Descrição do modelo: ACS355 machinery drive frequency conversor; 03E = 3-phase input, IP20 enclosure; 07A3 = rated output 7.3 UM; 4 = 380–480 V voltage class
Número da peça: 3AUA0000058188
✅ Core Electrical Specifications
Potência nominal: 3.0 kW (sobrecarga leve / standard duty)
Rated Output Current I₂ₙ: 7.3 UM
Entrada: 3-phase 380–480 V ±10%, 48–63Hz
Saída: 0 ~ Uₙ, 0–599 Hz
Proteção de gabinete: IP20 (without +B063 or other options)
Tamanho do quadro: R0
Resfriamento: Resfriamento de ar
Motor compatível: 3 kW 3-phase asynchronous motor
📦 Dimensions & Peso
Unidade: W70 mm × H239 mm × D161 mm
Peso líquido: 1.8 kg
Packaged Size: 350×220×130 mm, Peso bruto 2.3 kg
🧩 On-board I/O (Padrão)
5 Entradas Digitais (DE)
1 Saída de relé (RO)
2 Entradas Analógicas (IA, 0–10V / 4–20 mA)
1 Saída Analógica (AO, 4–20 mA)
Modbus RTU integrado (Terminal X1)
Optional plug-in communication adapters: Profibus DP, CANopen, DeviceNet, EtherCAT, etc..
📌 Aplicações Típicas
Máquinas gerais: transportadores, fãs, bombas, misturadores, small processing machines. Supports standard V/F control and vector control, velocidades predefinidas, ramps, multi-set parameter groups.
⚠️ Seleção & Notas de substituição
- For IP66 version: add suffix +B063. Dimensions and weight differ completely, part number changes.
- Upgrade alternative within ABB portfolio: ACS380. Older ACS350 of the same power can be cross-referenced by current rating.
- Fusível / disjuntor: sized per 7.3 A converter standard circuit. Output du/dt reactor is optional.
📎 Common Spare Parts & Acessórios
Control Panels: ACS-CP-A / ACS-CP-D
Input filter, output du/dt filter, resistor de frenagem (braking chopper built-in)
Adaptadores de comunicação, Módulos de expansão de E/S
ABB ACS355 (ACS355-03E-07A3-4)|Factory Default Parameters for ABB Standard Macro (9902=1)
Observação: Parameters in Group 99 (dados da placa do motor) have no fixed default values. Enter data per 3 kW motor nameplate after power-up.
| Parâmetro Não. | Nome do parâmetro | Valor padrão | Observações |
| 9902 | Application Macro Selection | 1 ABB Standard Macro | DI1 start, DI2 direction, AI1 reference; mais amplamente utilizado |
| 9904 | Motor Control Mode | 3 Escalar (V/F) | Opcional: 1=Vector Speed, 2=Vector Torque |
| 9905 | Tensão nominal do motor | - | Follow nameplate; 380 V for standard 3 motor kW |
| 9906 | Corrente nominal do motor | - | Typical value for matched motor ≈6.2 A |
| 9907 | Motor Rated Frequency | - | 50 Hz for general asynchronous motors |
| 9908 | Velocidade nominal do motor | - | 1440 rpm (4-pólo) |
| 9909 | Potência nominal do motor | - | 3.0 kW |
| 1001 | Ext1 Start/Stop Command | 2 DI1 | DI1 closed = Run |
| 1002 | Ext Direction Command | 3 ED2 | DI2=0 Forward, DI2=1 Reverse |
| 1103 | Ext Reference 1 Seleção | 1 AI1 | AI1 0–10 V / 4–20 mA |
| 1105 | Ext Reference 1 Máximo | 50.0 Hz | Matches full-scale AI signal |
| 1201 | Constant Speed Selection | 0 Not Selected | Multi-speed via DI combination |
| 1301 | AI1 Minimum | 0.0 V | 0 V corresponds to 0 Hz |
| 1302 | AI1 Maximum | 10.0 V | 10 V corresponds to 50 Hz |
| 1304 | AI2 Minimum | 0.0 V | AI2 disabled by default |
| 1401 | Relay Output RO1 Source | 0 Ready | Output when drive is ready |
| 1501 | AO1 Signal Source | 102 Frequência de saída | AO: 4–20 mA mapped to 0–50 Hz |
| 1504 | AO1 Minimum Output | 4 mA | |
| 1505 | AO1 Maximum Output | 20 mA | |
| 2007 | Minimum Frequency | 0.0 Hz | |
| 2008 | Maximum Frequency | 50.0 Hz | |
| 2202 | Tempo de aceleração 1 | 5.0 é | |
| 2203 | Tempo de desaceleração 1 | 5.0 é | |
| 2102 | Stop Mode | 1 Coast Stop | 2=Ramp Stop |
| 2601 | U/F Ratio | 1 Linear | Squared for fan/pump duty |
| 3017 | Overcurrent Trip Limit | 4×I₂n | |
| 3025 | STO Function | 0 Alarm Only | Definir como 1 triggers fault 0044 |
| 5302 | EFB Station Address | 1 | Modbus RTU Slave Address |
| 5303 | Taxa de transmissão | 9600 | |
| 5304 | Paridade | 0 No Parity, 1 Stop Bit |
ACS355 Fault Code List (English with Troubleshooting Guidance)
| Código de falha | Nome da falha | Descrição | Solução de problemas comuns |
| 1 | SOBRECORRENTE | Output current exceeds trip threshold | Curto-circuito do motor, danos no cabo, locked load, too short ramp time, incorrect motor data |
| 2 | DC OVERVOLT | DC bus voltage too high | Desaceleração rápida, regenerative load, high supply voltage, faltando resistor de frenagem |
| 3 | DEV OVERTEMP | IGBT module overtemperature | Blocked airflow, ventilador com falha, alta temperatura ambiente, sobrecarga, má ventilação do gabinete |
| 4 | SHORT CIRC | Motor-side short circuit | Motor winding short, phase-to-phase short on power cable, shorted output terminals |
| 6 | DC UNDERVOLT | DC bus voltage insufficient | Fase de entrada ausente, open fuse/contact, voltage dip, undersized supply |
| 9 | MOT OVERTEMP | Estimated motor temperature exceeded | Sobrecarga do motor, resfriamento deficiente, incorrect motor thermal protection settings |
| 16 | EARTH FAULT | Earth leakage on motor/power cable | Damaged cable insulation, motor insulation failure, entrada de umidade |
| 22 | SUPPLY PHASE | Perda de fase de entrada / 3-desequilíbrio de fase | Blown input fuse, poor contactor contacts, unbalanced 3-phase supply |
| 44 | SAFE TORQUE OFF (STO) | STO safety circuit activated | STO terminals not jumpered, safety loop open, parameter 3025=1 triggers fault |
| 28 | COMM ERROR | Built-in EFB bus communication break | Modbus wiring, resistor de terminação, address conflict, master offline |
| 35 | AI1 LOSS | AI1 signal below fault threshold | Transmitter wire break, faulty sensor, threshold setting in 3021 |
| 36 | AI2 LOSS | AI2 signal loss | Broken AI2 wiring, transmissor defeituoso |
| 41 | ID RUN FAIL | Motor identification run failed | Wrong motor wiring, classificação de potência incompatível, rotor bloqueado |
| 51 | USER PARAM FAULT | Parameter set corrupted | Restore factory defaults and re-enter motor parameters |
| 71 | FAN FAULT | Cooling fan failure | Fan jammed, fan supply fault |
✅ Reset Methods: Panel RESET, DI reset, communication reset, ciclo de energia. Fault history stored in Group 04 parâmetros.
Quick Operation
Redefinição de fábrica: Parâmetro 9606, enter RESET. The drive restarts and loads ABB Standard Macro defaults.
Installation Notes for ABB ACS355-03E-07A3-4 (Frame R0, IP20)
This unit is for cabinet installation only. Classificação IP20, not suitable for direct outdoor exposure.
- Montagem Mecânica & Dissipação de Calor
- Orientação de montagem: Vertical upright installation is mandatory. Do not invert. Side mounting is permitted for R0 frame but vertical is preferred. Cooling air flows bottom-in, top-out; inverted mounting causes overheating fault 0003.
- Minimum Clearances
Top ≥75 mm, Bottom ≥75 mm; no mandatory side clearance, reserve space for maintenance.
Stacked multiple drives: hot exhaust from lower unit must not blow directly onto upper unit. Use baffles, staggered layout or independent air ducts.
- Mounting Options: Screw fixing or 35 trilho DIN padrão mm. Mounting base must be rigid and flame-retardant. Prevent conductive dust from entering the unit during drilling (risk of short circuit).
- Condições ambientais
Temperatura ambiente: -10 ~ +50 °C; desclassificar acima 40 °C. Sem condensação, sem glacê.
Altitude: Full rating ≤1000 m; derate with increasing altitude above 1000 eu.
Prohibited environment: poeira condutora, gás corrosivo, strong magnetic fields (near contactors / large single-core cables), heavy vibration or shock.
- Segurança & Power-off Procedures (Crítico)
After disconnection, espere 5 minutes for DC bus capacitors to fully discharge before opening covers, wiring or measuring. Do not touch power terminals or internal PCB when powered.
For permanent magnet motors: motor may generate back EMF when rotating even with supply disconnected. Mechanically lock the shaft before working on motor cables.
Before power-up: Disconnect U2/V2/W2 at the converter, test motor insulation to earth with 1000 V megô. Do not energise if insulation is poor (≥100 MΩ @25°C for ABB motors).
Strictly forbidden: Connect mains supply to U2/V2/W2 output terminals, this will destroy the unit.
- Seleção de cabos, Routing & EMC
- Cable Recommendations
Cabo do motor: Symmetric shielded VFD cable preferred, reduces bearing currents and EMI. Unshielded standard cables often interfere with sensors and instruments.
Sinais analógicos (IA/Mundo): Double-shielded twisted pair. DI/DO relay signals: shielded twisted pair. Separate power cables and control cables in different trunking, minimum gap ≥20 cm. Cross only at 90° where unavoidable.
Do not mix 24 V low-voltage and 220 V high-voltage circuits inside one cable.
- Shield Grounding Rules
360° shield termination with earthing clamp; avoid pigtail earthing (poor high-frequency EMC performance). Shield of motor cable grounded at both converter and motor ends.
PE conductor must be short, thick and connected reliably to cabinet earth bar.
- ISTO / Ungrounded Delta System: Remove internal EMC filter earth screw, otherwise earth fault 0016 may occur. Keep screw fitted for standard TN-S systems.
- Output-side Restrictions: Do not connect capacitors or surge suppressors to U2/V2/W2. For long motor cables (>50 eu), fit output du/dt reactor to protect motor insulation.
- Torque Terminal & STO Safety Circuit
Torque de aperto do terminal de controle: 0.4 N·m. Power terminals follow datasheet torque specification.
STO (Torque seguro desativado): Factory fitted with jumper. If STO function is unused, STO terminals must be permanently jumpered. Open STO triggers fault 0044. For safety applications, wire to safety relay contacts.
Resistor de frenagem (BRK+, BRK-): Utilize cabo blindado, mount close to drive to minimise lead inductance.
- Input Protection, Aterramento & Auxiliary Devices
Fit circuit breaker or fuses on input side, sized for 7.3 Uma classificação. Input AC reactor is recommended to reduce harmonic distortion.
Aterramento: PE conductors must be home-run separately to earth bar, do not daisy-chain. Never use neutral N as protective earth PE.
Cabinet ventilation: Install cabinet fans to keep internal temperature below 40 °C. Clean filters regularly to prevent blocked cooling paths.
- Pre-power-up Checklist
- Terminais de energia: U1/V1/W1 supply, U2/V2/W2 motor, BRK+/braking resistor – verify connections.
- Circuitos de controle: DI/AI/AO, STO jumper, shield grounding.
- Insulation test passed, no short circuit or earth leakage.
- Air path unobstructed.
- Motor nameplate data ready; perform motor identification after first power-up.
- Installation-related Fault Quick Reference
0003 Overtemp: Blocked airflow, insufficient top/bottom clearance, montagem invertida, high cabinet temperature
0016 Falha à Terra: Incorrect shield grounding, EMC screw not removed for IT system, damaged/wet motor cable
0044 STO Fault: STO terminals not jumpered, safety loop open
Fluctuating AI signals: Mixed power/control wiring, poor shield grounding, non-twisted analog cable
ABB ACS355 Model & Part Number List|03E 3-phase 380–480 V, IP20, Filtro EMC integrado, Versão padrão
Descrição do modelo:
03 = 3-phase input; E = EMC filter enabled (50 Hz); trailing 4 = 380~480 V; +B063 = IP66 high protection variant (pedido separado)
Part Number format: 3AUA00000XXXXX (ABB part number, used for purchasing, quotation and customs declaration)
Frame sizes: R0/R1/R3/R4; built-in braking chopper and STO.
| Modelo | Rated Power kW | Output Current I₂N(UM) | Quadro | ABB Part Number (3AUA) |
| ACS355-03E-01A2-4 | 0.37 | 1.2 | R0 | 3AUA0000058186 |
| ACS355-03E-01A9-4 | 0.55 | 1.9 | R0 | 3AUA0000058243 |
| ACS355-03E-02A4-4 | 0.75 | 2.4 | R0 | 3AUA0000058187 |
| ACS355-03E-03A3-4 | 1.1 | 3.3 | R1 | 3AUA0000058184 |
| ACS355-03E-04A1-4 | 1.5 | 4.1 | R1 | 3AUA0000058185 |
| ACS355-03E-05A6-4 | 2.2 | 5.6 | R1 | 3AUA0000058189 |
| ACS355-03E-07A3-4 | 3 | 7.3 | R0 | 3AUA0000058188 |
| ACS355-03E-08A8-4 | 4 | 8.8 | R1 | 3AUA0000058190 |
| ACS355-03E-12A5-4 | 5.5 | 12.5 | R3 | 3AUA0000058191 |
| ACS355-03E-15A6-4 | 7.5 | 15.6 | R3 | 3AUA0000058192 |
| ACS355-03E-23A1-4 | 11 | 23.1 | R3 | 3AUA0000058193 |
| ACS355-03E-31A0-4 | 15 | 31 | R4 | 3AUA0000058195 |
| ACS355-03E-38A0-4 | 18.5 | 38 | R4 | 3AUA0000058194 |
| ACS355-03E-44A0-4 | 22 | 44 | R4 | 3AUA0000058196 |
Supplementary Range: 01E Single-phase 200–240 V, IP20, EMC integrado
| Modelo | Power kW | Current A | Quadro | Número da peça |
| ACS355-01E-02A4-2 | 0.37 | 2.4 | R0 | 3AUA0000058174 |
| ACS355-01E-04A7-2 | 0.75 | 4.7 | R1 | 3AUA0000058175 |
| ACS355-01E-06A7-2 | 1.1 | 6.7 | R1 | 3AUA0000058176 |
| ACS355-01E-07A5-2 | 1.5 | 7.5 | R2 | 3AUA0000058177 |
| ACS355-01E-09A8-2 | 2.2 | 9.8 | R2 | 3AUA0000058178 |
Acessórios Comuns & Part Numbers for ACS355
| Nome do acessório | Modelo | Número da peça |
| Basic Control Panel | ACS-CP-A | 3AUA0000040901 |
| Painel de controle assistente (chinês) | ACS-CP-D | 3AUA0000040902 |
| Profibus DP Adapter | FPBA-01 | 3AUA0000040888 |
| CANopen Adapter | FCAN-01 | 3AUA0000040889 |
| DeviceNet Adapter | FDNA-01 | 3AUA0000040890 |
| EtherCAT Adapter | FECA-01 | 3AUA0000040891 |
Suffix Options (added after model +xxxx)
+B063: IP66 high protection version (for humid, dusty environments)
+N830: Non-coated PCB (standard cabinet version)
+J400: Potentiometer kit
Exemplo: ACS355-03E-07A3-4+B063 (IP66 variant, different part number)
Model Code Guide for Export Selection
03E: 3-fase, EMC filter enabled (mainstream for China market) ✅
03Você: 3-fase, EMC filter disabled (60 Hz overseas version)
03X: Export special version, not common locally
01E / 01Você: Monofásico 220 V models
Replacement series: ACS380 (nova geração, successor to ACS355)