- Visual inspection: No shell cracks, intact terminals, armature moves freely without jamming when pressed manually.
- Tools: 2 Phillips screwdriver, wire stripper, multimeter, torque wrench; 35mm standard DIN rail or mounting base plate.
- Wire specification
Main circuit solid wire: 1.5~6mm²; Stranded wire with ferrule: 1~4mm²
Control circuit (A1/A2, auxiliary contacts): 0.75~1.5mm²
Tightening torque: 1.2 N·m (avoid over-tightening to prevent thread stripping, or loose connection causing overheating)
- Environmental check: Cabinet temperature -5℃~+55℃, keep away from dust, moisture and oil. Mount vertically upright. Do NOT install upside down or horizontally.
- Fixing (2 methods: DIN rail / base plate screw mounting)
Method 1: 35mm DIN rail mounting (preferred)
- The contactor has upper hooks and a spring locking clip at the bottom.
- Hook the upper notch onto the top edge of the DIN rail first.
- Press the bottom of the contactor down until you hear a click, the bottom clip locks onto the rail.
- Shake lightly to confirm firm fixation. Removal: Use a flat screwdriver to pry down the bottom clip and pull out the contactor.
Method 2: Screw mounting on insulated base plate (no rail)
- Mark and drill holes on the insulated plate according to the rear mounting holes (for M4 screws).
- Insert screws diagonally, pre-tighten, then torque evenly in diagonal sequence; do not force one side to avoid casing deformation.
- Accessory Fitting (Optional: LA1EN auxiliary block, mechanical interlock etc.)
- Top auxiliary contact block: Align with the slots on top of contactor, push vertically down until latched.
- Thermal relay LRD/LRN: Clip directly underneath the contactor, align positioning slots; the linkage will engage automatically.
- Surge suppressor LA9D: Clip beside coil terminals A1/A2, absorbs back EMF to protect PLC output points.
- Wiring Sequence (Main circuit → Auxiliary contacts → Coil control circuit)
Standard routing: Line side on top, load side on bottom. L1/L2/L3 on top for three-phase supply; T1/T2/T3 at bottom for load (motor).
- Main circuit wiring
Strip insulation 5~6mm, avoid loose copper strands; ferrules are mandatory for stranded wire.
Keep phase sequence L1→T1, L2→T2, L3→T3 as per drawing.
Torque screws to 1.2N·m; only one conductor per terminal.
- Built-in auxiliary contact (95-96, NC)
Terminals 95-96: Conductive when coil de-energized, open when contactor pulls in. Usually used in stop circuit or fault feedback for motor control.
If NO contact is required, add LA1EN auxiliary block.
- Coil A1, A2 (control circuit)
A1 and A2 have no polarity for AC. For AC220V: one to live, one to neutral; for AC380V: connect to two different phases.
Wire in series with start/stop pushbuttons, thermal relay NC contact or PLC outputs.
Route control wires separately from power cables to reduce interference.
Terminal summary:
L1/L2/L3 (Supply In), T1/T2/T3 (Load Out), A1 A2 (Coil), 95-96 (Built-in 1NC)
- Pre-power-on Inspection
- Visual check: All terminals tightened, no exposed copper, no short circuit risk, no loose strands touching adjacent terminals.
- Continuity test with multimeter:
De-energized state: No continuity between L-T; 95-96 auxiliary contact is conductive.
Manually press armature to simulate pull-in: L-T becomes conductive, 95-96 opens.
- Double-check coil voltage; separate power supply for main circuit and control circuit.
- Power-on Commissioning
- Energize control circuit only, keep main power off: Press start button, contactor should pull-in smoothly without chattering or buzzing; release stop button for reliable drop-out.
Chattering: Low supply voltage, loose wiring or dirty core surfaces.
- After control circuit test passes, energize main circuit and run on load.
- Temperature check after 10min running: No obvious overheating at terminals (temperature rise indicates poor connection).
- Installation Notes & Prohibitions
- Keep minimum clearance ≥10mm between contactor and fuse / MCB for heat dissipation.
- Minimum spacing ≥5mm between multiple contactors; increase spacing for high ambient temperature.
- Do not plug or remove auxiliary blocks when energized.
- Do not trap wire insulation inside terminal clamps; copper must be fully clamped.
- LC1E discontinued, spare replacement: LC1N1801, same mounting size and terminal definition.
- Common Installation Faults
No pull-in after energized: Wrong A1/A2 voltage, broken control wire or open button circuit
Buzzing when pulled in: Undervoltage, dust or rust on magnetic core faces
Cannot drop out after power cut: Welded main contacts or core jammed by oil
Schneider Easy TeSys E (LC1E / EasyPact TVS) Series Full List
Important note: LC1E series fully discontinued in July 2020. Direct replacement: LC1N series, identical mounting dimensions and terminal layout.
Model rule: LC1E + current code + auxiliary contact code (10=1NO; 01=1NC) + coil suffix
Coil suffix description:
B5=AC24V 50Hz; F5=AC110V 50Hz; M5=AC220V 50Hz; Q5=AC380V 50Hz
B7/F7/M7/Q7=50/60Hz universal; BD=DC24V; 6=60Hz only
- 3P LC1E Contactors (AC-3 @400V)
| Base Model | AC-3 Current | Motor Rating @400V | Built-in Auxiliary Contact |
| LC1E0610 | 6A | 2.2kW | 1NO |
| LC1E0601 | 6A | 2.2kW | 1NC |
| LC1E0910 | 9A | 4kW | 1NO |
| LC1E0901 | 9A | 4kW | 1NC |
| LC1E1210 | 12A | 5.5kW | 1NO |
| LC1E1201 | 12A | 5.5kW | 1NC |
| LC1E1810 | 18A | 7.5kW | 1NO |
| LC1E1801 | 18A | 7.5kW | 1NC (your referenced model) |
| LC1E2510 | 25A | 11kW | 1NO |
| LC1E2501 | 25A | 11kW | 1NC |
| LC1E3210 | 32A | 15kW | 1NO |
| LC1E3201 | 32A | 15kW | 1NC |
| LC1E3810 | 38A | 18.5kW | 1NO |
| LC1E3801 | 38A | 18.5kW | 1NC |
| LC1E4011 | 40A | 18.5kW | 1NO+1NC |
| LC1E5011 | 50A | 22kW | 1NO+1NC |
| LC1E6511 | 65A | 30kW | 1NO+1NC |
| LC1E8011 | 80A | 37kW | 1NO+1NC |
| LC1E9511 | 95A | 45kW | 1NO+1NC |
| LC1E120 | 120A | 55kW | No built-in, add auxiliary block separately |
| LC1E160 | 160A | 75kW | No built-in, add auxiliary block separately |
| LC1E200 | 200A | 90kW | No built-in, add auxiliary block separately |
| LC1E300 | 300A | 160kW | No built-in, add auxiliary block separately |
Example complete model: LC1E1801M7 = 18A, 1NC, AC220V 50/60Hz universal
- Matching LRE Thermal Overload Relays (plug-on fit for LC1E)
LRE01N~LRE35N (for 06~38A); LRE322N~LRE365N (for 40~300A)
LRE01N: 0.1~0.16A
LRE02N: 0.16~0.25A
LRE03N: 0.25~0.4A
LRE04N: 0.4~0.63A
LRE05N: 0.63~1A
LRE06N: 1~1.6A
LRE07N: 1.6~2.5A
LRE08N: 2.5~4A
LRE09N: 4~6A
LRE10N: 6~10A
LRE12N: 10~16A
LRE14N: 16~24A
LRE16N: 24~36A
LRE21N: 28~36A
LRE22N: 36~48A
LRE322N: 55~70A
LRE323N: 63~80A
LRE353N: 80~104A
LRE355N: 104~135A
LRE365N: 130~165A
- E-series Accessories
- LA1EN: Top-mounted auxiliary contact block (1NO / 1NC, stackable)
- LAEM1: Mechanical interlock module (for two contactor interlocking)
- LA9D: Coil surge suppressor (RC network / varistor, PLC output protection)
- LAEB1N / LAEB3N: Thermal relay independent base (when not mounted under contactor)
- LA1EBN: Timed auxiliary contact block (on-delay / off-delay)
- 2P / 4P LC1E (single phase, lighting & resistive load, AC-1 duty)
LC1E0920: 2P 9A
LC1E2520: 2P 25A
LC1E0940: 4P 9A
LC1E2540: 4P 25A
LC1E4040: 4P 40A
4P versions commonly used for HVAC, lighting and heating resistive loads
- Cross Reference Table
| Old LC1E Model | Direct Replacement LC1N |
| LC1E0601/0610 | LC1N0601 / LC1N0610 |
| LC1E0901/0910 | LC1N0901 / LC1N0910 |
| LC1E1201/1210 | LC1N1201 / LC1N1210 |
| LC1E1801/1810 | LC1N1801 / LC1N1810 |
| LC1E2501/2510 | LC1N2501 / LC1N2510 |
| LC1E3201/3210 | LC1N3201 / LC1N3210 |
| LC1E3801/3810 | LC1N3801 / LC1N3810 |
| LC1E40~95 | LC1N40~95 |