TENSE DGK-04F Voltage Monitoring Relay - Contactor,circuit breaker,sensor,Encoder,PLC,Converter

Wechat: +86-13184948252  WhatsaApp: 0086-13811255435  E-mail:  kent@bestcontactor.com

About    Contact    |    

TENSE DGK-04F Voltage Monitoring Relay - Contactor,circuit breaker,sensor,Encoder,PLC,Converter

PLC/

TENSE DGK-04F Voltage Monitoring Relay

Brand: TENSE (Turkey) Product: 3-Phase Digital Adjustable Overvoltage / Undervoltage & Phase Sequence Protection Relay (Voltage Monitoring Relay) Model Code Explanation DGK: Series of 3-phase digital voltage control relays 04: Function code → Overvoltage + Undervoltage + Phase Sequence Monitoring F: Digital display version (enhanced model) Sibling model: DGK-04PF with extra phase loss protection Protection ...

  • Product Details

Brand: TENSE (Turkey)

Product: 3-Phase Digital Adjustable Overvoltage / Undervoltage & Phase Sequence Protection Relay (Voltage Monitoring Relay)

  1. Model Code Explanation

DGK: Series of 3-phase digital voltage control relays

04: Function code → Overvoltage + Undervoltage + Phase Sequence Monitoring

F: Digital display version (enhanced model)

Sibling model: DGK-04PF with extra phase loss protection

  1. Protection Functions
  2. 3-phase overvoltage protection (U>)
  3. 3-phase undervoltage protection (U<)
  4. Phase sequence / reverse phase protection (phase sequence detection cannot be turned off on DGK-04F)
  5. Real-time digital display of 3-phase line voltages + fault LED indication
  6. Technical Specifications

Power supply & measurement: 3-phase AC380V, no neutral required, L1/L2/L3 only

Frequency: 50/60Hz auto-adaptive

Undervoltage setting range: 230~360V AC

Overvoltage setting range: 400~460V AC

Fault delay time: 0.1~10s adjustable

Output contact: 1NO+1NC (SPDT), 5A / 250V AC resistive load

Mounting: Standard DIN rail mounting

Operating temperature: -10℃ ~ +55℃

Measuring accuracy: ±1V

  1. Terminal Definition

L1, L2, L3: 3-phase voltage input

1, 2, 3: Relay changeover contacts

Terminal 1: NC (Normally Closed)

Terminal 2: COM (Common)

Terminal 3: NO (Normally Open)

Standard Wiring (Motor / Air Compressor / Water Pump)

Contactor coil circuit: Wire in series with 2-3 (NO)

Alarm lamp / Buzzer: Connect to 1-2 (NC)

Safety note: L1/L2/L3 must be from the same 3-phase power source; do not mix phases from different circuits.

  1. Wiring & Commissioning Manual

Panel Buttons & Indicators

U: Overvoltage setting key

U< : Undervoltage setting key

t : Time delay setting key

Digital display: Cyclically shows L1-L2 / L2-L3 / L3-L1 line voltages

OUT: Relay output indicator (ON under normal condition)

U: Overvoltage fault LED

U< : Undervoltage fault LED

PHASE: Phase sequence error LED

Power-on logic: The unit shows parameter settings for 2 seconds first, then automatically cycles through 3-phase voltage readings.

Pre-power Check (Mandatory)

  1. Perform all wiring with power disconnected; confirm no short circuit on L1/L2/L3.
  2. Contact load limit: Max 5A/250VAC; only interlock the control circuit, do not switch main power of large contactors directly.
  3. Keep away from inverters and large contactors to avoid strong electromagnetic interference.

Step-by-step Commissioning

Step 1: Power On

Switch on 3-phase supply, digital display lights up:

OUT ON: Voltage & phase sequence normal, relay energized, 2-3 closed.

PHASE ON: Phase sequence reversed → Power off and swap any two incoming phases (L1↔L2 or L2↔L3).

U/ U< ON: Voltage exceeds threshold, protection activated.

Step 2: Set Undervoltage U< (Recommended: 340V for 380V systems)

  1. Short press the U< key to enter undervoltage setup.
  2. Press U< to increase value; press t to decrease value.
  3. Wait 4 seconds without operation to auto-save and return to voltage monitoring screen.

Setting range: 230~360V

Step 3: Set Overvoltage U(Recommended: 420V for 380V systems)

  1. Short press the Ukey to enter overvoltage setup.
  2. Press Uto increase value; press t to decrease value.
  3. Auto-save after 4 seconds idle.

Setting range: 400~460V

Step 4: Set Fault Time Delay t (Recommended 1~3s to avoid false tripping from momentary voltage dips)

  1. Short press the t key to enter delay setup.
  2. U= increase time; U< = reduce time.
  3. Settings take effect after auto-save.

Range: 0.1~10s; same delay applies for fault trip AND automatic reset after voltage recovers.

Step 5: Phase Sequence Function Note

DGK-04F: Phase sequence detection cannot be disabled. Reverse phase will trigger protection, PHASE LED lights up, OUT turns off, and contact 2-3 opens.

If phase sequence monitoring is not required (fans without rotation direction requirement), you need to select another model. Only DGK-04PF adds phase loss protection.

Step 6: Functional Test

  1. Normal status: OUT stays ON, 2-3 closed, contactor can energize.
  2. Simulate overvoltage: Raise supply voltage or lower the Uthreshold; ULED lights up, OUT cuts off, 2-3 opens.
  3. Simulate undervoltage: Lower supply voltage or raise the U< threshold; U< LED lights up, relay de-energizes.
  4. Swap two phases: PHASE fault triggers, relay drops out.

Hysteresis: Relay only restores after voltage returns within the set window (+5V tolerance) plus the programmed time delay.

Recommended Parameters (AC380V 3-phase Equipment)

Undervoltage U<: 340V

Overvoltage U>: 420V

Time delay t: 2s

Troubleshooting List

  1. PHASE LED always ON after power-up: Phase sequence reversed; swap any two incoming phases.
  2. OUT OFF with no fault indication: One phase is missing; measure line voltages on L1/L2/L3.
  3. Frequent false tripping: Increase time delay t; check for grid voltage flicker or loose terminal connections.
  4. Flashing reading on one phase: Abnormal voltage on that phase.
  5. Voltage reading normal but relay will not energize: Check continuity of terminals 2-3 and the contactor control circuit.

Strict Prohibitions

❌ Never connect L1/L2/L3 to the output terminals of an inverter (distorted sine wave will cause false fault alarms).

❌ Do not feed single-phase 220V power into L1/L2/L3.

❌ Do not use the relay contacts to drive high-power loads directly; only use them for control circuit interlock.

Time Delay (t) Setting for TENSE DGK-04F

Delay range: 0.1~10 seconds. This single setting covers both fault confirmation delay AND voltage recovery reset delay. The relay will only re-energize after the voltage returns to normal and the set time elapses.

Operation Steps

  1. While the display is cycling through line voltages, short press the t key to enter delay setup; the digital tube shows the current time value.
  2. Press U= increase time value
  3. Press U< = decrease time value
  4. Stop pressing any key; wait approx. 4 seconds for auto-save, then the unit returns to voltage monitoring mode automatically.

✅ Factory recommended setting: 1~2s to filter short grid transients and prevent false tripping.

Air compressors & water pumps: 2s preferred

Fast cut-off protection requirement: set to 0.5s

Key Logic

When overvoltage / undervoltage / reverse phase occurs: The relay starts timing; contacts only open after the delay expires.

When the fault clears and voltage recovers (with +5V hysteresis): The relay waits the same t seconds before closing contacts again.

Phase sequence faults also follow this same time delay setting.

Common Issues

New setting not saved: Do not press any confirm key; just wait for automatic return. Avoid long key presses.

Unwanted frequent tripping: Increase the t value.

Slow recovery after fault: Reduce the t value appropriately.

Full Model List of TENSE (Turkey) DGK Digital Voltage Monitoring Relays

DGK series: Digital readout, adjustable over/undervoltage, DIN rail mounting, no neutral required (L1/L2/L3 line voltage detection).

Suffix definition: F = digital display; P = phase loss protection added

ModelPhaseCore FunctionsRemarks
DGK-01Single-phaseAdjustable overvoltage + undervoltage, digital displayAC220V single-phase monitoring
DGK-033-phaseAdjustable over/undervoltage, no phase sequence check, digital displayFor loads with no rotation direction requirement
DGK-043-phaseAdjustable over/undervoltage, no phase sequence, analog knob (no display)Analog version without digital readout
DGK-04F3-phaseOvervoltage + Undervoltage + Phase Sequence, digital displayYour current model; no phase loss protection, phase sequence check cannot be disabled
DGK-04PF3-phaseOvervoltage + Undervoltage + Phase Sequence + Phase Loss, digital displayUpgraded model of DGK-04F, widely used on air compressors & chillers

Analog Knob Series (GK Series, No Digital Display)

ModelFunction
GK-033-phase over/undervoltage adjustable, no phase sequence
GK-043-phase over/undervoltage adjustable, no phase sequence
GK-04F3-phase over/undervoltage + phase sequence

Phase Sequence / Phase Loss / Unbalance Protection Series (FK / FKV Series, without continuous voltage adjustment window)

These models focus on phase loss, 3-phase unbalance and phase sequence; some support PTC motor temperature protection, not the DGK over/undervoltage main series.

FK-04: Phase loss + phase sequence, fixed 30% unbalance threshold

FK-05 / FK-05F: Phase loss + phase sequence, unbalance adjustable 5~25% (F = digital display)

FK-14 / FK-14P: Phase sequence + phase loss; P model with PTC motor thermal protection

FKM-05 / FKM-05F: Adjustable unbalance, phase sequence, phase loss

FKT-06 / FKT-06PF: 3-phase unbalance + phase loss + phase sequence; PF with PTC input

FKV-03 / FKV-03F / FKV-03DF / FKV-03HF: Phase loss, phase sequence, unbalance; some versions require neutral N

FKV-14 / FKV-14P: Economy phase sequence & phase loss relay; P with PTC protection

Suffix Quick Reference

F: Digital display type

P: Phase loss protection function

T: Built-in PTC motor temperature protection

DF/HF: Adjustable unbalance ratio

N: Requires neutral wire (3P+N)

Quick Selection Guide (Most Popular Engineering Models)

  1. Only over/undervoltage monitoring, no rotation check: DGK-03
  2. Over/undervoltage + anti-reverse phase (motor rotation control): DGK-04F
  3. Over/undervoltage + anti-reverse phase + phase loss protection: DGK-04PF (first choice for air compressors & water chillers)
  4. Only phase loss & unbalance monitoring without voltage threshold adjustment: FK-05F / FKV-14

Common Specifications for All DGK 3-phase Models

Output: 1NO+1NC SPDT contact, 5A/250VAC

Time delay: 0.1~10s adjustable (shared trip & reset delay)

Voltage range: Undervoltage 230~360V; Overvoltage 400~460V (for 380V line voltage systems)

Power & measurement input: L1/L2/L3 only, no neutral wire needed

Prev:

Leave a Reply

Leave a message