ES2008: EtherCAT 8-channel digital output terminal module, 24 CCV / 0.5 Um por canal, version with pluggable split wiring base. Its electrical performance is identical to EL2008 of beckhoff, differing only in wiring structure.
Differences Between ES / ELE / ED Versions
| Modelo | Tipo de fiação | Cenários de aplicação |
| EL2008 | Integrated screw terminals, non-pluggable | Standard fixed control cabinets with infrequent IO replacement |
| ES2008 | Split pluggable wiring base | Fast module replacement for equipment after-sales service; no cable re-crimping required |
| ED2008 | Integrated spring push-in terminals | Fiação rápida, tool-free connection |
- Especificações elétricas principais
- Channel Specifications
Output channels: 8-channel single-ended NPN digital outputs
Tensão nominal: 24 CCV (allowable fluctuation range: -15% ~ +20%)
Maximum current per channel: 0.5 UM, equipped with short-circuit protection and reverse polarity protection
Maximum total carrying capacity of power contacts: 10 UM
Permitted loads: Cargas resistivas, inductive solenoid valve loads, indicator light loads
Breaking energy: < 150 mJ per channel (compatible with small solenoid valves)
- Timing & Isolamento
Turn-on time Ton ≈ 60 μs, Turn-off time Toff ≈ 300 μs
Electrical isolation between E-bus and field loads: 500 VAC
Process image occupation: 8 output bits
- Consumo de energia
E-bus supply consumption: Típico 90 mA
Field supply: 15 mA quiescent current + load current of each channel
- Mecânico & Especificações Ambientais
Dimensões: 12 milímetros (C) × 100 milímetros (H) × 68 milímetros (D)
Peso: Aprox.. 55 g
Montagem: Padrão 35 mm trilho DIN
Classe de proteção: IP20 (cabinet installation only)
Temperatura operacional: -25 ℃ ~ +60 ℃ (montagem horizontal); máx.. +45 ℃ for vertical mounting
Temperatura de armazenamento: -40 ℃ ~ +85 ℃
Umidade: 95% RH, sem condensação
Certificações: CE, UKCA, cULus, EAC
Vibração / Shock resistance: Compatível com EN 60068-2-6 / EM 60068-2-27
- Unique Advantages of ES2008 Pluggable Structure
- The wiring base remains permanently on the cable side inside the control cabinet; the module body can be plugged and replaced separately.
- No terminal cable disassembly required for equipment fault maintenance, greatly reducing downtime.
- The base supports standard wire gauges: 0.08~2.5 mm² solid / stranded wires; 0.14~1.5 mm² for wires with cable lugs.
- Standard wire stripping length: 8~10 mm, screw-tightened terminals.
- Wiring Definition (Fully Compatible with EL2008)
Common power terminals: 24V+, 0V (unified power supply on module side)
Channel outputs: Ch1~Ch8 (Saída NPN, saídas 0 V when switched on)
Independent status LED for each channel; green light = output activated
- Cenários típicos de aplicação
- Control of machine tool solenoid valves and cylinder directional valves
- Assembly line indicator lights and alarm buzzers
- Drive of small relay coils
- Output for conveying and material stop cylinders on packaging equipment
- Production lines requiring frequent on-site IO module replacement (ES version is preferred)
- Substituição & Descrição de compatibilidade
- Direct interchangeable: ES2008 ↔ EL2008 (fully compatible in programming and EtherCAT configuration, only base structure differs)
- High-density alternative: EL4008 (16 FAZER, saves DIN rail space)
- High-current alternative: EL2024 (4 FAZER, 2 A per channel for large solenoid valve driving)
- Diagnostic-equipped version: EL2014 (4 FAZER, with short-circuit channel fault diagnosis)
- Resumo da seleção
Choose ES2008: Frequent equipment after-sales maintenance and fast IO module replacement needed
Choose EL2008: Fixed control cabinets with rare cable disassembly, menor custo
Choose ED2008: Fast on-site wiring without screwdrivers
Protection Class of Beckhoff ES2008
IP20 (Standard parameter from Beckhoff official manual)
Supplementary Explanation
- EL2008, ED2008 and ES2008 in the same series feature identical housing protection structure, all rated IP20.
- Definition of IP20 rating:
First digit 2: Prevents ingress of solid foreign objects ≥12.5 mm such as fingers
Second digit 0: No water or dust protection; must not be directly exposed to mist, dust or liquid
- Application requirement: Must be installed inside a sealed electrical control cabinet, not for bare installation outdoors, in humid or dusty environments.
- If high-protection field IO is required, select EP series EtherCAT junction boxes (IP65 / IP67).
Full List of Beckhoff ES2xxx Digital Output Modules with Pluggable Base (Matching EL2xxx specifications; ES = split pluggable wiring base)
- Padrão 0.5 A NPN Output (General Solenoid / Luz Indicadora, IP20)
| ES Model | Corresponding EL Model | Canais | Specification Description |
| ES2004 | EL2004 | 4 FAZER | 24 CCV, 0.5 Um por canal, no per-channel diagnosis |
| ES2008 | EL2008 | 8 FAZER | 24 CCV, 0.5 Um por canal, general-purpose standard model (the model you enquired about) |
| ES2014 | EL2014 | 4 FAZER | 24 CCV / 0.5 UM, per-channel short-circuit / overcurrent diagnosis |
| ES2024 | EL2024 | 4 FAZER | 24 CCV, alta corrente 2 A per channel for large solenoid valve driving |
| ES2032 | EL2032 | 2 FAZER | 24 CCV / 2 A with channel diagnosis |
| ES2034 | EL2034 | 4 FAZER | 24 CCV / 2 A with channel diagnosis |
| ES2084 | EL2084 | 4 FAZER | High-density 16 mm largura, 8-channel capacity condensed into 4 terminais |
| ES2088 | EL2088 | 8 FAZER | Ultrafino 16 mm housing, saves DIN rail space |
| ES2807 | EL2807 | 16 FAZER | High-density 16-channel 0.5 A outputs |
| ES2809 | EL2809 | 32 FAZER | High-density 32-channel 0.5 A outputs |
- ES Series with Special Voltage Outputs
| ES Model | Corresponding EL Model | Canais | Specification Description |
| ES2124 | EL2124 | 4 FAZER | 5 VDC CMOS level output, matching industrial control board signals |
- Naming Rule Distinction for ES Series (3 wiring versions with identical electrical parameters)
- ELxxxx: Integrated screw terminals, non-pluggable, standard low-cost version
- ESxxxx: Split pluggable screw base (series that ES2008 belongs to), no cable disassembly during maintenance
- EDxxxx: Integrated spring push-in terminals, fiação rápida sem ferramentas
- EFxxxx: Split pluggable spring push-in base
- General Common Parameters of ES2xxx Series
- Classe de proteção: All rated IP20, cabinet-use only
- Bus isolation: 500 VAC isolation between E-bus and field loads
- Fonte de energia: 24 VDC field power, NPN low-side output (saídas 0 V when activated)
- Funções de proteção: Proteção contra curto-circuito, proteção contra polaridade reversa, with channel status LEDs
- Mechanical width: Padrão 24 milímetros; ultra-slim 16 mm for ES2084 / ES2088
- Special DO Modules Without ES Versions in the Same Series (No Split Base Variants, ELE / ED Only)
EL2042: Saída de relé (no ES version available)
EL2062: 230 VAC triac output (no ES version available)
ELX2008: Explosion-proof intrinsically safe output (no ES version available)
TwinSAFE safety outputs EL29xx: No split-base ES variants available
Notas de Tradução
- Industry standard terms unified:
DO = Digital Output, Trilho DIN, NPN low-side output, proteção contra curto-circuito, intrinsecamente seguro, triac, quiescent current
- Beckhoff official terminology retained: E-bus, EtherCAT, TwinSAFE
- Unit symbols follow international industrial standards (CCV, UM, μs, mJ, milímetros, ℃, mm²)
- Tables maintain original structure for engineering document direct use
Contator,disjuntor,inversor solar,medidor elétrico,baterias solares