Model A9L40600 SchneiderModel Analysis and Technical Parameters A9L40600 is the complete order number of a low-voltage surge protection product (Surge Arrester) under Schneider Electric‘s Acti9 Series. It belongs to the iPRD40 modular surge arrester series and is mainly used for Type 2 surge protection in power distribution systems. Model Segment Analysis Code Segment ...

  • Detalhes do produto

Model A9L40600 SchneiderModel Analysis and Technical Parameters

A9L40600 is the complete order number of a low-voltage surge protection product (Surge Arrester) under Schneider Electric‘s Acti9 Series. It belongs to the iPRD40 modular surge arrester series and is mainly used for Type 2 surge protection in power distribution systems.

  1. Model Segment Analysis
Code SegmentDescriptionCorresponding Product Attribute
A9Schneider Acti9 Series IdentifierA standardized low-voltage component series for terminal power distribution, including circuit breakers, surge arresters, etc..
L40Product Type Sub-codeRepresents the iPRD40 series modular surge arrester. “eu” generally indicates surge protection products, e “40” corresponds to the 40kA maximum discharge current rating.
600Structural Feature and Configuration CodeCorresponding to 3P+N (trifásico + neutral) pole configuration, 350V rated voltage, and equipped with a pluggable trip module
  1. Summary of Core Product Attributes
ItemSpecification Parameter
Brand and SeriesSchneider Acti9 iPRD40 Series
Product TypeType 2 modular surge arrester (with pluggable trip unit)
Pole Configuration3P+N (trifásico + neutral)
Tensão nominal (Uc)350V e (suitable for domestic 400V three-phase systems)
Maximum Discharge Current (Imax)40o (8/20forma de onda μs)
Classe de ProteçãoType 2 (secondary surge protection for power distribution systems)
Technical PrincipleCombined technology of MOV (Varistor de óxido metálico) + GDT (Gas Discharge Tube)
Applicable Earthing SystemTN-S, TT systems (not applicable to TN-C, IT systems)
  1. Detailed Technical Parameter Table
Categoria de parâmetroSpecific ValueRemarks
Electrical Parameters
Tensão operacional nominal350V e50/60Hz
Maximum Discharge Current40o (8/20μs)Core indicator of surge protection
Nominal Discharge Current20o (8/20μs)
Nível de proteção de tensão (Acima)≤ 1.5kVMeasured at In=10kA
Tempo de resposta≤ 25nsMOV+GDT combined technology ensures fast response
Mechanical and Installation Parameters
Module Width4 módulos (72milímetros)Suitable for 35mm DIN standard rail
Dimensões85milímetros (H) × 72mm (C) × 69mm (D)
TerminalSuitable for 2.5~35mm² copper conductorsRecommended torque: 8~10N·m
Classe de ProteçãoIP20Suitable for installation inside power distribution cabinets
Environmental and Service Life Parameters
Temperatura operacional-25°C ~ +60°C
Temperatura de armazenamento-40°C ~ +85°C
Mechanical Service Life 10,000 vezes (plug-in operation)
Electrical Service LifeComplies with IEC 61643-11 padrãoThe pluggable module can be replaced when surge protection components age
Certification and Standards
Compliant StandardsCEI 61643-11, GB 18802.1Certified with CE and CCC
  1. Core Functions and Working Principle
  2. Surge Suppression Mechanism: Adopts MOV+GDT hybrid technology. MOV is responsible for fast response (≤25ns) to suppress most surges, while GDT provides higher surge withstand capacity and lower leakage current.
  3. Fault Indication Function: The pluggable module is equipped with a visual status indicator (green = normal, red = fault) for quick identification of protection status.
  4. Proteção Térmica de Viagem: Built-in thermal trip device automatically trips when surge energy is excessive or components age, preventing overheating damage to the arrester.
  5. Replaceable Design: Only the pluggable trip module needs to be replaced after a fault, eliminating the need for overall replacement and reducing maintenance costs.
  6. Cenários típicos de aplicação
Application FieldSpecific Application ScenarioProtection Target
Edifícios ComerciaisMain/distribution power cabinets in office buildings, shopping malls, hotéisProtect critical loads such as air conditioners, elevadores, and lighting systems
Industrial PlantsProduction line control circuits, PLC systems, front-end of frequency convertersPrevent damage to precision electronic equipment caused by lightning strikes or grid fluctuations
Data CentersUPS input/output terminals, front-end of server cabinet PDUsEnsure continuous and stable operation of IT equipment and avoid data loss
InfrastructureCritical power distribution circuits in hospitals and transportation hubsProtect life-safety related equipment and control systems
Photovoltaic SystemsAC side output terminals of invertersSuppress surges generated by photovoltaic systems and grid feedback surges
  1. Installation and Operation Precautions
  2. Local de instalação:

As Type 2 proteção, it should be installed in the main or distribution power cabinet, after the main circuit breaker.

Recommended to be installed close to the protected equipment, with the line length not exceeding 10 metros.

  1. Wiring Requirements:

Phase lines (L1/L2/L3) and neutral line (N) must be wired correctly according to the markings.

The protective earthing (Educação Física) wire should be as short and thick as possible. It is recommended to use ≥16mm² copper conductors with a length not exceeding 50cm.

All terminals must be tightened to the recommended torque (8~10N·m) to prevent overheating due to poor contact.

  1. Matching Requirements:

A 16A~32A miniature circuit breaker or fuse must be installed upstream as overcurrent protection to prevent short circuits caused by surge arrester faults.

Not applicable to IT and TN-C earthing systems, only suitable for TN-S and TT systems.

  1. Pontos de Manutenção:

Regularly check the status indicator (green = normal, red = fault).

Replace the pluggable trip module in a timely manner after a fault; do not perform plug-in operations with power on.

It is recommended to conduct a surge protection performance test every 2 years.

  1. Reference of Related Models in the Same Series
ModeloNúmero do póloMaximum Discharge CurrentTensão nominalApplication Scenario
A9L402001P+N40o350VType 2 surge protection for single-phase power distribution systems
A9L404002P+N40o350VTwo-phase power distribution systems (por exemplo, lighting systems)
A9L406003P+N40o350VThree-phase power distribution systems (mainstream model)
A9L156003P+N15o350VPlaces with low surge risk

 