Chint NA1-3200X-3200M/3P Air Circuit Breaker

  Code Segment Description NA1 Series code for Chint air circuit breakers (ACB) 3200 Corrente nominal do quadro: 3200UM (maximum current specification of the breaker) X Breaking capacity grade: Class X (100o); distinguished from standard type (80o) and Class H (120o) 3200 Rated operating current: 3200UM (actual set working current) M Trip unit type: Intelligent trip ...

  • Detalhes do produto

 

Segmento de códigoDescrição
NA1Series code for Chint air circuit breakers (ACB)
3200Corrente nominal do quadro: 3200UM (maximum current specification of the breaker)
XGrau de capacidade de ruptura: Class X (100o); distinguished from standard type (80o) and Class H (120o)
3200Rated operating current: 3200UM (actual set working current)
MTipo de unidade de disparo: Intelligent trip unit (Micrológico); distinguished from standard Type L and high-breaking Type H
3PNúmero do pólo: 3-pólo (3-phase circuit protection, without neutral pole)
  1. Especificações Técnicas Principais
Categoria de parâmetroTechnical Data
Tipo de produtoIntelligent low-voltage air circuit breaker (ACB)
Tensão operacional nominalAC 400V/690V, 50Hz
Quadro atual (Eu)3200UM
Corrente operacional nominal (Em)3200UM
Capacidade nominal máxima de interrupção de curto-circuito (UTI)100o (Class X @ 400V)
Capacidade nominal de interrupção de curto-circuito em serviço (CIs)100o (equal to Icu)
Corrente suportável nominal de curta duração (Icw)80o (1é)
Unidade de viagemType M intelligent trip unit, featuring long-time delay overload, short-time delay short-circuit and instantaneous short-circuit protection
Tipo de montagemDraw-out or fixed type (X series is generally draw-out)
Modo de operaçãoManual or motorized (motor operating mechanism optional)
Tensão do Circuito de ControleAC 220V/380V or DC 220V (opcional)
Contatos AuxiliaresPadrão: 5NÃO + 5NC (expansível)
Proteção de entradaIP30 (compatível com GB/T 4942.2)
Applicable StandardsGB/T 14048.2, IEC/EN 60947-2
Dimensões (A×L×P)Draw-out type: aprox.. 600mm×400mm×1000mm (refer to official manual for exact data)
PesoAprox.. 80~100kg (varies by mounting type and accessory configuration)
  1. Recursos principais

3.1 Intelligent Protection System

Three-stage protection: Long-time delay for overload (inverse time characteristic), short-time delay for short circuit (selectable fixed/inverse time), and instantaneous short-circuit protection, precisely matching power distribution system requirements.

Earth fault protection: Residual current protection optional, sensitivity adjustable from 0.03A to 1A.

Adjustable protection parameters: Flexible parameter configuration via intelligent controller to adapt to diverse load characteristics.

Gravação de falhas: Automatically stores the latest 10 fault records including fault type, current value and time for rapid troubleshooting.

3.2 High Reliability Design

High Class X breaking capacity: 100kA short-circuit breaking capacity to ensure reliable disconnection under severe short-circuit faults and guarantee equipment safety.

Optimized arc extinguishing system: Adopts multi-break and longitudinal seam arc extinguishing technology for rapid arc extinction and fast recovery after breaking.

Longa vida útil: Mechanical durability up to 10,000 operações; electrical durability up to 5,000 operações.

Vibration and shock resistance: Compatível com GB/T 14048.2 to adapt to harsh industrial environments.

3.3 Expansibilidade flexível

Rich optional accessories: Viagem de manobra, disparo por subtensão, closing solenoid, motor charging mechanism, contatos auxiliares, contatos de alarme, key lock, etc..

Extended communication: Optional Modbus-RTU, Profinet, EtherNet/IP modules for remote monitoring and intelligent power distribution management.

Interlock functions: Cable interlock and connecting rod interlock available to meet electrical and mechanical interlock requirements.

  1. Compatible Equipment & Cenários de aplicação

Compatible Equipment

Distribution transformer: Main protection switch for low-voltage side of transformers

Generator set: Protection switch for generator outgoing circuits

Busbar system: Bus section protection and tie control

Large motor: Incoming switch for Motor Control Center (MCC)

UPS system: Protection switch for UPS input and output circuits

Cenários de aplicação

  1. Distribuição de energia industrial: Main power distribution systems for factories, workshops and production lines.
  2. Commercial building power distribution: Main and floor power distribution for shopping malls, hotels and high-rise buildings.
  3. Centros de dados: Mission-critical areas requiring high power supply reliability such as server rooms and cloud computing centers.
  4. New energy industry: Low-voltage power distribution systems for photovoltaic power stations and wind farms.
  5. Infrastructure: Power distribution systems for transportation hubs including airports, subways and railways.
  6. Comparação de modelos
ModeloQuebrando CapacidadeCorrente nominalUnidade de viagemAplicativo
NA1-3200-3200M/3P80o (Padrão)3200UMType M IntelligentGeneral industrial distribution with low short-circuit current
NA1-3200X-3200M/3P100o (Class X)3200UMType M IntelligentIndustrial sites with high short-circuit current and high breaking capacity requirements
NA1-3200H-3200M/3P120o (Class H)3200UMType M IntelligentLarge industrial enterprises and grid connection points with extreme short-circuit current
NA1-3200X-2500M/3P100o (Class X)2500UMType M Intelligent3200A frame with actual load current of 2500A
NA1-3200X-3200L/3P100o (Class X)3200UMType L StandardGeneral scenarios with basic protection demands
  1. Cross-Brand Equivalent Model Comparison
ChintSiemensSchneiderABBMitsubishi
NA1-3200X-3200M/3P3WL2N32 ETU25B 3PMT32H1 3P 3200A Micrologic 5.0EMAX2 E3S3200 R100 3PAE3200-SW 3P F 3200A
Quebrando Capacidade100o100o100o85o
Unidade de viagemType M IntelligentETU25B IntelligentMicrológico 5.0 InteligenteStandard Intelligent Trip
Tipo de montagemDraw-out / FixoDraw-out / FixoDraw-out / FixoDraw-out / Fixo
ComunicaçãoOptional Modbus / ProfinetOptional Profinet / Ethernet/IPOptional Modbus / ProfinetOptional CC-Link / Profinet
  1. Seleção & Application Guidelines
  2. Correspondência de capacidade de ruptura: Select proper grade according to system short-circuit current calculation (Standard 80kA, Class X 100kA, Class H 120kA).
  3. Rated current selection: Determine operating current based on total load current and future expansion; optional ratings under 3200A frame: 2000UM, 2500UM, 3200UM.
  4. Trip unit selection: Type M intelligent trip for most industrial and commercial applications; Type L standard trip for simple protection requirements.
  5. Tipo de montagem: Draw-out type for easy maintenance and replacement (critical circuits); fixed type for cost-effective general circuits.
  6. Modo de operação: Manual for small-capacity and infrequent operation; motorized for large-capacity, frequent operation and remote control.
  7. Configuração de acessórios: Select shunt trip, disparo por subtensão, auxiliary contacts and communication modules as required by control and protection logic.
  8. Manutenção: Regularly inspect mechanical mechanisms, arc extinguishing chambers and contact wear to ensure long-term stable operation.

Chint NA1-3200X-3200M/3P Complete Accessory List & Selection Codes

  1. Core Control Accessories (Essential for Control Circuit)

1.1 Viagem de manobra (F)

Used for remote breaker tripping, applicable to emergency shutdown and automatic control systems.

TipoModeloTensão nominalConsumo de energiaAplicativoSelection Code
Contínuo (Default)NA1-F-3200XAC220V/230V460VA(AC220V)Controle industrial geral, infrequent operationF-AC220
AC380V/400V400VA(AC380V)F-AC380
CC110V70C(CC110V)F-DC110
DC220V140C(DC220V)F-DC220
Pulse Type (Recomendado)NA1-FP-3200XAC220V/230V880VA(AC220V)Wind & solar power, ATS system, frequent operationFP-AC220
AC380V/400V1800VA(AC380V)FP-AC380
CC110V850C(CC110V)FP-DC110
DC220V880C(DC220V)FP-DC220

Selection Note: Pulse type: single power-on duration ≤ 2s, máx. 5 times/min; Continuous type: single power-on duration ≤ 2s to avoid component burnout.

1.2 Desarme por subtensão (Q)

Automatically trips the breaker under low grid voltage to prevent equipment overload damage.

TipoModeloTensão nominalOperating CharacteristicDelay TimeSelection Code
Instant Suction (Default)NA1-Q-3200XAC230VTrip at 70% Us, reliable trip at 35% UsInstantQ-AC230
AC400VQ-AC400
Delayed SuctionNA1-QD-3200XAC230VIgual ao acima1s/3s/5s (Fixo)QD-AC230-1s
AC400VQD-AC400-3s
Self-suction DelayNA1-QZ-3200XAC230VIgual ao acima0.3s~7.5s (Ajustável)QZ-AC230
AC400VQZ-AC400
Under-voltage Delay (UVTZ-1)NA1-UVTZ-1AC230VAutomatic reclosure after voltage recovery1s/3s/5sUVTZ-1-AC230
AC400V

Selection Note: 3200A frame adopts instant suction type as standard; self-suction type features wider delay range for voltage-fluctuation-sensitive equipment.

1.3 Closing Solenoid (X) / Closing Coil

For remote closing, matched with motor charging mechanism.

TipoModeloTensão nominalConsumo de energiaAplicativoSelection Code
Pulse Type (Mandatory for ATS)NA1-X-3200XAC220V/230VSame as shunt tripAutomatic control system, frequent closingX-AC220
AC380V/400VX-AC380
CC110VX-DC110
DC220VX-DC220

1.4 Motor Charging Mechanism (M)

Stores energy for breaker closing and provides closing power.

ModeloTensão nominalPoderCharging TimeSelection Code
NA1-M-3200XAC220V/230V0.37kW≤15sM-AC220
AC380V/400VM-AC380
CC110VM-DC110
DC220VM-DC220
  1. Controle Inteligente & Communication Accessories

2.1 Intelligent Controller Upgrade

Type M is standard; upgraded versions with enhanced functions are optional.

ModeloCaracterísticasAplicativoSelection Code
Type 3MAdded voltage measurement and harmonic analysisPower quality monitoring required3M
Type HAdvanced protection with extended parameter settingsComplex power distribution systems & precise protectionH
Type 3HHighest configuration, full 3M+H functions + event loggingCritical circuits & fault analysis3H

2.2 Communication Modules (Monitoramento Remoto)

Module TypeModeloProtocolFunçãoMatching ComponentSelection Code
Modbus-RTUNA1-COM-MODModbus-RTUData acquisition & remote controlNot requiredCOM-MOD
Profibus-DPNA1-COM-DPProfibus-DPIndustrial fieldbus communicationST-DP protocol moduleCOM-DP+ST-DP
ProfinetNA1-COM-PNProfinetEthernet communicationPSU-1 power moduleCOM-PN+PSU-1
Ethernet/IPNA1-COM-ENIPEthernet/IPEtherNet/IP communicationPSU-1 power moduleCOM-ENIP+PSU-1

2.3 Auxiliary Functional Modules

NomeModeloFunçãoAplicativoSelection Code
Power Supply UnitPSU-1Stable power supply for communication modulesMandatory for all Ethernet modulesPSU-1
Relay ModuleRU-1Signal amplification & contact expansion (AC250V/10A, DC28V/10A)High-power load controlRU-1
Under-voltage Delay ControllerUVTZ-1Delayed trip during temporary low voltageVoltage-sensitive equipmentUVTZ-1
  1. Auxiliary Contact System (Indicação de status & Controlar)

NA1-3200X standard configuration: 4 sets of transfer contacts (4NO+4NC), expansível.

TipoModeloConfiguração de contatoAvaliaçãoAplicativoSelection Code
3 sets TransferNA1-AX-3Z3NO+3NCAC230V/5ABasic controlAX-3Z
4 sets Transfer (Default)NA1-AX-4Z4NO+4NCAC230V/5AConfiguração padrãoAX-4Z
5 sets TransferNA1-AX-5Z5NO+5NCAC230V/5AExtended controlAX-5Z
3NO+3NCNA1-AX-333NO+3NCAC230V/5ACustom control logicAX-33
4NO+4NCNA1-AX-444NO+4NCAC230V/5AConfiguração padrãoAX-44
5NO+5NCNA1-AX-555NO+5NCAC230V/5AComplex controlAX-55
6NO+6NCNA1-AX-666NO+6NCAC230V/5AOnly for Type M controller, cannot match suction undervoltage delayAX-66
  1. Intertravamento Mecânico & Safety Accessories

4.1 Intertravamento Mecânico (Misoperation Prevention)

TipoModeloFunçãoAplicativoSelection Code
Connecting Rod InterlockNA1-LK-LGMutual interlock for two breakers to prevent simultaneous closingBus tie & ATS systemLK-LG
Cable InterlockNA1-LK-GLRemote mechanical interlock, standard cable length: 2euATS system with large cabinet spacingLK-GL
Key LockNA1-KEYMultiple configurations: 1-lock-1-key, 2-lock-1-keyUnauthorized operation preventionKEY-1-1
KEY-2-1
Button LockNA1-BLLock closing/tripping buttonsAccidental touch preventionBL

4.2 Door Interlock

TipoModeloFunçãoAplicativoSelection Code
Position Door InterlockNA1-DL-WZCabinet door locked at test/connected positionDraw-out breaker, electric shock preventionDL-WZ
Status Door InterlockNA1-DL-ZTCabinet door locked when breaker closedLive operation prevention for all typesDL-ZT

4.3 Other Safety Accessories

NomeModeloFunçãoAplicativoSelection Code
Transparent Protective CoverNA1-TPIP54 protection for operating mechanismDust environments & safety enhancementTP
CounterNA1-CTMechanical operation countingFrequent circuits & predictive maintenanceTC
Position IndicatorNA1-PSDraw-out position indication (Disconnect/Test/Connected)Draw-out breaker status monitoringPS
Phase BarrierNA1-PSBIsolate three-phase busbars to prevent phase short circuitInsulation improvementPSB
  1. Montagem & Connection Accessories

5.1 Main Circuit Accessories

NomeModeloAvaliaçãoAplicativoSelection Code
Horizontal BusbarNA1-BUS-H3200UMStandard horizontal wiringBUS-H
Vertical L-type BusbarNA1-BUS-V3200UMInstalação vertical & space savingBUS-V
Rotatable BusbarNA1-BUS-R3200UMFlexible wiring for draw-out breakersBUS-R

5.2 Secondary Circuit Accessories

NomeModeloFunçãoAplicativoSelection Code
Secondary ConnectorNA1-SPSecondary circuit connection for draw-out breakersQuick plug & unplugSP
Control FuseNA1-FU6UM, control circuit protectionMandatory for all control loopsFU-6A
  1. Complete Configuration Example

Exemplo:

NA1-3200X-3200M/3P, motorized draw-out type, AC220V, with shunt trip / disparo por subtensão / closing solenoid + 5 sets transfer contacts + Profinet communication + connecting rod interlock

Complete Order Model:

NA1-3200X-3200M/3P Motorized Draw-out AC220 F-AC220 Q-AC230 X-AC220 AX-5Z COM-PN+PSU-1 LK-LG

  1. Accessory Application Notes
  2. Unified control voltage: Use identical voltage for shunt trip, disparo por subtensão, closing solenoid and motor charging mechanism to simplify wiring.
  3. Communication matching: PSU-1 power module required for Profinet/EtherNet/IP; ST-DP module required for Profibus-DP.
  4. Auxiliary contact capacity: 5A@AC230V; use RU-1 relay module for high-power load control.
  5. Undervoltage trip requirement: Undervoltage trip coil must be powered on before breaker closing.
  6. Shunt trip specification: Single energization time ≤ 2s, frequency ≤ 5 times/min to avoid overheating damage.

 