Phoenix Contact MINI MCR-SL-UI-2I Analog Signal Duplicator

Pedido nº.: 2864794, Modelo de substituição: 2905025 MINI MCR-2-UNI-UI-2UI-C Type: 4-way isolated analog signal duplicator / isolation amplifier (conexão de parafuso, custom configuration version) Core Function It accepts 1 channel of standard analog input signal and replicates it into 2 mutually independent current outputs after galvanic isolation. It realizes signal isolation, conversão, amplification, filtering and 1-in-2-out signal ...

  • Detalhes do produto

Pedido nº.: 2864794, Modelo de substituição: 2905025 MINI MCR-2-UNI-UI-2UI-C

Tipo: 4-way isolated analog signal duplicator / isolation amplifier (conexão de parafuso, custom configuration version)

Função principal

It accepts 1 channel of standard analog input signal and replicates it into 2 mutually independent current outputs after galvanic isolation. It realizes signal isolation, conversão, amplification, filtering and 1-in-2-out signal duplication. The measuring range is configured via DIP switches, with 4-way isolation (entrada / saída 1 / saída 2 / power supply isolated from each other).

Suitable for splitting transmitter signals to PLC + paperless recorder, anti-interference isolation and instrument loop distribution.

📌 Key Electrical Specifications

Fonte de energia: 19.2–30 V CC, nominal 24VDC; power consumption <600mW, current <30mA @24V (including load)

Entrada (selectable via DIP switch): 0…20mA / 4…20mA / 0…10V / 1…5V

Input impedance for voltage signal ≈100kΩ; input impedance for current signal ≈50Ω

Saída: 2 independent current outputs, 0…20mA /4…20mA; máx.. output ≈22mA; load ≤250Ω@20mA

Precisão: Máx.. transmission error ≤0.2%FS, typical <0.1%FS; temperature drift <0.01%/K

Largura de banda (-3dB): ≈35Hz; step response (0–99%) ≈10ms

Isolation test voltage: 1.5kV AC 60s between input, saída e fonte de alimentação, basic insulation per EN61010

Classe de proteção: IP20; temperatura operacional -20 ~ +60℃, storage temperature -40~85℃, sem condensação

📐 Mechanical Data

Montagem: 35mm trilho DIN (EN60715), any mounting orientation

Largura: 6.2 milímetros (ultra-slim design for dense installation); 93.1(H) ×102.5(D) milímetros

Conexão: Terminais de parafuso M3, conductor 0.2–2.5mm² (AWG26–12), stripping length 12mm

Habitação: PBT, RAL6021 green; net weight 73.3g, gross weight 89.7g

📋 Certificações

CE, UL508, Classe I Div.2, Aprovação marítima GL, II 3G Ex nA IIC T4 Gc X (explosion protection)

🧩 Series Identification & Peças de reposição

2864794: MINI MCR-SL-UI-2I made-to-order configuration, non-returnable

2864176: MINI MCR-SL-UI-2I-NC standard pre-configured version

2864804: MINI MCR-SL-UI-2I-SP special version

Matching bus base: 2869728 MEU 6,2 TBUS-2 (DIN rail power bus connector)

Matching power terminal: 2864134 MINI MCR-SL-PTB

The original part number 2864794 is no longer available for regular supply. Para novos projetos, use the replacement 2905025 MINI MCR-2-UNI-UI-2UI-C (new-generation MINI MCR-2 series, fully compatible with upgraded performance).

Application Scenarios for 2864794 (MINI MCR-SL-UI-2I)

Posicionamento central: 1 entrada analógica, galvanically isolated duplication into 2 independent 4/0–20mA current signals, 4-isolamento de caminho (Entrada / Saída1 / Fora2 / Poder), conversão de sinal + noise immunity. Ultra-slim 6.2mm width for dense cabinet layout, certified for installation in Zone 2 áreas perigosas.

  1. Split One Sensor Signal into Two Outputs (Most Common Use Case)
  2. CLP + Paperless Recorder / Data Logger

Pressão, temperatura, level and flow transmitters with only one 4–20mA output can feed the PLC for control meanwhile send a copy to the recorder for data archiving and traceability. The two outputs are galvanically isolated; a fault on the recorder side will not drag down the transmitter loop or affect control.

  1. DCS Main System + Independent SIS Safety Interlock

One process measurement point sends one signal to DCS for monitoring and the isolated second signal to the independent SIS safety loop. Physical signal separation meets the independence requirement for functional safety.

  1. Dual PLC / Dual Controller Redundant Acquisition

Primary and backup controllers acquire the same field instrument signal at the same time. Isolated dual outputs prevent cross-interference caused by ground potential difference between controllers.

  1. SCADA Host Collection + IHM local / Secondary Indicator

One channel feeds the PLC for SCADA upload, the other goes to local digital indicator or analog pointer meter for on-site display.

Input compatibility: 0/4–20mA, 0–10V, 1–5V; both outputs are current-only (0/4–20mA). Measuring ranges are freely combined via DIP switches.

  1. Ground Loop Elimination & Noise Isolation

When transmitters are installed near high-power motors, frequency converters or medium-frequency furnaces, long cable runs introduce ground potential difference and common-mode interference, resulting in signal jumping and drift. This module breaks ground loops and stabilizes analog signals.

Cross-cabinet signal transmission between cabinets with different potential (LV cabinet, Gabinete VFD, DCS cabinet). It isolates potential offset and protects PLC analog channels from common-mode overvoltage damage.

  1. Signal Type Conversion

Field transmitters output voltage signals (0–10V/1–5V), while the two downstream receiving devices only accept 4–20mA current input. This unit converts the voltage input into two isolated current outputs.

  1. Aplicações Específicas da Indústria

Químico, Tratamento de Água & Municipal Wastewater: Nível, pH, turbidez, flow and pressure. Many projects require simultaneous control and data logging; adequado para Zona 2 instalação de gabinete (Zona 2 apenas, NOT intrinsic safety barrier).

Poder & Nova Energia (VP / Armazenamento de energia / Distribuição de energia): Bus voltage, transducer signals, temperatura da água de resfriamento, split to PLC and waveform recording device.

AVAC, Automação Predial & Salas limpas: Temperatura, humidity and differential pressure transmitters, split for BA controller and independent monitoring system.

Marinho & Ferrovia (GL Marine Certificate): Cabin pressure and temperature monitoring. Ultra-slim footprint saves cabinet space for marine control cabinets.

Embalagem, Borracha & Plásticos, Máquinas-ferramentas & Automação personalizada: Tensão, pressure and displacement sensors. One output for motion control PLC, the other for quality inspection recording system.

  1. Selection Limitations & Notas
  2. Both outputs are current only, voltage output is not supported. Do not select this model if one current + one voltage split is required.
  3. It is an isolated duplication amplifier, not an intrinsically safe barrier. It cannot directly connect to IS instruments in Zone 0 / Zona 1; it may only be fitted inside Zone 2 hazardous-area cabinets.
  4. Excellent for slim cabinets and high-density I/O layouts. TBUS bus bases support daisy-chain rail power supply to reduce wiring work.

Fênix Contact Analog Signal Duplicator (1-in-2-out Signal Repeater) Order List

Two major series: Legacy MINI MCR-SL (6.2mm ultrafino, incluindo 2864794, descontinuação) and New MINI MCR-2 / MINI Analog Pro (replacement series, freely configurable current/voltage output, NFC configuration supported)

Definição: Signal Duplicator (1-in-2-out isolated repeater). Pure 1-in-1-out isolators are excluded from this table.

  1. Legacy MINI MCR-SL Series | UI-2I (UI Input, Dual Current Output 4/0–20mA)
Número do pedido.Modelo CompletoDescriçãoStatus
2864794MINI MCR-SL-UI-2ICustom configuration, non-returnableObsoleto, recomendar 2905025
2864176MINI MCR-SL-UI-2I-NCStandard pre-configured, regular stockObsoleto
2864804MINI MCR-SL-UI-2I-SPCustom configuration, non-returnableObsoleto, recomendar 2905027
2864189MINI MCR-SL-UI-2I-SP-NCStandard pre-configuredObsoleto

Common limitation for legacy models: dual outputs are current only, voltage output unavailable; 4-isolamento de caminho (Entrada / Saída1 / Fora2 / Power isolated).

  1. New MINI MCR-2 Universal Duplicator UNI-UI-2UI (Entrada universal da IU, Two Outputs Independently Configurable for Voltage or Current)
Número do pedido.Modelo CompletoTipo de conexãoDescrição
2905026MINI MCR-2-UNI-UI-2UIParafusoStandard pre-configured NC
2905025MINI MCR-2-UNI-UI-2UI-CParafusoCustom configuration C (replaces legacy 2864794)
2905028MINI MCR-2-UNI-UI-2UI-PTEmpurrarStandard pre-configured NC
2905027MINI MCR-2-UNI-UI-2UI-PT-CEmpurrarCustom configuration C (replaces legacy 2864804)

Upgrade highlights for new series: each output independently configurable as current or voltage, MERGULHAR + NFC + software configuration, diagnóstico de falhas, improved accuracy.

  1. Additional 1-in-2-out Duplicators in Family (Loop-Powered Version)
Número do pedido.Modelo CompletoDescrição
2905628MINI MCR-2-RPSS-I-2IAlimentado por loop, 1 current input, 2 current outputs, conexão de parafuso
2905629MINI MCR-2-RPSS-I-2I-PTAlimentado por loop, 1 current input, 2 current outputs, Empurrar
  1. Acessórios correspondentes (Bus Power Base for Duplicators)
Número do pedido.NomePropósito
2869728MEU 6,2 TBUS-2 1,5/5-ST-3,81 GNTBUS rail bus connector for parallel power supply, compatible with slim MINI MCR-SL
2864134MINI MCR-SL-PTBBloco terminal de energia

Quick Cross Reference for Replacement

2864794 (parafuso, personalizado) → 2905025

2864176 (parafuso, padrão) → 2905026

2864804 (spring-cage, personalizado) → 2905027

2864189 (spring-cage, padrão) → 2905028

MINI MCR-SL-UI-UI-NC (2864150): 1-in-1-out isolator, NOT a duplicator, excluded

MACX series are mostly high-withstand, SIL functional safety or explosion-proof isolators, not general signal duplicators.

Phoenix MINI MCR-2 / MINI Analog Pro Analog Signal Duplicator (1-in-2-out Isolated Repeater) Order List

Notas: MINI MCR-2 belongs to the MINI Analog Pro platform; supports NFC / programas / DIP configuration, diagnóstico de falhas, 4-isolamento de caminho. Split into universal UI input duplicator and loop-powered HART RPSS-I-2I. PT = Push-in quick connection; no PT suffix = screw connection; suffix -C = made-to-order custom configuration (non-returnable).

  1. Universal Multi-Range Type: MINI MCR-2-UNI-UI-2UI (Universal UI Input, Two Outputs Independently Selectable for Current / Tensão)
Número do pedido.Modelo CompletoDescriçãoSubstituição herdada
2905026MINI MCR-2-UNI-UI-2UIStandard pre-configured NC, regular stock2864176
2905025MINI MCR-2-UNI-UI-2UI-CCustom configuration C, parameters specified on order, non-returnable2864794 (your original part)
2905028MINI MCR-2-UNI-UI-2UI-PTStandard pre-configured NC2864189
2905027MINI MCR-2-UNI-UI-2UI-PT-CCustom configuration C, non-returnable2864804

Características: Input accepts 0/4–20mA, 0–10V, 1–5V; OUT1 and OUT2 can be independently set to current or voltage, mixed output allowed. Supports HART pass-through, NFC mobile configuration, alarme de falha, Zona 2 Ex certification.

  1. Loop-Powered Type: MINI MCR-2-RPSS-I-2I (4–20mA Loop Powered, HART Transparent, 1-in-2-out Current)
Número do pedido.Modelo CompletoTipo de conexãoDescrição
2905628MINI MCR-2-RPSS-I-2IParafusoAlimentado por loop, HART transparent, dual current output
2905629MINI MCR-2-RPSS-I-2I-PTEmpurrarAlimentado por loop, HART transparent, dual current output

Características: Powered directly from transmitter loop, independent 24V supply not required. Two passive 4–20mA outputs. Ideal for 2-wire HART transmitters, shared measurement points for DCS/SIS. Máx.. load per channel up to 500Ω.

  1. Acessórios correspondentes (General for MINI Analog Pro Platform)
Número do pedido.NomePropósito
2902066MINI MCR-2-PTBScrew-type power terminal for rail bus daisy-chain power supply
2902067MINI MCR-2-PTB-PTPush-in power terminal
2904504MINI MCR-2-FM-RCScrew fault collective alarm module
2904508MINI MCR-2-FM-RC-PTPush-in fault collective alarm module
2905634MINI MCR-2-V8-MOD-RTUModbus-RTU communication adapter, suporta até 8 modules in network
2905635MINI MCR-2-V8-MOD-TCPModbus-TCP communication adapter, suporta até 8 modules in network
  1. Orientação de seleção & Evitar armadilhas
  2. UNI-UI-2UI: Requires separate 24VDC supply, universal voltage/current input, two outputs can mix voltage + atual. Direct upgrade replacement for legacy MINI MCR-SL-UI-2I.
  3. RPSS-I-2I: Alimentado por loop, apenas entrada atual, dual current output only. Preferred for HART projects; cannot be used for voltage signal splitting.
  4. 1-in-1-out isolators of the same series (por exemplo. MINI MCR-2-UI-UI) are not duplicators and excluded from this list.
  5. Código HS: 85437090, País de origem: Alemanha (DE)