Series: SIRIUS 3RT, Size S10, Product Status: Active
✅ Key Specifications
Main contacts: 3-pole
Rated AC-3 current: 265 A
Motor rating at 400 V: 132 kW (50/60 Hz)
Coil voltage Uc: AC/DC 220~240 V (universal AC/DC coil)
Built-in auxiliary contacts: 2NO + 2NC, fixed, non-removable
Main circuit connection: Busbar terminals
Control / auxiliary circuit: Screw terminals
Actuation: Traditional electromagnetic coil (non-electronic energy-saving type)
Rated insulation voltage Ui: 1000 V (pollution degree 3)
Power consumption: 54 W total loss at hot state, typical 7.4 W at no-load
📌 Model Breakdown (3RT1065-6AP36)
3RT: SIRIUS contactor
1: Standard power contactor (non-safety, non-vacuum)
0: Standard main contacts
65: Size code → S10 frame, AC-3 265 A
6: Frame + main circuit connection type
A: Coil AC/DC 220–240 V
P: Auxiliary contacts 2NO+2NC
36: Main circuit busbar, auxiliary screw terminals
🧩 Compatible Accessories (common for S10)
Surge suppressor: 3RT1966-1DG00 (RC), 3RT1966-1ES00 (varistor)
Auxiliary contact block: Series 3RH1921 (for extra auxiliary contacts)
Matching thermal overload relay: Series 3RU2 (for S10)
Mechanical interlock: 3RT1966-2A
🔁 Alternative Selection
Same frame, different coil voltage: 3RT1065-6… change suffix for coil voltage
Economy equivalent: 3RT5065-6AP36 (Series 3RT5, identical mounting dimension, similar performance)
⚠️ Note: 3RT5 is economy version, mechanical & electrical service life is shorter than premium 3RT1 series. Check datasheet before retrofit.
📋 Typical Applications
Starting/stopping of 3-phase asynchronous motors up to 132 kW: fans, water pumps, air compressors, large belt conveyors, power distribution cabinets, HVAC, production line main circuits.
📎 Remarks
Not vacuum contactor (vacuum type is 3RT12xx series)
Universal AC/DC coil, can be driven directly by PLC DC220 V or mains AC220 V
Main circuit is busbar type, cannot connect cable lugs directly; copper busbar adapter required
Benchmark target: Siemens 3RT1065-6AP36|3P / AC-3 265 A / 132 kW @ 400 V / Coil AC/DC 220~240 V / Built-in 2NO+2NC / Busbar main connection
⚠️ Important note: Only equivalent in power rating. Mounting dimensions, mounting holes, accessories and auxiliary contact base are NOT interchangeable. Verify cabinet space, wiring and auxiliary contact configuration before retrofit.
✅ Schneider (TeSys Giga, current production, replacement for old LC1F265)
LC1G265KUEN
AC-3: 265 A, 132 kW @ 400 V, 3P
Coil: 100–250 V AC/DC wide voltage, covers 220–240 V perfectly
Standard: No built-in 2NO+2NC. Auxiliary contact block LA1G22 (2NO+2NC) must be added to match Siemens original configuration
Obsolete old model: LC1F265M7 (AC220 V only, discontinued, not recommended for new projects)
Full matched equivalent: LC1G265KUEN + LA1G22
✅ ABB AF series (AF with electronic wide-voltage coil, similar positioning to Siemens universal AC/DC coil)
AF265-30-22-12
AC-3: 265 A, 132 kW @ 400 V, 3P
Coil: 200–240 V AC/DC (suffix 12 for this voltage range)
Built-in auxiliary contacts: 2NO+2NC (-22), same as Siemens built-in 2NO+2NC
Main circuit: Busbar connection, same busbar terminal style as Siemens S10
Material No.: 1SFL547002R1222
Suffix explanation:
-22 = 2NO+2NC
-12 = 200–240 V AC/DC
-13 = 48–130 V AC/DC (do not select by mistake)
Comparison Table
| Item | Siemens 3RT1065-6AP36 | Schneider LC1G265KUEN+LA1G22 | ABB AF265-30-22-12 |
| AC-3 Current | 265 A | 265 A | 265 A |
| Motor Power @400 V | 132 kW | 132 kW | 132 kW |
| Coil | 220–240 V AC/DC | 100–250 V AC/DC | 200–240 V AC/DC |
| Auxiliary Contacts | Built-in 2NO+2NC | No built-in, add LA1G22 | Built-in 2NO+2NC |
| Main Connection | Busbar | Busbar | Busbar |
| Product Status | Active | Active | Active |
Selection Reminders
- ABB AF uses electronic wide-voltage coil, different principle from Siemens traditional electromagnetic coil, surge suppression solution differs;
- Schneider TeSys Giga overall size and mounting pitch differ from legacy LC1F and Siemens S10, cabinet space must be rechecked for retrofit;
- For direct replacement of old LC1F265, OEM recommendation is LC1G265KUEN;
- If you prefer built-in 2NO+2NC without extra auxiliary block, ABB AF265-30-22-12 is preferred.
Siemens SIRIUS 3RT10 Standard Power Contactors (3-pole, AC-3, benchmark for 3RT1065-6AP36)
Note: 3RT10 = premium imported SIRIUS, electromagnetic coil, motor contactor; Frames: S00 / S0 / S2 / S3 / S6 / S10 / S12; 400 V, 50/60 Hz; Only base catalog numbers listed; suffix varies by coil voltage, auxiliary contact and terminal type
Matching economy equivalent: 3RT50xx (local production, same mounting footprint, shorter service life)
3RT10 Base Catalog List (AC-3 @400 V)
| Base Model | AC-3 Current | Motor Power @400 V | Frame Size |
| 3RT1015 | 7 A | 3 kW | S00 |
| 3RT1016 | 9 A | 4 kW | S00 |
| 3RT1017 | 12 A | 5.5 kW | S00 |
| 3RT1023 | 9 A | 4 kW | S0 |
| 3RT1024 | 12 A | 5.5 kW | S0 |
| 3RT1025 | 17 A | 7.5 kW | S0 |
| 3RT1026 | 25 A | 11 kW | S0 |
| 3RT1034 | 32 A | 15 kW | S2 |
| 3RT1035 | 40 A | 18.5 kW | S2 |
| 3RT1036 | 50 A | 22 kW | S2 |
| 3RT1044 | 65 A | 30 kW | S3 |
| 3RT1045 | 75 A | 37 kW | S3 |
| 3RT1046 | 95 A | 45 kW | S3 |
| 3RT1054 | 115 A | 55 kW | S6 |
| 3RT1055 | 150 A | 75 kW | S6 |
| 3RT1056 | 185 A | 90 kW | S6 |
| 3RT1064 | 225 A | 110 kW | S10 |
| 3RT1065 | 265 A | 132 kW | S10 (this item) |
| 3RT1066 | 300 A | 160 kW | S10 |
| 3RT1075 | 370 A | 200 kW | S12 |
| 3RT1076 | 450 A | 250 kW | S12 |
Model Suffix Coding Rule (3RT10XX X P X X)
Take 3RT1065-6AP36 as example:
- 1st segment (6): Frame + main circuit terminal type (screw / busbar)
- A: Coil code
A = AC/DC 220–240 V (this item)
B = AC/DC 110–127 V
C = AC 24 V
D = AC 48 V
E = AC 110 V
F = AC 230 V
G = AC 400 V
M = DC 24 V
- P: Auxiliary contact configuration
P = 2NO+2NC (built-in, this item)
K = 1NO+1NC
N = 0NO+0NC (no built-in auxiliary contacts, add 3RH1921)
- Last two digits: Terminal type
36: Main busbar, auxiliary screw terminals (common for S10/S12 high current)
30: Screw terminals (S00~S6 small & medium frames)
Example: 3RT1065-6AP36 → Coil AC/DC 220~240 V, 2NO+2NC, busbar main connection
Other Series Branches (do not select incorrectly)
3RT12xx: Vacuum contactor (high voltage, frequent switching, not for standard motor duty)
3RT16xx: Railway dedicated contactor
3TC: DC contactor
3RT20xx: New generation SIRIUS (replaces legacy 3RT1, mixed local/import, similar dimension but accessories not interchangeable)
3RT50xx: Economy version, equivalent to 3RT10, lower cost, shorter electrical life, preferred for retrofit
3RT60xx: Low-cost domestic small contactor (S00/S0)
3RT50 Economy Equivalent List (one-to-one match with 3RT10)
3RT5015 / 3RT5016 / 3RT5017
3RT5023 / 3RT5024 / 3RT5025 / 3RT5026
3RT5034 / 3RT5035 / 3RT5036
3RT5044 / 3RT5045 / 3RT5046
3RT5054 / 3RT5055 / 3RT5056
3RT5064 / 3RT5065 / 3RT5066
3RT5075 / 3RT5076
Example: 3RT5065-6AP36 = economy equivalent of 3RT1065-6AP36
Common Accessory Prefix (SIRIUS S00~S12)
Auxiliary contact block: 3RH1921
Surge suppressor: 3RT19xx (RC / varistor / diode)
Mechanical interlock: 3RT19xx-2A
Thermal overload relay: 3RU21 (S00~S6), 3RU22 (S10/S12)
Electrical interlock, timer attachment: 3RT19 / 3RA19
Important Selection Notes
- S00~S6 are mostly screw terminals; S10, S12 (225 A and above) are mainly busbar type, cable lugs cannot be crimped directly
- 3RT10 is traditional electromagnetic coil; many new 3RT20 use electronic energy-saving coil, surge absorption scheme differs
- Versions with built-in auxiliary contacts are limited; most stock types have no built-in aux contacts, external 3RH1921 is required
- Old 3TF series is discontinued; prefer 3RT50 / 3RT20 for replacement
Surge Suppressor, Thermal Overload Relay & Mechanical Interlock by Frame for 3RT10
Base series: 3RT10 standard SIRIUS contactor (electromagnetic coil); accessories also fit equivalent 3RT50 economy series;
Thermal relay: 3RU21 (S00~S6), 3RU22 (S10/S12); Surge suppressor: RC circuit, varistor, diode; Mechanical interlock is frame-specific.
S00 Frame (3RT1015/1016/1017)
Surge suppressor: 3RT1916-1DG00 (RC) / 3RT1916-1ES00 (varistor)
Thermal overload relay: Series 3RU2116 (select current range as required)
Mechanical interlock: 3RT1916-2A
S0 Frame (3RT1023/1024/1025/1026)
Surge suppressor: 3RT1926-1DG00 (RC) / 3RT1926-1ES00 (varistor)
Thermal overload relay: Series 3RU2126
Mechanical interlock: 3RT1926-2A
S2 Frame (3RT1034/1035/1036)
Surge suppressor: 3RT1936-1DG00 (RC) / 3RT1936-1ES00 (varistor)
Thermal overload relay: Series 3RU2136
Mechanical interlock: 3RT1936-2A
S3 Frame (3RT1044/1045/1046)
Surge suppressor: 3RT1946-1DG00 (RC) / 3RT1946-1ES00 (varistor)
Thermal overload relay: Series 3RU2146
Mechanical interlock: 3RT1946-2A
S6 Frame (3RT1054/1055/1056)
Surge suppressor: 3RT1956-1DG00 (RC) / 3RT1956-1ES00 (varistor)
Thermal overload relay: Series 3RU2156
Mechanical interlock: 3RT1956-2A
S10 Frame (3RT1064/1065/1066, including 3RT1065-6AP36)
Surge suppressor: 3RT1966-1DG00 (RC snubber) / 3RT1966-1ES00 (varistor)
Thermal overload relay: Series 3RU2266 (S10 dedicated high-current thermal relay)
Mechanical interlock: 3RT1966-2A
S12 Frame (3RT1075/1076)
Surge suppressor: 3RT1976-1DG00 (RC) / 3RT1976-1ES00 (varistor)
Thermal overload relay: Series 3RU2276
Mechanical interlock: 3RT1976-2A
Supplementary Accessory Notes
- External auxiliary contact block: 3RH1921 for all frames
3RH1921-1CA01: 1NO+1NC
3RH1921-1FA22: 2NO+2NC
- Diode suppressor (DC coil only): suffix 1BB00, example S10: 3RT1966-1BB00
- Thermal relay selection:
The digits after 3RU21 / 3RU22 indicate base unit; current range is determined by the last two digits, e.g. 3RU2126-1DB0 (2.8~4 A)
- Distinction reminder:
RC (1DG00): Preferred for AC coil, suppress overvoltage, minor time delay
Varistor (1ES00): Suitable for AC/DC, fast response, shorter service life
Diode (1BB00): DC coil only, not for AC
Contactor,circuit breaker,sensor,Encoder,PLC,Converter



















NH42-63-318x560.png)