Differences between EOCRPFZ-H2DZ7W and EOCRPFZ-WRDUH

Samwha EOCR-PFZ Motor Protection Relay

Comparação de modelos: EOCRPFZ-WRDUH VS EOCRPFZ-H2DZ7W

Coding Rule for PFZ Series

`EOCRPFZ [Classificação CT][Configuração de contato][Mostrar][Poder de controle][Função][Comunicação][Curva de viagem][Terminal/Housing Type]`

  1. Model Suffix Breakdown

1) EOCRPFZ-WRDUH

C: Built-in CT range 0.5~100A (W-type CT)

R: Relay contact layout: Trip contact OL (1NÃO+1NC) + Alarm contact AL (1NÃO)

D: Visor digital

Você: Control supply AC/DC 85~264V universal wide voltage

H: Integrated zero-sequence ZCT, earth fault protection supported

👉 No suffix Z = standard version; without special trip curve code, no Curve 7

2) EOCRPFZ-H2DZ7W

H: Built-in CT range 0.5~60A (H-type CT) ✅【Key Difference 1】

2: Configuração de contato: Two independent changeover contact sets ✅【Key Difference 2】

D: Visor digital

Z: Built-in Modbus-RTU RS485 communication port ✅【Key Difference 3】

7: Special thermal protection curve (customized I²t overload & motor starting characteristic parameters, Curve No.7) ✅【Key Difference 4】

C: Habitação / feed-through terminal type

⚠️ Important Note:

EOCRPFZ-WRDUH has no Z code → no RS485 communication;

EOCRPFZ-H2DZ7W with Z suffix = factory-fitted Modbus communication.

  1. Main Comparison Table
Item de comparaçãoEOCRPFZ-WRDUHEOCRPFZ-H2DZ7W
Built-in CT Measuring Range0.5~100A0.5~60A
Fonte de alimentação de controleAC/DC 85~264V wide universal rangeTypically AC100~240V (confirm upon order, wide voltage not guaranteed)
Output Relay ContactsOL: 1NÃO+1NC; AL: 1NÃOTwo sets of changeover contacts (2×NO/NC), more contact terminals
Total 3 contact points
Modbus RS485 Communication❌ Not supported✅ Standard onboard communication; allows PLC remote reading of current & códigos de falha
Overload Protection CurveStandard universal curveSpecial No.7 trip curve (optimized for heavy-start loads: trituradores, air compressors etc.)
Earth Fault ProtectionBuilt-in ZCT, earth fault availableBuilt-in ZCT, earth fault available (same function)
4~20mA Analog OutputDual-channel 4–20mA outputDual-channel 4–20mA output
Direct Interchangeability❌ Not plug-and-play❌ Not plug-and-play
Differences in measuring range, contact definition, communication and terminal layout
  1. Seleção & On-site Replacement Guidelines
  2. Measuring Range Priority

EOCRPFZ-WRDUH max range 100A; EOCRPFZ-H2DZ7W max 60A.

Never use H2DZ7W if motor rated current exceeds 60A.

  1. Communication Requirement as Key Criterion

If remote current monitoring, fault signal acquisition or remote parameter setting via PLC is required → choose H2DZ7W (with Z communication).

Only local protection without upper system communication → EOCRPFZ-WRDUH is acceptable.

  1. Rewiring Required for Contact Circuits

Terminal assignments and contact numbers differ between the two models. Direct replacement will cause control circuit malfunction. Drawings and wiring must be rechecked and modified.

  1. Match Trip Curve with Load Type

No.7 curve version (sufixo 7) is preferred for crushers and heavy-duty long-start motors; standard curve WRDUH is sufficient for ordinary fans and water pumps.

  1. Brief Summary
  2. Measuring range: WRDUH = 0.5–100A; H2DZ7W = 0.5–60A
  3. Comunicação: H2DZ7W supports Modbus; WRDUH has no communication
  4. Contatos: H2DZ7W equipped with two changeover contact sets; WRDUH adopts standard 1OL+1AL contacts
  5. Protection curve: H2DZ7W uses special No.7 curve for heavy startup loads
  6. Fonte de energia: WRDUH supports wide AC/DC 85~264V input for better compatibility