LC1G: TeSys Giga series contactor
500: AC-3 rated 500A @ 440V
KUEN: Wide-voltage coil 100–250V AC/DC, global standard version, built-in 1NO + 1NC auxiliary contacts
| Item | Parameter |
| Poles | 3P, 3 main NO contacts |
| AC-3 @ 440V | 500A (≤60℃) |
| AC-1 @ 1000V | 700A (≤40℃) |
| Rated insulation voltage Ui | 1000V AC |
| Impulse withstand voltage Uimp | 8kV |
| Coil | 100~250V AC/DC wide-range electronic coil |
| Built-in auxiliary contacts | 1NO + 1NC |
| Motor power AC-3 @ 400V | 250kW |
| Mechanical endurance | 8 million operations |
| Maximum operating frequency (AC-3) | 600 cycles/hour |
| Operating time | Make: 40~70ms, Break: 15~50ms |
| Short-time withstand current Icw | 4kA / 10s |
| Main circuit wiring | Max. 185mm² cable, busbar 32×10mm, tightening torque 35N·m |
| Overall dimensions | H225 × W140 × D226 mm, net weight 7.5kg |
| Operating temperature | -25~+60℃ |
| Certifications | CCC, CE, cULus, EAC, UKCA |
| Protection class | IP2X (with front cover fitted) |
Typical Applications
High-power motor starting, water pumps, fans, compressors, low-voltage capacitor switching, busbar circuit switching; suitable for upstream of variable frequency drives and high-power distribution circuits.
Equivalent Models & Spare Parts within the Series
Same current rating with different coil: LC1G500KUEN = 100–250V AC/DC; separate 24V, 48V, 230V single-voltage versions available
Matching thermal overload relay: LR9G series electronic thermal relays
Accessories: Auxiliary contact blocks, mechanical interlocks, surge suppressors, terminal shrouds, interlock mechanisms
Comparison with Older Generations
Direct replacement for legacy large LC1D contactors (LC1D475, LC1D620, etc.). Advantages of TeSys Giga: wide-voltage electronic coil, low holding power consumption, integrated surge suppression, enhanced short-time withstand, B10d safety life rating, compliant for safety-related machinery (ISO13849).
LC1G500KUEN (TeSys Giga) Troubleshooting Guide
Important note: KUEN uses an electronic wide-voltage coil (100–250V AC/DC). It differs from conventional AC coils and does not have a shading ring. Failure behaviour is not the same as LC1D models. The unit is fitted with contact wear diagnostic LED; always check the indicator first.
Safety precaution: Isolate and verify zero voltage on main circuit and control circuit. Do not remove main terminal cover while energised for this high-current device.
- Coil energised but contactor does not close (no movement)
Quick Check Sequence
- Check front diagnostic LED first: TeSys Giga electronic coil diagnostic code: 2 repeated flashes = control voltage below 80% of minimum operating voltage
- Measure voltage across A1/A2 while control command is active: Must stay within 100–250V. Long control cables, insufficient conductor cross-section and excessive voltage drop are common site issues.
- Resistance measurement across A1-A2 with power removed: Electronic coil does not have a fixed resistance value. Do not judge coil health by resistance reading, do not compare with LC1D coil resistance.
Root Causes
Control circuit: Failed PLC output, faulty pushbutton/emergency stop, open thermal relay NC contact, safety chain open, broken latching circuit, loose terminals
Power supply: Undersized power source, excessive ripple on DC supply, residual / induced voltage (capacitance effect on long cables)
Mechanical binding: Dust, metallic debris or arc powder inside magnetic circuit; misfitted auxiliary contact block, deformed return spring, lightly welded main contacts jamming the moving assembly
Electronic coil module failure: Lightning surge, overvoltage damaging the built-in driver PCB (Giga coil includes circuit board, not simple enamelled wire winding)
Ambient factors: Temperature >60℃, humidity / corrosive atmosphere causing internal electronic component failure
Remedial Actions
Bench test the coil by applying a stable rated supply directly to A1/A2, to isolate faults between control circuit and contactor itself.
Clean dust and metallic debris from pole faces; inspect auxiliary attachments for binding.
Electronic coil can be replaced individually if defective; full contactor replacement is not mandatory.
- Chatter, buzzing or repeated bouncing after closing
⚠️ Critical reminder: LC1G electronic coil has no shading ring, do not attempt troubleshooting by replacing shading rings as on older AC contactors!
Root Causes
- Unstable control voltage / voltage sag under load: High source impedance, voltage dip when other large loads cycle, insufficient PLC output drive capacity
- Faulty latching circuit: Oxidation / poor contact on the 1NO latching auxiliary contact, loose latching wiring causing loss of holding voltage immediately after closure (most frequent cause)
- Control circuit interference: VFD harmonic noise, control cables routed alongside power cables disturbing the coil driver PCB
- High mechanical friction: Dust accumulation on magnetic pole faces, trapped foreign matter, stiff return spring, insufficient magnetic force from electronic coil to maintain closed position
- Intermittent control signal: PLC program flicker, sensor chatter, loose wiring
- Missing surge suppression: Multiple contactors in parallel, inductive loads generating back EMF that disturbs coil electronics
Remedial Actions
Monitor A1-A2 voltage dynamically during closing, check for voltage dip; static voltage reading alone is not sufficient.
Verify continuity of the built-in 1NO latching contact; add external auxiliary contact block if reliability is poor.
Separate control wiring, use screened cable where required; fit RC snubber or freewheeling diode according to AC/DC supply type.
Disassemble and clean magnetic circuit; manually cycle mechanism to confirm smooth movement and positive return.
- Main contact overheating, pitting, welding, three-phase imbalance
TeSys Giga includes contact wear diagnostic LED: Steady ON indicates remaining contact life <15%, warning for contact block replacement. All three poles must be replaced as a set; single-pole replacement is not permitted. Reset wear counter by toggling A/B dipswitch after replacement.
Progressive failure sequence: Terminal overheating → contact arcing and erosion → contact welding (stuck closed)
Root Causes
- Misapplication / overload: Continuous operation above 500A AC-3, duty cycle exceeding 600 operations/hour, frequent inching, capacitor switching, locked-rotor starts (AC-3 duty is not suitable for capacitor loads)
- Incomplete closure (preceding chatter / undervoltage): Low contact pressure, high contact resistance and thermal runaway accelerating contact degradation
- Insufficient tightening torque on main terminals: Specified torque 35N·m. Vibration-induced loosening, poor cable lug crimping, undersized conductors
- Failed arc chamber: Broken arc chute, accumulated arc powder preventing rapid arc extinction
- Unbalanced three-phase load, motor phase loss, downstream short circuit exposing contacts to high short-circuit current
- Environmental conditions: Conductive dust, moisture causing contact surface oxidation
- Failed mechanical interlock (star-delta, dual-supply interlock): Simultaneous closure of two contactors leading to phase-to-phase short circuit and catastrophic contact damage
Evaluation & Remedial Criteria
Light surface discolouration without craters: Clean contacts, measure three-phase contact resistance for consistency, monitor temperature rise and increase inspection frequency.
Contact craters, metal spatter, charred / damaged arc chute: Replace contact module (breaking assembly) directly. Do not file / dress contacts; polishing removes arc-resistant silver alloy layer and drastically shortens service life.
Permanently welded contacts: Do not pry open forcibly. Replace complete contact block and verify upstream short-circuit protection coordination.
Retorque main terminals to 35N·m; inspect mechanical interlock operation.
Reset wear diagnostic counter: Toggle A/B dipswitch, power on for 10 seconds to complete reset.
- Standard On-site Troubleshooting Workflow
- Visual inspection: Diagnostic LED, burnt marks, discoloured terminals, damaged arc chute, accumulated dust
- Manual mechanism test (isolated): Operate moving core manually to confirm smooth travel without binding
- Isolated coil bench test to rule out upstream control circuit faults
- Continuity test: Main three-pole contacts and built-in 1NO+1NC auxiliary contacts (power off)
- Loaded monitoring: Control voltage, three-phase current, contactor housing temperature rise
- Verify operating conditions: Cycle rate, load type, ambient temperature against nameplate ratings
- Common Pitfalls (Key Differences between LC1G and Legacy LC1D)
- KUEN electronic wide coil accepts AC or DC, but is sensitive to high ripple and induced voltage on long cables
- Diagnostic LED is the primary troubleshooting indicator; inspect LED before disassembly
- Modular replaceable contact assembly, full contactor replacement not required; three poles must be replaced as a set plus wear counter reset
- Chatter faults do not involve shading rings, this is an older AC contactor design feature not present on Giga
- Mechanical interlock failure in star-delta circuits is the top cause of main contact explosion
- Spare Part Reference
Coil module: Separate replaceable electronic coil for LC1G (KUEN variant)
Contact assembly: LA9G series breaking module (3-pole set)
Accessories: Mechanical interlock, surge suppressor module, auxiliary contact extension block, remote diagnostic module LA9GRD01
Schneider TeSys Giga|KUEN Wide-Voltage Contactor Order List (KUEN = 100–250V AC/DC Electronic Wide Coil, Standard Version, Built-in 1NO+1NC)
Series note: LC1GxxxxKUEN, 3P 3NO main contacts, AC-3 @440V, diagnostic LED fitted, modular replaceable contact block; same coil variant as LC1G500KUEN above
| Order Code | AC-3 Rating @440V | Motor Power @400V |
| LC1G115KUEN | 115A | 55kW |
| LC1G150KUEN | 150A | 75kW |
| LC1G185KUEN | 185A | 90kW |
| LC1G225KUEN | 225A | 110kW |
| LC1G265KUEN | 265A | 132kW |
| LC1G330KUEN | 330A | 160kW |
| LC1G400KUEN | 400A | 200kW |
| LC1G500KUEN | 500A | 250kW |
| LC1G630KUEN | 630A | 335kW |
| LC1G800KUEN | 800A | 400kW |
4-Pole Versions (KUEN, 100–250V AC/DC, AC-1 Duty)
| Order Code | AC-1 Rating @440V | Remarks |
| LC1G8004KUEN | 1050A | 4P 4NO, for distribution / capacitor banks |
Supplement: TeSys Deca (LC1D KUE Small Wide-Voltage 100–250V AC/DC)
Suffix KUE (not KUEN). Compact TeSys D, no diagnostic LED, non-modular fixed contacts
| Order Code | AC-3 Rating @440V |
| LC1D09KUE | 9A |
| LC1D12KUE | 12A |
| LC1D18KUE | 18A |
| LC1D25KUE | 25A |
| LC1D32KUE | 32A |
| LC1D38KUE | 38A |
| LC1D40KUE | 40A |
| LC1D50KUE | 50A |
| LC1D65KUE | 65A |
| LC1D80KUE | 80A |
| LC1D95KUE | 95A |
TeSys Giga Wide-Voltage Coil Suffix Reference
KUEN: 100–250V AC/DC (your selected type)
BEEA: 24–48V AC/DC (advanced coil)
EHES207N: 48–130V AC/DC
LSEA: 200–500V AC/DC (high-range wide coil)
Common Spare Part Order Codes for Giga KUEN
| Description | Order Code |
| Mechanical interlock (115–500A) | LA9G970 |
| Mechanical interlock (630–800A) | LA9G971 |
| Remote diagnostic module | LA9GRD01 |
| Auxiliary contact extension block | LA9G11 |
| Surge suppressor module | LA9GRT |
| Contact breaking module (match current rating) | LA9Gxxxx (e.g. LA9G500 for 500A) |
Selection Notes
- KUEN is an electronic coil, no shading ring; suitable for equipment with variable control voltage, multi-country machines, mixed AC/DC PLC outputs, reduces spare part SKUs.
- Standard KUEN coil and advanced LSEA / BEEA look similar but have different PCB assemblies; coils are not interchangeable.
- Capacitor switching applications require AC-6b rating check, AC-3 rating cannot be used directly.
- Star-delta starters can use KUEN on both main and delta contactors to unify control voltage.